Loading…
Loading…
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
Tender Value
₹44.6 L
EMD Value
₹32,500
Closing Date
3 Nov 2026, 3:00 pm
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
Joint Commissioner/Executive Officer
The Head Office, Arulmigu Dhandayuthapani Swamy Temple, Palani
Providing Fire Fighting Arrangements, Smoke Detection and Fire Alarm System at Newly Constructing College of Arulmigu Palaniandavar Arts and Science College for Women, Oddanchatram Campus, Dindigul District
2026_HRCE_715458_1
03/2026-2027/D3-1
Open Tender
Miscellaneous Works
Lump-sum
90 days
Oddanchatram
Please refer Tender documents.
7 documents required · 7 mandatory
₹0
₹32,500
16 Oct 2026
16 Oct 2026
3 Nov 2026
16 Oct 2026
3 Nov 2026
23 Oct 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 2 | Supply, Erection, Testing and Commissioning of FireFighting Application Monoblock Motor Pumpset of 450 LPM at 20 metres head to develop 2.0 kg/sq.cm at the highest and farthest hydrant point to make 10m water jet at the time of fire fighting emergency circumstances, coupled with 3.75 KW / 5 HP rated three phase 415 volts, 50 Hz, 2880 rpm electrical motor, the pump with cast ron body, bronze impeller, rope gland packaging, suction size of 80 mm dia. delivery size of 65 mm dia, including the cost of foundaton concrete anti vibration mounting, rain safety hood and etc. complete as directed by the Departmental Officers | 1 | No | - | - |
| 3 | Supplying, Erection, Testing and Commissioning of Fire Fighting Electrical Control Panel of 10HP, 415V, 50Hz rating Wall Mounted Type fabricated using CRCA sheet, hinged lockable door, dust and vermin proof with following provisions.
a. 50 Amps, 4 Pole MCB-Incomer, 6 Amps, 2 Pole MCB for Control Circuit-1 set
b. R, Y, B Phase Indication Lamp, Voltmeter (0-500V),Ammeter (0-50A), Voltmeter Selector Switch-1set
c. 32 Amps Power Contactor with 230V Coil, 14-23 Amps Over Load Relay-1 set
d. Single Phase Preventer-1 No.
e. Indication Lamp for Motor On/Off Push Button-1 set
f. Auto / Manual Selector Switch, On / Off Push Button-1 set
g. Add On Block, Terminal Block, Power Wiring, Control Wiring, Connectors, Cable Lugs, Slotted Cable Cover. The above panel mounted on wall using anchor fastners, bolts, plugs, incoming and outgoing cable connection and all works carried out as per standard specifications and as directed by the Departmental Officers. | 1 | No | - | - |
| 4 | Supply and laying of following sizes of Armoured Aluminium / Copper Cables for electrical motor, control panel, pressure switch, jockey motor etc., all incidental charges, neccessary scaffolding and re-doing the dismantled portions to its original condition wherever found neccessary, etc., complete as per standard specification and as directed by the Departmental Officers. a) 2 core 1.5 sq.mm armoured multi strand aluminium cable | 2,400 | Mts | - | - |
| 5 | Supply, Erection, Testing and Commissioning of following MS ‘C’ Class Heavy Duty Pipe as per IS 1239 to withstand a developing pressure of 10 kg./sq.cm including necessary fittings like MS flange of table ‘E’, elbows, reducers, gaskets, bolt, nuts with washers & joints as per standard method of arc welding, including one coat metal primer and two coat Post Office Red painting including conveyance, all incidental charges, neccessary scaffolding and re-doing the dismantled portions to its original condition wherever found neccessary, etc., complete as per standard specification and as directed by the Departmental Officers. a) 100 mm | 230 | Mts | - | - |
| 6 | B) 80 mm | 450 | Mts | - | - |
| 7 | C) 25 mm | 200 | Mts | - | - |
| 8 | Supply and fixing nominal bore quartized bulb type sprinkler bulb 68 Deg C fast response pendent type including GI collar for each sprinkler bulb, mounted in MS pipe line using suitable size MS threaded coupling, thread, shellac etc., as per standard methods and including conveyance, all incidental charges, neccessary scaffolding and re-doing the dismantled portions to its original condition wherever found neccessary etc., complete as per standard specification and as directed by the Departmental Officers. | 145 | Nos | - | - |
| 9 | Supply, Erection, Testing and Commissioning of cast iron body and gun metal or stainless steel Internal Non-Return Valve of size of
80mm dia to control one way flow of water to be installed pump room at delivery line and near overhead tank at terrace level near to jockey pump and motor including necessary MS flange of table ‘E’, gaskets, bolts & nuts, etc. as per IS 5312 including conveyance, all incidental charges, neccessary scaffolding and re-doing the dismantled portions to its original condition wherever found neccessary, etc., complete as per standard specification and as directed by the Departmental Officers | 1 | No | - | - |
| 10 | Supply and Fixing of Fire fighting application oblique type stainless steel Hydrant Valve of size 63 mm dia with oblique type instantaneous coupling with rotating wheel to open and close the valve including MS flange of table E,bolts & nuts with washer as per IS 5290 at ringmain around the building and wet riser inside the building including conveyance, all incidental charges, neccessary scaffolding and re-doing the dismantled portions to its original condition wherever found neccessary etc complete as per standard specification and as directed by the Departmental Officers. | 7 | Nos | - | - |
| 11 | Supply, Installation of Fire Fighting Application 180 degree swinging type, hose reel drum with 20 mm dia braided thermo plastic hose of 30 metres long, so as to extend to necessary distance by self rolling spindle wheel including necessary 20 mm dia ball valve and open and close spray nozzle,warmclip, etc., as per the standard pattern of any reputed make at every floor nearer to hydrant valve, including conveyance, all incidental charges,neccessary scaffolding and re-doing the dismantled portions to its original condition wherever found neccessary., etc., complete as per standard specification and as directed by the Departmental Officers | 7 | Nos | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.34 MB
Fire.pdf
Tender Documents • 1.67 MB
BOQ_859425.xls
BOQ • 0.26 MB
dr.pdf
Additional Documents • 1.08 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .