Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹7.5 LAccepted-AOC | L1 | Accepted-AOC L1 | |
| 2 | L2₹8.6 L+₹91,470 (11.9%)Rejected-Finance SHIV BARI ROAD NEAR KASUMAL HOTEL BIKANER 334003 RAJASTHAN | BIKANER | BIKANER | RAJASTHAN | 334003 | L2 | Rejected-Finance L2 | |
| 3 | L3₹9.9 L+₹2.2 L (28.7%)Rejected-Finance | L3 | Rejected-Finance L3 |
Tender Value
₹10.0 L
EMD Value
₹20,000
Closing Date
7 Sept 2023, 6:00 pmClosed
AGE (I) Kanasar
Assistant Garrison Engineer (I) Kanasar, Bikaner Military station kamasar, Bikaner (Raj)
REPAIR / MAINTENANCE OF ELECTRIFICATION INCL REPLACEMENT OF LT CABLE,FEEDER PILLAR AND ALLIED WORK AT ZONE A AT MIL STN KANASAR
2023_MES_594910_3
CA NO. AGE (I) KNS/Token No. 10/2023-2024
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
AGE(I) Kanasar
Contractor shall be enlisted with MES in Class E and above and category b(i) subject to satisfactory remarks wrt performance in respect of works in hand as reflected in Work Load Return (WLR) of any other report circulated by competent engineer
8 documents required · 8 mandatory
₹500
Assitant Garrison Engineer (I) Kanasar
₹20,000
2 Nov 2023
10 Aug 2023
11 Sept 2023
10 Aug 2023
7 Sept 2023
24 Aug 2023
10 Aug 2023 - 17 Aug 2023
Amount
Supply and fixing in replacement Indicator Lamp LED type (R-Y-B) 240 V, AC, single phase, on existing LT panel, complete all as specified and directed.
M & L for taking out the existing unsv Voltmeter and Supply & fixing in replacement Digital type Volt Meter 96 mm x 96 mm, of range 0-500 volts, class -1, incl internal wiring with 1.0 sqmm single core PVC wire complete all as specified and directed.
M & L for taking out the existing unsv Ammeter and Supply & fixing in replacement Digital type Ammeter 96 mm x 96 mm, single phase , range up to 0-600 Amp, class -1, incl internal wiring with 1.0 sqmm single core PVC wire complete all as specified and directed.
Preparation of surface of existing panel of size not more than 1.2 m x 0.30m x 1.2m , mounted on angle iron frame not more than 30 cm height by scratching and complete removing of existing paint and M & L for spray painting the existing panel outside and inside of approved shade with two coat of synthetic enamel paint complete all as specified and directed.
Preparation of surface of existing panel of size not more than 0.9 m x 0.30m x 0.9m , floor mounted by scratching and complete removing of existing paint and M & L for spray painting the existing panel outside and inside of approved shade with two coat of synthetic enamel paint complete all as specified and directed.
Material and labour for repairing of existing LT panel by welding, replacing of 06 Nos of broken hinges as per existing size all as directed.
Supply and fixing in replacement of aluminium strip 25 mm x 3.15 mm as earthing strip including connecting with nut, bolts etc complete all as specified and directed
M&L for earthing complete with galvanized steel earth plate electrode size 600 mm x 600 mm x 6.3 mm thick buried directly in ground vertically in a pit of depth not less than 2.25 mtr below ground levels with top edge of the earth plate not less than 1.5 mtr below normal ground level surrounded from all sides by mixture of charcoal and common salt and electrode connected to and including galvanized iron strip 25 x 4 mm as earthing lead and GI protection pipe light grade 40 mm dia connected to main earth strip on panel or control board and 20mm dia GI pipe light grade with wire meshed funnel for watering of earthing electrode bore for watering funnel with wire mesh. RCC cover with frame, PCC chamber pit with PCC 1:3:6 type C-2 excavation and earth work all as shown in electrical plate No 3 connected to earthing test point all as specified or indicated including testing on completion complete all as specified and directed. Note:-The unit rate includes for protection pipe and GI strip from top of earth plate up to 7.5 meter above ground level.
Supply and fixing 240V, 10 KA 'C' curve MCB SP 5 to 32 AMP, in (In accordance with IS/IEC 60898-1 & IS/IEC 60947-2) 240 V/415 V, 50 Hz, 10 kA curve rating ISI marked and fecilitate safety terminals, bistable clip,Large cable terminal,precise hammer action,grooves for cooling and trip free mechanism and making all connection complete all as specified and directed
Supply and fixing 240V, 10 KA 'C' curve MCB SPN 32 AMP, in (In accordance with IS/IEC 60898-1 & IS/IEC 60947-2) 240 V/415 V, 50 Hz, 10 kA curve rating ISI marked and fecilitate safety terminals, bistable clip,Large cable terminal,precise hammer action,grooves for cooling and trip free mechanism and making all connection complete all as specified and directed
Supply and fixing 240V, 10 KA 'C' curve MCB SPN 40 to 63 AMP, in (In accordance with IS/IEC 60898-1 & IS/IEC 60947-2) 240 V/415 V, 50 Hz, 10 kA curve rating ISI marked and fecilitate safety terminals, bistable clip,Large cable terminal,precise hammer action,grooves for cooling and trip free mechanism and making all connection complete all as specified and directed.
Supply And fixing MCB TPN 63 Amps (In accordance with IS/IEC 60898-1 & IS/IEC 60947-2) 240 V/415 V, 50 Hz, 10 kA curve rating ISI marked and fecilitate inscription window, safety terminals, bistable clip,Large cable terminal,positive contact indication and auxiliary and making all connection complete all as specified and directed.
Supply installation, commissioning and testing in replacement of MCCB 800 Amp ( fixed on existing panel) 415 volt, 4 pole, 50 KA breaking capacity with adjustable current range for overload protection and thermal release complete with spreader terminals all as specified & directed.
Descriptions all as per Srl item No '14' above but 630 Amps, Breaking capacity 50 KA .
Descriptions all as per Srl item No '14' above but 400 Amps, Breaking capacity 36 KA .
Descriptions all as per Srl item No ‘14’ above but 250 Amps, Breaking capacity 36 KA.
Descriptions all as per Srl item No '14' above but 200 Amps, Breaking capacity 25 KA.
Descriptions all as per Srl item No '14' above but 160 Amps, Breaking capacity 25 KA .
Descriptions all as per Srl item No '14' above but 125 Amps, Breaking capacity 16 KA .
Descriptions all as per Srl item No '14' above but 25 to 100 Amps,3 pole,fixed type, 415 volts, 16 KA breaking capacity.
Disconnecting the electric connection and draw out Air circuit Breaker (ACB) carefully of any make of capacity upto 3200 Amps for servicing the ACB by removing dust, cleaning and checking the serviceability of the parts and testing, refixing it after servicing at the original position all as directed by Engr In Charge.
Supply installation, commissioning and testing in replacement of ACB 1250 Amp ( fixed on existing panel) 415 volt, 4 pole with thermal magnetic release(manual Fixed type) complete with spreader terminals all as specified & directed.
Disconnecting and taking out underground cable ,dismantle LT cable of following sizes of length not more than 5 mtr and locating the fault with fault locating machine and cutting the faulty damaged portion of cable ,making with new straight through jointing kit with suitable size , including excavation, returning filling and all connected materials complete all as specified and directed. (Note:-Necessary excavation , sand cushioning ,cable cover as bricks etc beyond 5 mtr should be measured and paid separately)
3.5/4 core 50 to 95 Sqmm.
3.5/4 core 120 to 185 Sqmm.
3.5/4 core 240 Sqmm.
3.5/4 core 300 Sqmm.
Cutting the faulty/ damaged end portion of the U/G cables of any type and making good end termination with and including suitable size of aluminium thimble duly crimped with crimping tool and refixing its own position ,including Insulation tape, nut ,bolts etc as reqd for the following sizes.( Necessary Excavation,relaying of cable, sand and old bricks included in quoted rate.)
10 Sqmm to 16 sqmm.
25 Sqmm to 35 sqmm .
50 sqmm to 70 Sqmm .
95 sqmm to 120 Sqmm.
150 Sqmm to 240 sqmm .
300 Sqmm to 400 sqmm .
S & F 1100 volts grade heavy duty flat cable of the following sizes , pvc insulated aluminum solid conductor , served with inner sheathing of pvc tape and overall PVC sheathed in service connections suspended by insulating hangers not more then 1 mtr apart including replacing 4 mm suspension wire , as directed by Engr-In-Charge.
(a) 4 sq mm x2 core
(b) 6 Sqmm x2 core
(c )10 Sqmm x2 core
(d) 16 Sqmm x2 core
S&F Ultra heavy duty power capacitor enclosed box type 3 phase having the technical specification :- 480V-25KVAr-30.07A, 440V-21.01 KVAr – 27.57A,415V-18.69 KVAr-26.00A, 3 x 115.1 Mfd, 50Hz, App, Ui 3/Kv as per IEC 30931:2002, 13585: 2012 including disconnecting & taking down old unserviceable etc complete all as specified & as directed.
S&F in replacement bus bar chamber type of size 50x50x40 cm (Box size) with MCCB100 Amps, capacity and 16 KA breaking capacity, bus bar chamber having 4 wire 415 Volts, factory made dust proof vermin proof for outdoor using made out of CRCA sheet 3.15mm thick power coated, machine pressed, single side opening, provision of rubber beading and locking system, including aluminium bus bar of 200 Amp capacity (considering 1 Sqmm = 1Amps) 4 strip mounted on DMC/epoxy insulator, bus bar chamber shall be provided with inspection cover, penal shall be mounted on angle iron frame and legs made from angle of size 40x40x6mm, frame and legs duly spray painted internally and externally with two coats of synthetic enameled paint over a coat of red oxide primer, leg grouted in PCC (1:3:6) type C1 (using 20 mm graded crushed stone aggregate). Note : Cost of MS frame work, painting, platform, locking arrangement with lock and key and any minor addition/alteration required at site shall be deemed to be included in the quoted rates.
Repair & maintenance of 600 KVAr APFC panel, compartmentalized, Indoor Floor mounted and replacing the defective parts, neccesary wiring & its insulation and make it complete operational upto full capacity with automation and making necessary adjustments with ACB panel complete At Aakash Sub station as specified and directed. Note:- The quoted rate of the contractor includes for fixing the serviceable parts in position and replacement of unserviceable parts with new parts. The new replaced parts shall be measured and paid separately under appropriate item of Sch 'A' (29.01 to 29.12) as supply only.
APFC microprocessor control relay 12 step ICT For 600 KVAr
Current transformer of 3000/5 ratio,resin cast
Step protection MCCB,3 Pole,415 V, 250 A,36 kA breaking capacity as per existing.
Step protection MCCB,3 Pole, 415V,125 A, 16 kA breaking capacity as per existing.
Step protection MCCB,3 Pole,415V, 63 A, 16 kA breaking capacity as per existing.
Capacitor duty contactor with damping resistors for 100KVAr with aux cont
Capacitor duty contactor with damping resistors for 50 KVAr with aux cont
Capacitor duty contactor with damping resistors for 25 KVAr with aux cont
25 KVAr Heavy duty Capacitor Square type.
3 Phase HD Harmonic Detuned filter reactor(copper wound), 50 KVAr,7%,440 V, Class H
OT Switch disconnector handle For 125A MCCB
LED Indicator(R,Y,B)
M & L for LT Danger notice plate of size 20 X 15 cm of 1.6 mm thick mild steel sheet, vitreous enameled white, with letters, figures, and conventional skull and bones, in signal red colour and fixed with MS CLAMPS, bolts, and nuts of approved size.
Excavation in trenches not exceeding 1.5 m wide and not exc. 1.5 m depth for laying cables, foundation for pole etc and getting out in soft/loose soil complete all as directed.
Removing excavated material to distance n. exc 50m and depositing where directed at a level n. exc 1.5m above the starting point complete all as directed.
Returning filling in incl spreading leveling watering and well ramming in layers n. exc 25cm thick complete all as directed.
Material & labour cement concrete 1:4:8 type D-2 using 40 mm graded crushed stone aggregate as in foundation complete all as specified and directed by Engineer- in-charge.
Material & labour PCC 1: 3 : 6 type C-1 (using 20 mm graded mechanically crushed stone aggregate) as in mass concrete including necessary form work complete all as specified and directed.
M&L for PCC 1:2:4 type B1 using 20 mm graded stone aggregate as in coping and the like including weathering slightly rounded or chamfered angles complete all as specified and directed.
Supply and fixing wire netting of galvanised steel wire, 1.40mm dia of mesh size 12 mm for protection of transformer/panel inside Sub station from outside reptile,rabbit and pigeon to cover window etc complete as specified and directed.
M/s Rohit Construction Co.
Aman Enterprises
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .