Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹16.1 LAccepted-AOC DISTT KANGRA HP | KANGRA | HIMACHAL PRADESH | 176001 | L1 | Accepted-AOC L1 | |
| 2 | L2₹19.2 L+₹3.1 L (19.1%)Rejected-AOC H NO 199 W NO 6 NEAR OLD SDM OFFICE DISTT HAMIRPUR HP 177001 | HAMIRPUR | HAMIRPUR | HP | 177001 | L2 | Rejected-AOC L2 | |
| 3 | L3₹19.4 L+₹3.3 L (20.7%)Rejected-AOC BHOTA CHOWK HAMIRPUR H P 177001 | HAMIRPUR | HAMIRPUR | HIMACHAL PRADESH | 177001 | L3 | Rejected-AOC L3 | |
| 4 | L4₹21.0 L+₹4.9 L (30.4%)Rejected-AOC HOUSE NO 214 WARD NO 2 TEHSIL SUJANPUR DISTT HAMIRPUR HP | HAMIRPUR | HIMACHAL PRADESH | 174304 | L4 | Rejected-AOC L4 | |
| 5 | L5₹21.1 L+₹5.0 L (31.1%)Rejected-AOC | L5 | Rejected-AOC L5 |
Tender Value
₹23.3 L
EMD Value
₹47,000
Closing Date
25 Oct 2024, 10:00 amClosed
EE Design
O/o Estate Organization ,UHF ,Nauni
Construction of new girls Hostel college of horticulture and forestry at Neri-Hamirpur SH Providing Electrical Installation
2024_YSPU_94020_1
UHF/Const.-1/ Parttfile/2024/-1386-87 dtt 14.10.2024
Open Tender
Electrical Works
Item Rate
570 days
Neri
Please refer Tender documents.
5 documents required · 5 mandatory
₹3,000
EE Design
₹47,000
5 Apr 2025
14 Oct 2024
25 Oct 2024
14 Oct 2024
25 Oct 2024
14 Oct 2024
Amount
Wiring for light point / fan point / exhaust fan / call bell point with 1.5sqmm PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface / recessed PVC conduit and earthing the light point with 1.5 sqmm HRFRLS / PVC insulated single core copper conductor cable as required complete in all respect as per satisfaction of Engineer-in-charge (Group – A).
Wiring for twin control light point with 1.5 Sqmm PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface / recessed PVC conduit with 2-way, 5/6 amps. piano type switch and earthing the light point with 1.5 Sqmm HRFRLS / PVC insulated single core copper conductor cable as required complete in all respect as per satisfaction of Engineer-in-charge (Group – A).
Wiring for power plug with 2x1.5 Sq. mm. PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface/recessed PVC conduit along with 1 No. 1.5 Sq.mm. HRFRLS/PVC insulated single core copper conductor cable for earthing as required complete in all respect as per satisfaction of Engineer-in-charge.
Wiring for power plug with 2x4 Sq. mm. PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface/recessed PVC conduit along with 1 No.4 Sq.mm. HRFRLS/PVC insulated single core copper conductor cable for earthing as required complete in all respect as per satisfaction of Engineer-in-charge.
Wiring for power plug with 4x4 Sqmm PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface/recessed PVC conduit along with 1 No. 4 sqmm HRFRLS / PVC insulated single core copper conductor cable for earthing as required complete in all respect as per satisfaction of Engineer-in-charge.
Wiring for circuit /submain with following size PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface/recessed PVC conduit along with 1 NO. HRFRLS/PVC insulated single core copper conductor cable or same size for earthing as required complete in all respect as per satisfaction of Engineer-in-charge.
2x 1.5 Sq. mm
2x 4 Sq. mm
2x 4 Sq. mm
2x 10 Sq. mm
2x 16 Sq. mm
Wiring for circuit / sub-main with 4x10 Sq. mm. PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface/recessed PVC conduit along with 2 No.10 Sq.mm. (4x10+2x10) HRFRLS/PVC insulated single core copper conductor cable for earthing as required complete in all respect as per satisfaction of Engineer-in-charge.
Wiring for circuit/sub-main with 4x16 Sq,mm PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface/recessed PVC conduit along with 2 No. 16 Sq.mm (4x16+2x16) HRFRLS/PVC insulated single core copper conductor cable of same size for earthing as complete in all respect as per satisfaction of Engineer-in-charge.
Wiring for circuit / sub-main with 3x25+1x16 Sqmm PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface / recessed steel conduit along with 2 No. 16 Sqmm (3x25+1x16) HRFRLS / PVC insulated single core copper conductor cable for earthing as required complete in all respect as per satisfaction of Engineer-in-charge.
Supplying & fixing metal box of following size (nominal size) on surface or in recess suitable for fixing phenolic laminated sheet cover in front including painting etc. as required complete in all respect as per satisfaction of Engineer-in-Charge.
180mmx100x60mm deep sizes
200mmx150x75mm deep sizes
Supplying and fixing ceiling rose on the existing junction box/wooden block including connection etc. as required complete in all respect as per satisfaction of Engineer-in-charge.
Supplying & fixing following rating Piano-type switch/socket on the existing switch box/cover including connections etc. as required complete in all respect as per satisfaction of Engineer-in-charge.
S.P. 5/6 amps one way switch, piano type.
S.P. 15/16 amps one way switch, porcelain base / piano type.
5 pin 5/6 amps socket outlet, porcelain base / piano type.
6 pin 15/16 amps socket outlet, porcelain base / piano type.
Supplying & fixing bakelite batten / angle holder including connections etc. as required complete in all respect as per satisfaction of Engineer-in-charge.
Supplying and fixing five stepped socket type modular fan regulator on the existing board / box including making connections etc. as required complete in all respect as per satisfaction of Engineer-in-charge.
Supplying and fixing Call bell/ buzzer suitable for D.C./A.C. single phase,230 volts complete as required complete in all respect as per satisfaction of Engineer-in-charge. e.
Suppling and erection of wall mounted metal boards for switch gear mounting of suitable size, with permissible variation in size of plus minus 5mm, welded frame work made of M.S.angle iron 50mm x 50mm x 6mm thick duly welded complete with 3mm thick M.S. sheet fixed with hinges as open able front complete with locking arrangement including painting and bonding to the existing earth as required in all respect as per satisfaction of Engineer-in-charge
Supplying & fixing sheet metal bus-bar chamber suitable for 100 amp. 415 volts capacity with 4 Nos. copper strip bus-bars each of length 450mm & cross-sectional area (25.4mmx3.17mm), enclosure made from 1.6mm thick M.S. sheet having overall dimensions (530mmx400mmx150mm) nominal with all accessories including connections, earthing the body etc. as required complete in all respect as per satisfaction of Engineer-in-charge.
Supplying & fixing sheet metal bus-bar chamber suitable for 200 amp. 415 volts capacity with 4 Nos. copper strip bus-bars each of length 600mm & cross-sectional area (25.4mmx4.75mm), enclosure made from 1.6mm thick M.S. sheet having overall dimensions (680mmx450mmx150mm) nominal with all accessories including connections, earthing the body etc. as required complete in all respect as per satisfaction of Engineer-in-charge.
Providing & fixing TP&N switch disconnector fuse unit cubical type, 415/500 volts with 3 Nos. HBC/HRC fuses, in sheet steel enclosure including drilling holes on the board, connections, earthing the body etc. as required complete in all respect as per satisfaction of Engineer-in-charge.
100 amps. category – A
200 amps. category – A
400 amps. category – A
Supplying & erection of 6 amps. To 32 amps. Rating, 10KA breaking capacity, 240 volts, ‘C’ curves, miniature circuit breaker of following poles in the existing MCB DB complete with connections etc. as required complete in all respect as per satisfaction of Engineer-in-charge. a) Single pole. Category – A
Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. a). 63 Amps. Cat-A.
Supplying and fixing 63 Amps. Cat-A, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required complete in all respect as per satisfaction of Engineer-in-charge.
Supplying and fixing 63 Amps. Cat-A. , , double pole (single phase & neutral) 240 volts, residual current circuit breaker (RCCB), having a sensitivity current up to 300 millampers in the existing MCB DB complete with connections, testing and commissioning etc. as required complete in all respect as per satisfaction of Engineer-in-charge.
Supplying and fixing 63 Amps. Cat-A, four pole (three phase & neutral) 415 volts, residual current circuit breaker (RCCB),having a sensitivity current up to 300 miliampers in the existing MCB DB complete with connections, testing and commissioning etc. as required complete in all respect as per satisfaction of Engineer-in-charge.
PrProviding and fixing on wall face unplasticised – PVC moulded Coupler for unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion etc. complete in all respect as per satisfaction of Engineer-in-Charge. a).110 mm(one hundred ten milimetre) diameter).
Double door-8 way
Double door-12 way.
Double door-16 way.
Supplying and fixing of double door – 4 way (8+12), horizontal type. triple pole and neutral sheet steel MCB distribution board, 415 volts, on surface / recess, with provision for 4-pole MCB / isolator / RCCB / RCBO as incomer and SP MCBs as outgoing, complete with tinned copper bus-bar, wire-set, neutral link, earth bar, din-bar, detachable gland plate, cable, identification labels interconnections, phosphatized and powder painted, including earthing etc. as required complete in all respect as per satisfaction of Engineer-in-charge.
Earthing with copper earth plate 600mm x 600mm x 3mm thick, including accessories and providing masonry enclosure with cover plate having locking arrangement and water pipe etc. (but without charcoal or coke and salt) complete as required complete in all respect as per satisfaction of Engineer-in-charge.
Extra for using salt and charcoal for G.I. or copper plate earth electrode complete as required complete in all respect as per satisfaction of Engineer-in-charge.
Supplying and laying 8 SWG copper wire at 0.50 Rmt. below ground level for earth electrode conductor, including soldering etc. as required complete in all respect as per satisfaction of Engineer-in-charge.
Providing, laying and fixing of one no. aluminium conductor, PVC insulated and PVC sheathed, armoured / XLPE power cable, working voltage 1100 volts grade on surface etc. as required complete in all respect as per satisfaction of Engineer-in-charge (Gloster/ L&T/ Havell’s/ Plaza/ finolex make)..
Armoured cable 70 Sqmm (3.5 core).
Armoured cable 95 Sqmm (3.5 core)
Providing, laying and fixing of one no. aluminium conductor, PVC insulated and PVC sheathed, armoured / XLPE power cable, working voltage 1100 volts grade on surface etc. as required complete in all respect as per satisfaction of Engineer-in-charge (Gloster/ L&T/ Havell’s/ Plaza/ finolex make)..
Armoured cable 70 Sqmm (3.5 core).
Armoured cable 95 Sqmm (3.5 core).
Providing, laying and fixing of one no. aluminium conductor, PVC insulated and PVC sheathed, armoured / XLPE power cable, working voltage 1100 volts grade on surface etc. as required complete in all respect as per satisfaction of Engineer-in-charge (Gloster/ L&T/ Havell’s/ Plaza/ finolex make)..
25 Liter capacity water heater (Cat-A).
35 Liter capacity water heater (Cat-A).
Providing, Installation, testing & commissioning of ceiling fan 1200 mm sweep without regulator, including wiring the down rods of standard length (upto 30 cm) with 16/0.20mm twin twisted flexible, cotton braided, copper cable, including providing and fixing phenolic laminated sheet cover on the fan box and earthing etc. as required complete in all respect as per satisfaction of Engineer-in-charge (Bajaj/ Phillips/ Usha/ Crompton/ Havells/ Great white make)
Providing & installation of exhaust fan of following sizes in the existing opening, including making the hole to suit the size of the above fan, making good the damages, connections, testing and commissioning etc. as required complete in all respect as per satisfaction of Engineer-in-charge(Usha/ bajaj/ phillip’s/ Havell’s/ Crompton/ Great white make)..
Exhaust fan, Light duty (Domestic), 225mm sweep.
Exhaust fan, Heavy duty 300mm sweep.
Supplying and erection of street light bracket made of GI pipe ‘A’ class of suitable length and dia, the pipe bended to give an angle of 100 to 110 degree fitted with bolt and nuts at the top of existing pole or wall including painting the pipe with two coats of approved paint over priming coat complete in all respect as per satisfaction of Engineer-in-charge. a). 32mm dia. G.I. pipe, heavy class.
Providing, Installation, testing & commissioning of T5 4’-0” square batten 20 watt LED light with 16/0.20mm twin twisted flexible, cotton braided, copper cable and allied accessories etc. as required complete in all respect as per satisfaction of Engineer-in-charge (Wipro/ bajaj/ phillip’s/ Havell’s/ Crompton/ Jaquar/ Great white make).
Supplying, installation, testing and commissioning of outdoor street light LED 45 watt with 16/0.20mm twin twisted flexible, cotton braided, copper cable and allied accessories etc. as required complete in all respect as per satisfaction of Engineer-in-charge (Wipro/ bajaj/ phillip’s/ Havell’s/ Crompton/ Jaquar/ Great white make).
Providing, Installation, testing & commissioning of surface/ recessed LED light 2’-0” into 2’-0” and 36 Watt with 16/0.20mm twin twisted flexible, cotton braided, copper cable and allied accessories etc. as required complete in all respect as per satisfaction of Engineer-in-charge ( Wipro/ bajaj/ phillip’s/ great white/ havell’s/ Jaquar/ crompton make).
SHARMA ELECTRICAL CO.
Dhiman Elect-
RAJNEESH THAKUR
ARUN KUMAR SHARMA
Avtar krishan
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .