Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance H NO 2 460 SHIVKRUPA MANGAL OFFICE NEAR UPHALIVANCHEN TA HAVELI DISTRICT PUNE PIN NO 412202 | PUNE | PUNE | MAHARASHTRA | 412202 | Admitted-Finance |
| 4 | Admitted-Finance PUNE | PUNE | MAHARASHTRA | 410301 | Admitted-Finance |
Tender Value
₹47 L
EMD Value
₹94,000
Closing Date
18 Dec 2024, 3:00 pmClosed
Director IISER Pune
IISER Pune Dr Homi Bhabha Road Pashan 411008
PROVIDING ELECTRICAL DISTRIBUTION FOR AIR CONDITIONING SYSTEM AT H CROSS IISER PUNE
2024_IISRP_837690_1
30/IISERPUNE/2024-25
Open Tender
Electrical Works
Works
120 days
IISER Pune
As per NIT
3 documents required · 3 mandatory
₹1,180
Director IISER Pune
₹94,000
IISER Pune
3 Jan 2025
5 Dec 2024
19 Dec 2024
5 Dec 2024
18 Dec 2024
12 Dec 2024
11 Dec 2024
Amount
Please note that Quoted rates are exclusive opf GST. GST will be paid separtely as per rules and regulation of GOI.
Supplying LT cable having copper conductor XLPE insulated sheathed,galvanised steel tape armoured cable with pvc outer sheathing 1.1 KV ( Confirming to IS 7098 Part-II amended upto date as per the following sizes). Including the cost of all materials, lobour, Handling of materials of equipment and machineries all lead lift, loading and unloading, transportation, if any other incidental charges at all level complete all as per specification and as directed by Engineer-in charge. ( 3.5 Core x 300 Sqmm Armoured Aluminium Cable. )
Supplying LT cable having copper conductor XLPE insulated sheathed,galvanised steel tape armoured cable with pvc outer sheathing 1.1 KV ( Confirming to IS 7098 Part-II amended upto date as per the following sizes). Including the cost of all materials, lobour, Handling of materials of equipment and machineries all lead lift, loading and unloading, transportation, if any other incidental charges at all level complete all as per specification and as directed by Engineer-in charge. ( 4 Core x 16 Sqmm Armoured Copper Cable. )
Supplying LT cable having copper conductor XLPE insulated sheathed,galvanised steel tape armoured cable with pvc outer sheathing 1.1 KV ( Confirming to IS 7098 Part-II amended upto date as per the following sizes). Including the cost of all materials, lobour, Handling of materials of equipment and machineries all lead lift, loading and unloading, transportation, if any other incidental charges at all level complete all as per specification and as directed by Engineer-in charge. ( 4 Core x 10 Sqmm Armoured Copper Cable. )
Supplying LT cable having copper conductor XLPE insulated sheathed,galvanised steel tape armoured cable with pvc outer sheathing 1.1 KV ( Confirming to IS 7098 Part-II amended upto date as per the following sizes). Including the cost of all materials, lobour, Handling of materials of equipment and machineries all lead lift, loading and unloading, transportation, if any other incidental charges at all level complete all as per specification and as directed by Engineer-in charge. ( 3 Core X 4 Sq mm Armoured Copper Cable. )
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required. ( Upto 35 sq. mm (clamped with 1mm thick saddle) )
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required. ( Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp) )
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. ( Upto 35 sq. mm (clamped with 1mm thick saddle) )
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. ( Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS Metre flat clamp) )
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. ( 3/4 X 300 sq. mm (70mm) )
Supplying and making end termination with brass compression gland and Copper lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. ( 4 X 16 sq. mm (28mm) )
Supplying and making end termination with brass compression gland and Copper lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. ( 4 X 10 sq. mm (28mm) )
Supplying and making end termination with brass compression gland and Copper lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. ( 3 X 4 sq. mm (19mm) )
Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. ( 150 mm width X 50 mm depth X 1.6 mm thickness )
Providing and fixing 25 mm X 5 mm G.l. strip on surface or in recess for connections etc. as required.
Earthing with G.l. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre lonq etc. with charcoal/ coke 90 kg and salt 10 kg as required.
Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) 4 way (4 + 12), Double door
Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/lsolator) 8 way, Double door
Supplying fixing and wiring Current Operated RCBOs,240V/415V 50Hz with 10KA short circuit with standing capacity 25amps. double pole, 30/100mA, and Including the cost of all materials, lobour, HANDLING OF MATERIALS of equipment and machinery all lead lift, loading etc, complete. RCBO 63 A, 4P, 300 mA
Supplying fixing and wiring Current Operated RCBOs,240V/415V 50Hz with 10KA short circuit with standing capacity 25amps. double pole, 30/100mA, and Including the cost of all materials, lobour, HANDLING OF MATERIALS of equipment and machinery all lead lift, loading etc, complete. RCBO 63 A, 4P, 100 mA
Supplying fixing and wiring Current Operated RCBOs,240V/415V 50Hz with 10KA short circuit with standing capacity 25amps. double pole, 30/100mA, and Including the cost of all materials, lobour, HANDLING OF MATERIALS of equipment and machinery all lead lift, loading etc, complete. RCBO 32 A DP, 30 mA
Supplying fixing and wiring Current Operated RCBOs,240V/415V 50Hz with 10KA short circuit with standing capacity 25amps. double pole, 30/100mA, and Including the cost of all materials, lobour, HANDLING OF MATERIALS of equipment and machinery all lead lift, loading etc, complete. RCBO 32 A, DP, 100 mA
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioninq etc. as required. Single Pole
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioninq etc. as required. Tripal Pole
Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32 A 240 V "C" curve DP MCB complete with connections, testing and commissioning etc. as required.
Supplying and fixing TPN sheet steel enclosure on surface/ recess without MCB complete with connections, testing and commissioning etc. as required.
Supply & installation of surface mounted DLP U- PVC adaptable trunking raceways, fabricated out of U-PVC to Off-White or approved shade as per IS 733 of thickness 2.0mm for the base and sides with removable covers, complete with necessary bends, suitable sized junction boxes, internal angle, external angle, flat 90 degree angle , end caps and tees etc, Complete. (For every 1mtr distance cable tag has to be provided for each circuit in the raceways - as more that 1C FRLS copper wire is required for 1 Circuit) PVC RACEWAYS ( Along the wall), DLP U- PVC adaptable trunking . Size: 105x 50mm PVC Raceways with above specifications
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. 6 Pin 15/16 amp socket outlet
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. 15/16 amp switch
Supplying and fixing following Modular box with faceplate and cover on the existing raceways & PVC DLP truncking with required accessories to complete jobs. including connections, as required including connections, as required. 6 Module Box with faceplate & cover
Supplying and fixing following Modular box with faceplate and cover on the existing raceways & PVC DLP truncking with required accessories to complete jobs. including connections, as required including connections, as required. 4 Module Box with faceplate & cover
Supplying and installing following size of M. S. cable tray cover , non perforated painted with powder coating suitable for existing perforated painted M.S. cable trays 150x50x1.6 mm with M.S. suspenders including bolts & nuts, painting suspenders etc as required. ( minimum width 150 mm X minimum 50 mm depth X 1.6 mm thickness )
Supply and installation of PVC surface box on wall / ceiling / recess as required. 6 module
32Amp, single phase : Supply and fixing 32A, 3 pin, Single phase, Industrial Socket with safety shutters controlled by One no. of 32A, double Pole MCB to be mounted on wall, ( The job includes cutting & chasing on exisiting wall, fixing the box in position as required including rough plastering.) As per IEC 61439-3. suitable for flush mounting and surface mounting. 3P+ P+E Five pole, IP 44, material of plug & socket polyamide 6. Including the cost of all materials, lobour , HOM of equipment and machinerys all lead lift, loading and unloading,transportation, if any other incidental charges at all level complete all as per specification and as directed by Engineer-incharge. MCB/PLUG/BOX -32A .
32Amp, three phase : Supply and fixing 32A, 5 pin, three phase, Industrial Socket with safety shutters controlled by One no. of 32A, three Pole MCB to be mounted on wall, ( As per IEC 61439-3. suitable for flush mounting and surface mounting. 3P+ P+E Five pole, IP 44, material of plug & socket polyamide 6. The job includes cutting & chasing on exisiting wall, fixing the box in position as required including rough plastering.) Including the cost of all materials, lobour , HOM of equipment and machinerys all lead lift, loading and unloading,transportation, if any other incidental charges at all level complete all as per specification and as directed by Engineer-incharge. MCB/PLUG/BOX - 32A
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. ( 2 X 4 sq. mm + 1 X 4 sq. mm earth wire )
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. ( 4 X 4 sq. mm + 2 X 4 sq. mm earth wire )
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. 25mm dia conduit pipe
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. 32mm dia conduit pipe
Suvarna Electricals Pvt Ltd (BID ID -3139322)
BBP Electricals (BID ID -3139759)
BRITE INDUSTRIES (BID ID -3139580)
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .