Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹14.2 LAccepted-AOC SRINIKETAN ROAD BOLPUR BIRBHUM 731204 | BOLPUR | BIRBHUM | WEST BENGAL | 731204 | L1 | Accepted-AOC L1 BIdder | |
| 2 | L2₹14.6 L+₹43,884 (3.10%)Rejected-Finance 8 TOWNSHEND ROAD KOLKATA 700025 | KOLKATA | KOLKATA | WEST BENGAL | 700025 | L2 | Rejected-Finance Higher Quoted Rate. | |
| 3 | L3₹14.8 L+₹68,140 (4.81%)Rejected-Finance BALTIKURI INDUSTRIAL ESTATE PLOT NO A 01 DASNAGAR HOWRAH 711113 | HOWRAH | HOWRAH | WEST BENGAL | 711113 | L3 | Rejected-Finance Highest Quoted Rate. |
Tender Value
Refer Docs
EMD Value
₹24,900
Closing Date
17 Jan 2025, 12:00 pmClosed
SE, PWD, Kolkata Electrical Circle
P-16, India Exchange Place Extn. KIT Building, 2nd Floor, Kolkata-700073
Proposed Amphitheater, Artists Cottage and Multi-storied Office Complex cum Guest House within the Campus State Music Academy, Tollygunge, Kolkata-SITC of HVAC system at hall free space at 2nd floor-2nd call.Academy Tollygunge Kolkata-SITC of HVAC sy
2024_WBPWD_789379_1
PWD/SE/KEC/NIT-17(2nd call)/24-25
Open Tender
A/C ORG
Item Rate
30 days
State Music Academy, Tollygunge
Please refer Tender documents.
9 documents required · 9 mandatory
₹24,900
Office of the SE, PWD, Kolkata Electrical Circle
20 Mar 2025
23 Dec 2024
20 Jan 2025
23 Dec 2024
17 Jan 2025
3 Jan 2025
2 Jan 2025
Amount
Supply, installation, testing & commissioning of 8.5 Tr. Ductable split unit:-
Supply, installation, testing & commissioning of ceiling suspended inverter type ductable split Air Conditioner having Microprocessor based control system with the following specification. Capacity- 8.5Ton or higher, Minimum rated cooling capacity-102000 BTU/hr, No. of IDU- 1no.or multiple , Air-flow /IDU- 3400CFM(Total),No. of ODU- 1no. or multiple, Compressor- 1no. or multiple nos. Rotary/Scroll compresoor, Refrigerent -R-410A/R32, Condenser & Cooling coil- Copper coil, Power supply- 415V - 50 Hz - 3 Ph AC (as per OEM standard).(Make: Mitsubishi Electric/Daikin/O-General/Carrier/Blue Star/Voltas/ L.G/ Panasocnic/ Jhonson Controls / Thosiba/ Sharp / Mitsubishi Heavy)
SITC of Refrigerant Piping :-
Supply, installation, testing & commissioning of Copper Refrigeration Pipe line for liquid and suction line including vaccumiazation and Nitrogen of testing of following nominal size of soft/hard drawn copper refrigerent piping for Package/ Ductable/ Concealed Split/ Room AC system complete with fittings with adjustable ring type hanger supports, jointing/ brazing including accessories suitable for DX System of air-conditioning, duly insulated with XLPE class-O tubular insulation/ with Class- O closed cell Elastomeric Nitrile Rubber tubular insulation having 40-55 kg/cu.mtr. density of 9mm thickness for suction and liquid lines including protective coating on pipes exposed to sunlight as well as charging, complete with all accessories as per specification etc. as required & as per direction of E.I.C with proper medning good the damages to original finish. Mk. of Cu pipe;- Rajco/Ryoku/Mandev/Nippon. Make of Nitrile Rubber insulation- Aeroflex/K flex / Accroflex /Armacell. a) 28.6 mm O.D.(Thickness-1mm) (Insulation : 13 mm)
b) 12.7 mm O.D.(Thickness-0.8mm) (Insulation : 13 mm)
SITC of Control / comuunication cabling :-
Supply & laying of XLPE insulated copper control cabling (7 Core x 2.5 sqmm. flexible copper cable) between indoor to outdoor unit with necessary cable conduit & fittings. The cabling shall be bundled properly and shall be properly aligned with the refrigerant piping.(Make Havells/ Polycab/KEI/Gloster)
Supply & Pouring / filling of refregent:-
Supply & pouring / filling of rerigerant R32 / R410 refrigerant gas for AC machines incl. testing and commissioning of complete machines with all indoors, outdoor units, electrical, remotes etc. incl. pressure testing with nitrogen and vaccumiazation
Canvas Connection:-
Supply, Fixing,testing and commssiooning of fire retardant nonporous double layer flexible canvas connection between each indoor unit and duct/grill along with proper nut bolt joint for isolation of vibration (Design to be approved & as directed by E.I.C)
SITC of Air Distribution Work:-
Supply and Fixing of linear type AIuminium powder coated continuous supply air grills with VCD (Make: /Premier/Systemair/ Air Enterprise/ Caryaire) (Design to be approved & as directed by E.I.C)
Supply and Fixing of linear type aluminium Power coated continious return air grill without VCD (Make:Premier/Systemair/ Air Enterprise/ Caryaire) (Design to be approved & as directed by E.I.C)
SITC of Factory Fabricated Pre-Insulated SMART PIR Flat Oval Sandwitched Ducts, CNC machine cut Ducts made of SMART Pre-Insulated PIR(Poly Isocyanurate Rigid) Panels(20mm thick) complete CFC & HCFC Free sandwiched between aluminium foil on both the sides [with Internal side Embossed Aluminium foil of 80 Micron Thickness and External Side Embossed Aluminium foil of 200 Micron Thickness (Anti microbial, Anti fungal, Anti corrosion and UV Protection coating)] and close cell not less than 95% Rigid Cellular foam insulation of thickness as specified below and material shall be Class O as per BS 476 Part 6 & Part 7 with 2 hours fire rating, with Density of 46 kg/m3 & above for insulated glass wool duct board and should have Thermal Conductivity 0.033 W/mK at 10 deg. C temperature, Water absorption shall be not more than 0.03% as per EN 13403 standards for ducting and the panel should be Green Pro & GRIHA Certified. The duct work should be capable of handling pressure upto 1500 Pascals.The joint between the ducts shall be done by means of PVC slide in-type joints between the duct to prevent any air leakage or metal Coupler system with Special Reinforced tape & Tiger clamp between the ducts or any other suitable jointing arrangement as approved by E.I.C. Ducts supporting arrangement shall be factory fabricated Modular hanging/supporting system comprising of channel, threaded rods & clamps or wire & hanger support system, coupling, fitting, anchor, GSS nuts/bolts, gaskets etc. as per direction of E.I.C. Installation to be carried out by Manufacturer's installation team only. [Make- Aswa Insulation/P3/Aura/GP Sipra/Vent Air/Ductofab as approved by E.I.C]
SITC of Drain piping with insulation - PVC Pipes
Supply & laying PVC rigid drain pipe (Medium class) with necessary fitting proper supports at 5ft interval and duly insulation with 9mm thick Nitrile Rubber Insulation having weather protective coating as per drawing. (a) 32mm dia PVC pipe with insulation
(b) 40mm dia PVC pipe with insulation
SKY DECORATIONS PRIVATE LIMITED (BID ID -5963486)
NATIONAL AIRCON (BID ID -6005725)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .