PROVISION OF ROOF TOP SOLAR PANEL 40 KW AT BLDG NO. P-57 (VINTAGE-2004), ELECTRICAL LAB AT CQAV UNDER GE (S) AHILYANAGAR
2026_MES_771740_1
8355/E8
Open Tender
Miscellaneous Works
120 days
Ahilyanagar
Class D Any Category
8 documents required · 8 mandatory
₹500
Garrison Engineer (South) Ahilyanagar
₹62,000
Yes
12 Jun 2026
12 Jun 2026
4 Jul 2026
12 Jun 2026
2 Jul 2026
26 Jun 2026
12 Jun 2026 - 19 Jun 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Solar Power Plant of capacity not less than 40KW
Design, Supply, installation testing and commissioning of solar PV modules of 545Wp of type Mono Perc Half Cut (Mono crystalline) - Minimum 545 Wp each panel Solar Mono Perc144 Cells Module, with module efficiency, 21% at Standard test conditions with anti reflective coating and anti dust coating confirming to IEC 61215 and IEC 61730 complete including AC DB (with NVR, contactor) & DC DB electrical connection and mounting on GI structure frame all as specified and directed and the following items/equipments are included in rate quoted.
Make :- TATA / ADANI/ WARREE/ VIKRAM/ MAHINDRA or Equivalent make from ALMM, List I of MNRE with solar cells manufactured in INDIA.
Note: Solar PV cell (based on crystalline-silicon technology) shall be considered to be domestically manufactured only if the same has been manufactured in India, using undiffused silicon wafer (generally called 'Black Wafer'), classifiable under Customs Tariff Head 3818 and all steps/processes required for manufacturing solar PV cell from the undiffused silicon wafer have been carried out in India. | 1 | Per Job | - | - |
| 1.01 | Supply, installation & Erection of suitable height as directed by engineer in charge module mounting structure with required accessories for panel mounting [Material: Hot-dip galvanized mild steel (minimum 80μm zinc coating)] suitable for 40KW roof top solar power plant . Column’s and Rafters with digging, cementing and Panel laying (STADD PRO -180KMPH WIND), structure standard for solar panels. Structure shall be mounted using RCC/PCC blocks. MS mounting structures may be used for mounting the modules/ panels/arrays. Each structure should have angle of inclination as per the site conditions to take maximum insolation, including structure with suitable ladder & walkway of MS chequered plate, 600 mm width, load capacity 150 kg/m² & Ladder: GI/MS, 450 mm width with handrails. It has to follow IS safety standards. It should include water pipelines, fittings, jets,valves & pump of suitable capacity with electric cable and connection complete for cleaning of solar panels with accessories. | - | - | - | - |
| 1.02 | Supply, installation, testing and commissioning of Grid Tied String Inverter suitable for 40 KW (output capacity) solar power plants, 415V AC, 50Hz, respectively at given load condition), IP 68 out door wall mounting, with efficiency not less than 98% confirming to IEC 600682-2/vde standards with multifunctional LED indications with alarm and complying the following:-
(1) Operating frequency/ range - 50 Hz (49 to 51 Hz), Grid Frequency Synchronization range ± 1 Hz or more (shall also be compatible for Synchronization with DG Set) Waveform- Sine Wave Harmonics AC side total.
(2) Ripple DC voltage ripple content shall not be more than1%
(3) Harmonic current distortion (<3%) | - | - | - | - |
| 1.03 | (4) The bench marking efficiency criteria for the Grid tied ( central/string) inverter • At nominal voltage and full load is >95% • For load >25% is >94%. (5) No load losses should not be more than 5%.
Power Factor > 0.9 complete all as specified and directed by the engineer- in- charge.
(6) It shall have MPPT conditional & protection system and fan cooling ventilators complete all as specified and directed by the engineer- in- charge. (7) Inverter should have internal protection arrangements against any sustainable fault in feeder line and against the lightning on feeder. (8) Inverter generated harmonics, flicker, DC injection limits, voltage, frequency range and anti-islanding measures should follow latest guide lines/ IEC/ BIS codes. | - | - | - | - |
| 1.04 | S&F Outdoor type LT panel IP 65, powder coated, made out of 3.15 mm thickness CRCA SHEET, with stand of minimum height 2 feet, 1 in 1 Out LT Panel configuration with suitable capacity MCCB, AC SPD Type 2 complete, minimum size of enclosure shall be 700 mm x 600 mm x 300 mm (IP-55) along with 4 pole MCCB of suitable capacity, AC Surge Protection Device - 3 phase of 40 kA (as per IEC 60364-5-53), 4 Indication Lamp - R, Y, B with multi-functional meter 3 phase, 415 Volt (Voltage , Current, Power and Energy unit measurement (KWH)), including Copper Busbar including connecting lugs and Double compression glands etc complete as specified and directed.
Make: Switchgear: Siemens, L&T, Legrand, Schneider, SPD: Citel/ Phoenix/ OBO.
Note: -
1. Rate quoted is inclusive of integration & synchronization with existing three phase LT panel supply source.
2.LT panel configuration shall be provided by the contractor as per requirement/ designs of solar power plant output capacity). | - | - | - | - |
| 1.05 | DCDB, ACDB & three phase bidirection energy meter as per description mentioned below.
(a) Supply, installation connection & testing of AC DB shall be metal clad, totally enclosed, rigid,wall mounted, air ventilated, cubical type suitable for operation on three phase, 415 volts, 50 Hz, for 40 KW solar power plant with type 2 SPD NVR & contactor having provision of incoming & outgoing armoured cable). The panels shall be designed for minimum expected ambient temperature of 45 degree Celsius, 80 percent humidity and dusty weather. All indoor panels will have protection of IP54 or better. All outdoor panels will have protection of IP65 or better. All the 415 volts devices / equipment like bus bar support insulators, circuit breakers, SPDs, VTs etc., mounted inside the switchgear shall be suitable for continuous operation and satisfactory performance - 1 No. | - | - | - | - |
| 1.06 | (b) Supply, installation, connection & testing of DC DB, IP65 Panel shall be metal clad, totally enclosed, rigid, wall mounted, air ventilated, with suitable current rating, 1000 Volts string fuses, DC MCB of 80 Amp, 1000 Volts & DC SPD 1000 Volts as per DC input rating of invertor - 1 No.
(c) S & F FRP (Hensel or equivalent make) /PP/ ABS with dust, water and vermin proof provided with proper locking arrangements. Series / Array Junction Box (SJB/AJB) (whichever is required): All the arrays of the modules shall be connected to DC DB. AJB shall have terminals of bus-bar arrangement of appropriate size. Male & Female pair of MC4 connectors compatible with DC solar cable - 1 No.
(d) Supply, installation, connection & testing of Bi-directional energy meter 415V, 50Hz, three Phase with CT configuration as per latest IS-16444 suitable for 40 KW solar power plant
complete - 1 No. | - | - | - | - |
| 1.07 | M & L for 1.1 KV grade 3.5 core suitable size XLPE insulated and sheathed, multi-core multi- stranded copper armoured cables shall be used; Outdoor AC cables shall have a UV- stabilized outer sheath all as specified and directed. (To be used from inverter output to LT panel of BoQ item No. 1.04) | - | - | - | - |
| 1.08 | M & L for 6 sq mm (single core)/ suitable size DC Cable XLPE insulated and sheathed, UV-stabilized, multistranded flexible copper cable, should be colour coded, complete as all specified and directed. It should include DWC HDPE pipe of suitable size and clamps.
Note for Item No. 1.07 & 1.08 :-
All AC/DC copper cables shall be laid through DWC (N-450) pipe of suitable size included in the scope of work. | - | - | - | - |
| 1.09 | M & L for GI strip (HDG Grade)/ Copper strip (EC grade) of adequate size as per OEM recommendations with saddles and fixing screws etc. for roof conductors and down conductors above ground for all lightning protections, Solar panels, Inverter, ACDBs, DCDBs, Grid Tied inverter etc as per OEM and all as specified and directed. | - | - | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.40 MB
BOQ_864200.xls
BOQ • 0.83 MB
8355Tenderdocuments.pdf
Tender Documents • 0.34 MB
8355PStenderdocuments.pdf
Additional Documents • 0.64 MB
Download all tender documents and submit your bid