Loading…
India Infra Updates on WhatsApp
Join the Tenderkart WhatsApp channel for India Tender Updates
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Fee/PreQual/Technical/Finance | Admitted-Fee/PreQual/Technical/Finance |
| 2 | Admitted-Fee/PreQual/Technical/Finance | Admitted-Fee/PreQual/Technical/Finance |
| 3 | Admitted-Fee/PreQual/Technical/Finance 260 DEFENCE COLONY FLYOVER MARKET NEW DELHI NEW DELHI 110024 SOUTH DELHI DELHI 110024 | SOUTH EAST DELHI | DELHI | 110024 | Admitted-Fee/PreQual/Technical/Finance |
| 4 | Admitted-Fee/PreQual/Technical/Finance | Admitted-Fee/PreQual/Technical/Finance |
| 5 | Admitted-Fee/PreQual/Technical/Finance | Admitted-Fee/PreQual/Technical/Finance |
Tender Value
₹2.2 Cr
EMD Value
₹4.3 L
Closing Date
16 Jun 2023, 11:00 amClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
General Manager/Estate
5th Floor, Shikhar, RITES Limited, Plot No. 1, Sector-29, Gurgaon- 122001
Supply, Installation, Testing And Commissioning of 100 TR Air Cooled Chiller For 6th Floor At RITES Ltd. Shikhar, Plot No. 1, Sec-29 Gurugram, Haryana-122001
2023_RITES_155822_1
RITES/ES/SHIKHAR/CHILLER/2023
Open Tender
Construction Works
Works
274 days
RITES Ltd. Shikhar, Sec-29
Please refer Tender Document
10 documents required · 10 mandatory
₹7,000
RITES Ltd.
₹4.3 L
19 Jun 2023
31 May 2023
19 Jun 2023
31 May 2023
16 Jun 2023
8 Jun 2023
Amount
Total Amount of BoQ 2
Amount after unconditional Rebate
Description of Work / Item(s)
Amount
Total of BoQ 3 and BoQ 4
Total Amount of BoQ3 (Item Rate)
Total Amount of BoQ4 (Percentage Rate)
Description of Work / Item(s)
Amount
Schedule - (B) Bill of Quantites for Non Schedule Items (MR ITEMS)
Air cooled Screw Chiller
NS-1 Supply, Installation, Testing and Commissioning of AHRI Certified Air cooled Screw Water chillers complete with air cooled Copper Aluminium condensers, Single/ multiple Compressors, Single/ multi circuit Chiller, refrigerant R-134a, microprocessor based Control system, Electrical panel, mounting frame works, vibration isolators, integral refrigerant piping and wiring, all required accessories, automatic & safety controls, advanced microprocessor based control panel along with required hardware & software for integration with a 3rd party BMS (Open protocol), star delta starter, compressor shall be of the chiller supplier only i.e. outsourced compressor shall not be acceptable. The condenser shall be mandatory coated with goldfin or epoxy or equivalent coating. ASME Stamped evaporator first charge of refrigerant and oil, incommer switchgear with terminations box suitable for terminations of XLPE AL armoured cables, earthing terminations etc. all mounted on a steel frame, foundation bolts nuts and accessores complete duly finished as per manufacturer standard as required & as per technical specifications with the following charactreistices complete as required :
Chiller
Cooling Capacity : 100 TR (Actual)
Air Entering in Condenser : 110F
Chilled water in : 54 °F
Chilled water out : 44 °F
Chilled water flow : 240 USGPM
Fouling factor : 0.0005 FPS
IKW at design condition : 1.44 (Max)
NPLV at design condition : 0.90 (Max)
Chiller shall be preffered with ECBC Plus Compliant
a) The price quoted shall include pre shipping inspection / testing at the works of the manufactorer Freight, Insurance, Port clearance, loading / unloading, Installation, testing and commissioning as per specifications.
Factory Testing
Chiller will be run tested at 100% load at prevaling condition before despatch.
Lot- water flow switches at inlet and outlet of chiller
Lot- Cushy Foot type Vibration Isolator for mounting arrangement
Initial / first charge of refrigerant gas and compressor oil from factory
Chiller shall be factory tested in front of client before dispatch.
Shop drawing of Chiller base foundation to be installed on terrace need to be submitted before fabrication for approval.
Complete water chilling machine as above.
NS-2 Primary Chilled Water Pump
Supply, installation, testing and commissioning of PN16 rated primary chilled water pump with CI Casing, Bronze/SS Impeller, SS shaft, Outside/Inside Type balanced Mechanical Seal(to be easily replaceable without disburing the pump and motor shaft), each pump capable of delivering the specified flow rate comprising the following and complete as per specifications. Pumps shall be BMS compatible.
i) Vertical Inline Axial Split Coupled centrifugal pump
ii) Suitable HP, Motor Efficiency shall be IE3, class `F' insulation operating on 415 + 10% volts, 3 phase, 50 cycles AC supply. Motor up to 7.5 kw shall be strictly with IE3 efficiency.
Note: Contractor must provide necessary vibration isolation arrangement, if required.Suction Guide to be provided by Pump manufacturer for unit responsibility.Triple Duty Valve to be provided by Pump manufacturer for unit responsibility
NS-2.1 Primary Chilled water pumps
Water flow rate : 240 USGPM
Head : 90 ft.
RPM : 2900 rpm
Motor HP : 10.0 HP(suggested) or as per OEM standard
Efficiency : 75 % or above
Pumps as mentioned above (1W+1S)
ASME Expansion Tank and Dirt Air Separator
NS-3.0 Supply, installation, testing & commissioning of PN 16 rated and ASME stamped Closed Loop Expansion tank and Dirt Air Separator with strainer, auto airvent, insulaton, necessary pneumatic devices and Pressurization unit with two pumps (1W+1S), pressure switch & other accessories, the control panel should also be included as per followings. ASME expansion tank and dirt air separator must be sourced from pump manufacturer same as chilled water make for unit responsibility.
NS-3.1 500 Litres ASME stamped Expansion Tank
NS-3.2 125mm ASME stamped Dirt & Air Separator
Cooling Tower (Induced draft)
NS-4.0 Supplying, installing, testing & commissioning of CTI certified induced draft vertical out-door type FRP cooling tower (350 TR) of stated heat rejection capacity with fiber glass reinforced water basin, PVC fillings with integral louvers and drift eliminators complete with hot water basin, spray system comprising of GI pipe & brass nozzle,either fitted with statically & dynamically balanced axial flow type fan-direct driven or driven through reduction gear box with VFD operated TEFC induction motor having IP-65 protection and IE-3 rated, suitable for operation at 415 ± 10% voltage, 50 Hz A/C 3 phase supply.The outdoor noise criterion for cooling towers, at a distance of 50 meters from the fan shall be NC-45.Therefore, noise level in open areas 50 meters away from towers in any direction shall not exceed 60 DB.The structure of the cooling towers shall be designed for wind and other loads as per IS: 875. The steel structural base design to be provided seperately.
The cooling tower shall be complete with powder coated suction screen, make up quick fill arrangement, overflow and drain connections with necessary valves, fan guard and suitable inspection ladder, access arrangement for cooling tower interior, cement concrete foundation, steel/ masonary supporting structure, anti-vibration/spring mountings etc. complete as per CPWD 2017 specifications and as required. Note: The bidder should quote thier rate including dismantling/ removal of old existing colling tower and its scrap from site.
Water Leaving Temperature : 32.0 Deg C
Water Entering Temperature : 37.0 Deg C
Ambient Monsoon Wet Bulb Temperature for Gurgaon: 28.3 Deg C
Water Flow Rate : 1200 USGPM
Cooling Tower as above (2 Working+1 Standby)
NS-5.0 Make-Up Water Tank for Cooling Tower
Supplying, installing, testing & commissioning of sintex water tank for make up water for cooling tower at terrace.All valves acesessaries shall be complete as required.
NS-5.1 5000 lts
NS-6.0 Supplying, fixing, testing and commissioning of following valves, strainers, gauges in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported as per specifications. Butterfly Valve(Manual) with C I body SS Disc, Nitrile rubber Seal & O- Ring PN 16 pressure rating for chilled water/hot water circulation as specified
NS-6.1 250 mm Dia
NS-7.0 Balancing Valve with built in measuring facility with C I body flanged construction with EPDM coated disc with long pitch with protected out pipe insulation & PN 16 pressure rating for chilled / hot water circulation as specified.
NS-7.1 250 mm Dia
NS-8.0 Providing, fixing, testing & commissioning of resilient rubber lined double arch vibration eliminators suitable for raw water up to 45 deg. C temperature to provide relief from stresses at pipe flanges. It should be complete as per manufacturer's specifications & as directed by Engineer- in-charge.(PN 16 rating)
NS-8.1 100 mm dia.
Auto Air Vent Valves
NS-9.0 Providing and fixing auto airvent purging valve complete as per specification and drawings. 25mm dia
Pot Strainer
NS-10.0 Supplying, installation, testing and commissioning of Pot strainer. Pot Strainers body shall be fabricated out of MS plate IS 226. Thickness of sheet shall be as per size of the strainer chamfered pipes with flanges shall be provided at inlet /outlet connections of the strainer. A powerful magnet shall be provided in the body to arrest MS particles. Filter element of Pot Strainer shall be of non magnetic 18 gauge SS sheet properly reinforced to avoid damage of the element.A set of MS flanges with tongue and groove arrangement and neoprene rubber gasket shall be provided on the top cover and Pot Strainer flange with sufficient bolts and nuts to make the joint water light. The Pot strainer body shall be properly de-rusted and epoxy coated from inside and outside.
NS-10.1 Connection Size 250 mm dia (for Condenser water line)
NS-11 Sevicing of Air handling units
Sevicing of Air handling units shall includs following items
To Change of pre filters size 600mmx600mm =12 nos (As per Technical specification)
To Descaling of Existing Cooling Coil
Chemical cleaning of Coils of AHU
Repaire & pressure testing of leaked / Damaged Cooling Coil
Check & balancing of Fan section / Blower
Anti corrssioin Coating of Coil
NS-11.1 For 16400CFM
NS-11.2 For 14000CFM
NS-11.3 For 5600CFM
NS-12 Electronic Air Cleaner (EAC)
Supply, installation, testing, commissioning, and handing over of a central air cleaning system with high filtration efficiency on PM2.5 combined with a high kill rate on airborne infectious diseases using Ultraviolet Germicidal Irradiation. The system shall be designed for providing protection from airborne infection and maintaining Indoor Air Quality in AHU unit with the following features and technical specifications. It should be a Monobloc structured interconnectable units to form array of air cleaners specifically designed for integration in Return Air path, to centrally capture and kill germs and to improve indoor air quality. The unit shall include activated carbon filtration and UV-C light that together eliminate harmful gases and airborne microbes, including bacteria, fungi, and viruses and also on COVID 19 and test certificate also need to be submited. The multistage filter should be enclosed inside powder coated steel casing/ Galvanized steel cabinet and should be self contained. It should have a low pressure drop of 0.25" wg @ 2.5 m/s. The system shall meet EUROVENT ePM 1.0 80% requirement and ASHRAE guideline for UV-C application for airborne infection inactivation. The unit shall be Intertek ETL, UL 2998 certified for zero ozone, CSA C22 No. 187, and CE certified for safety and quality. The system shall be tested on E. coli (ATCC 15597) in accordance with the standard ASTM E2149 with a kill rate of 99% in less than 15 minutes. The system shall be designed in accordance with Chapter 62 Ultraviolet Air and Surface Treatment, 2019 ASHRAE Handbook. The system shall be ANSI/ASHRAE 52.2 2017 tested with at least a MERV 15 rating and an ISO 16890 ePM 1.0 90% rating by an accredited lab. The system must not emit Ozone, and maximum exposure concentration of ozone should not exceed 0.01 ppm. All components used in the construction of the unit must comply with the following standards of safety and quality:
For Air Handling Units
NS-12.1 For 16400CFM
NS-12.2 For 14000CFM
NS-12.3 For 5600CFM
HVAC PANEL
Plant Room AC PANEL - IP 55 (Outdoor Type)
NS-13 Supplying, assembling, erecting, connecting, testing and commissioning Outdoor type of dust, damp and vermin proof free floor standing factory built sheet steel enclosed non-drawout modular type Panel fabricated out of suitable sized angle iron and flats, base channel and covered with 2.0mm thick PCRC sheet, duly painted complete with earth bus, aluminium bus bar, numbering & sign writing, interconnection & including the cost of connection through bus bar / copper conductor flexible connection with all accessories, rotary handles,phase barriers etc. complete as shown in drawing & as per specifications and mounted with the followings etc. complete as required. (All the starters should have NO/ NC contacts for remote/ fire control facility etc. complete).
Incoming:
a) 1 Nos 400 A 4P MCCB, 36 KA 4P, complete in all respects as mentioned in specifications and as required with following accessories:
R, Y & B Phase indicating lamps (LED type) with 6A control SP MCBs.
Indicating lamps (LED Type) with 6A protection MCBs to indicate ON, OFF & TRIP.
1 Digital multifunction meter with suitable CTs.
Bus Bars:
Electrolytic high conductivity aluminium three phase and neutral busbars rated at 415V, 50 Hz., 800 amps. insulated with heat shrinkable coloured PVC sleeves & clip on shrouds for joints.
Outgoing:-
(i) 2 Nos. MCCB feeder as per following details/ specifications: For Water Chilling Machines (1 no spare)
400 Amp, 415 volts, 36KA, Four Pole, MCCB with Microprocessor based release having variable current settings of O/L, S/C & inbuilt E/F protection.
Extended rotary operating mechanism with door interlock, defeat feature and padlock facility. MCCB should be with spreader link and phase barriers.
Indicating lamps (LED Type) with 6A protection MCBs to indicate ON, OFF, TRIP.
(ii) 3 Nos. MCCB feeder as per following details/ specifications (With 1 no sapre):
63 Amp 415 volts, 36KA FP MCCB with thermal magnetic release having variable current settings of O/L, S/C protection.
Extended rotary operating mechanism with door interlock, defeat feature and padlock facility. MCCB should be with spreader link and phase barriers.
3 Phase, fully automatic Star Delta Starter for 3kw primary chilled water pumps.
HVAC Panel as per above
CABLES
NS-14 Supply, laying & fixing of following sizes of PVC sheathed PVC/XLPE insulated copper conductor power/ multicore control armoured cable of 1.1 KV grade.(Cables exposed to sunlight and rain to be UV resistant or UV safe.
NS-14.1 3.5 Core 150 Sqmm.
NS-14.2 4 Core 6 Sq mm
CONTROL CABLING
NS-15 Supply, laying, effecting proper connections, testing & commissioning of PVC insulated copper multicore cables (as per relevent BS Standards) HVAC equipments to central control console.
NS-15.1 6C X 1.5 Sq.mm cable
NS-15.2 3C X 1.5 Sq.mm cable
NS-15.3 2C X 1.5 Sq.mm cable
Bidder Name
Amount
Comfort systems(GSTN-07AACPT8904A1ZV)
S K Engineers(GSTN-NA)
Amber infracon & energy (I) Pvt.ltd.(GSTN-NA)
DRYCOOL SYSTEMS INDIA PVT LTD(GSTN-NA)
Airef Engineers Pvt Ltd(GSTN-NA)
Kausnvi International Private Limited(GSTN-NA)
Kausnvi International Private Limited
Amber infracon & energy (I) Pvt.ltd.
Airef Engineers Pvt Ltd
Comfort systems
DRYCOOL SYSTEMS INDIA PVT LTD
Kausnvi International Private Limited
Amber infracon & energy (I) Pvt.ltd.
Airef Engineers Pvt Ltd
Comfort systems
DRYCOOL SYSTEMS INDIA PVT LTD
Amber infracon & energy (I) Pvt.ltd.
Kausnvi International Private Limited
Airef Engineers Pvt Ltd
Comfort systems
DRYCOOL SYSTEMS INDIA PVT LTD
S K Engineers
Airef Engineers Pvt Ltd
Comfort systems
Amber infracon & energy (I) Pvt.ltd.
DRYCOOL SYSTEMS INDIA PVT LTD
stage.html
html • 0.02 MB
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .