Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
Tender Value
₹64 L
EMD Value
₹1.3 L
Closing Date
30 Dec 2020, 2:00 pmClosed
ER. A.K. CHHIBBER
Office of the Deputy General Manager, JKPCC Ltd., Unit Electrical, Rail Head Complex Jammu.
Internal Electrification works for IPD Hospital Kishtwar.
2020_PWDJK_111194_1
e-NIT No. 40/ELECT of 2020-21 Dt. 09-12-2020.
Open Tender
Electrical Works
Item Rate
365 days
Kishtwar
Please refer Tender documents.
6 documents required · 6 mandatory
₹1,000
Yes
Financial Controller, JKPCC Ltd.
₹1.3 L
Yes
O/o the General Manager, JKPCC Ltd.
19 Feb 2021
10 Dec 2020
2 Jan 2021
10 Dec 2020
30 Dec 2020
15 Dec 2020
15 Dec 2020
Amount
Sub Head-I (Wiring)
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.
Group C
Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point ( without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed PVC conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required.
Group C
Wiring for Light /Power Plug with 2 x 4 sq.mm FRLS PVC Insulated Copper Conductor single core cable in surface/Recessed medium class PVC Conduit along with 1 No. 4 sq.mm FRLS PVC Insulated copper conductor single core cable for loop earthing as required.
Wiring for Circuit/Submain Wiring along with earth Wire with the following Sizes of FRLSPVC insulated copper conductor,single core Cable in surface/Recessed medium class PVC conduit as required.
2 X 2.5 SQ.MM + 1 X 2.5 SQ.MM EARTH WIRE
4 X 6 sq. mm + 2 X 6 sq. mm earth wire
4 X 4 sq. mm + 2 X 4 sq. mm earth wire
4 X 16.0 SQ.MM + 2 X 6.0 SQ.MM EARTH WIRE
4 R x 1 C x 35 Sq.mm Multistrand Copper Wire
Supplying and fixing modular blanking plate on the existing modular plate and switch box excluding modular plate as required
Supplying and fixing Stepped Type Electronic Fan Regulator on the existing Modular Plate Switch Box including Connections but Excluding Modular Plate etc. as Required
Supplying and Fixing suitable size G.I box with modular plate and cover in front on surface or in recess,including providing and fixing 6 pin 15/16 amps modular socket outlet and 15/16 amps modular switch,connection,painting etc. as required.
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required.
Supplying and Fixing suitable size G.I box with modular plate and cover in front on surface or in recess,including providing and fixing 3 pin 25 amps modular Multi pin socket outlet with connection,painting etc. as required.
Sub Head-III(DB's and MCB's)
Supplying and fixing following way,Prewired TP&N PPI Distribution Board of Sheet Steel for 415 Volts on surface/Recess complete with Ready to use DBs - Provided with 100A insulated phase bus-bars,neutral bar/s with shroud/s, earth bar/s , sticking saddles , cement spill protector ,color-coded interconnecting wire set , cable ties , blanking plates and circuit identification labels.The D.B should be IK-09 Compliant.(The Cost of D.B is without MCB's)(IP Rating-43)
6 Way (8 Module Incomer),(2+2+2 incomer DP RCCB),(6+6+6 SP MCB's O/G's)
8 Way (8 Module Incomer),(2+2+2 incomer DP RCCB),(8+8+8 SP MCB's O/G's)
12 way (8 Module Incomer),(2+2+2 incomer DP RCCB),(12+12+12 SP MCB's O/G's)
Supplying,Installation ,Testing and Commissioning of Four Pole 415V ,MCB in the existing MCB DB With Connections Testing and Commissioning etc as Required
Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Supplying and fixing following rating, double pole, 240 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Supplying and fixing 5 amps. to 32 amps.rating 240 volts 'C' series, miniature circuit breaker of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Single Pole
Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
Supplying and Laying of B-Class 100 mm Dia Size G.I Pipe under the Road/Floor not less than 1 mtr below the Ground Level including cutting the Road/Floor and making Good the same as required.
Sub Head-IV(Lightning Conductor and Earthing)
ENVIRONMENTALLY SAFE MAINTENANCE FREE EARTHING SYSTEM Necessary soil treatment is to be made by the contractor in order to improve the Pit resistance value.
Supplying,Installation and Testing of 75 mm Cu. Pipe Filled with Crystalline conductive Mixture with Copper Strip of Size 40 mm x 6 mm of Length 2 mtr with Ecofriendly Backfill Compound 50 Kg.(2 Nos for Panel and 2 Nos for UPS for Fire Alarm Syatem)Makes:- Genus/Ashlok/G-MAXX Earth pit chamber (300mm x 300mm) with CI cover for the above.
Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm)
Sub Head -V(SITC of Fans and Fittings)
SITC of Ceiling Fan,Capacitor type suitable for low voltage operation including wiring the down rods of standard length(Upto 30 cm)with 1.5 sq.mm FR PVC insulated,copper conductor,single core cable including providing and fixing phenolic laminated sheet cover on the Fan Box etc as Required.
1200 MM SWEEP(5 STAR)
SITC of pre-wired Recess Mounted LED Ceiling Light 2' x 2' Fitting including connections with 1.5 sq.mm FR PVC insulated copper conductor single core cable and earthing etc as required(
SITC of pre-wired Recess Mounted LED Ceiling Light 18 W including connections with 1.5 sq.mm FR PVC insulated copper conductor single core cable and earthing etc as required.
SITC of pre-wired Recess Mounted LED Ceiling Light 12 W including connections with 1.5 sq.mm FR PVC insulated copper conductor single core cable and earthing etc as required.
Supply of AC 230/250 Volts, 50 Hz exhaust fan with louveres of Following Sizes including connection etc. complete as required .
Sub Head-VI(Meter Board and Safety Items)
OUTGOINGS MCCB 160 Amps FP with Breaking Capacity 18 KA With Adjustable TMR Icu=Ics=100%(4 Nos) MCCB 100 Amps FP with Breaking Capacity 18 KA With Adjustable TMR Icu=Ics=100%(1 Nos) MCCB 63 Amps FP with Breaking Capacity 18 KA With Adjustable TMR Icu=Ics=100%(3 Nos) MCCB 40 Amps FP with Breaking Capacity 18 KA With Adjustable TMR Icu=Ics=100%(1 Nos) MCB 25 Amps DP with Breaking Capacity 10 KA (2 Nos) Indicating Lamps ON OFF TRIP( 9 Nos) Load Bearing Members to be made out of 2.0 mm CRCA Sheet. Partitions to be made out of 1.6 mm CRCA Sheet Gland Plates to be 3.0 mm Thick.
Supplying,Installation,Testing and Commissioning of Cubical Indoor Type LT Panel Board Suitable for 415 V 3 Phase 4 Wire 50 HZ AC Supply System including Incomers,Out Goings,Bus Bars, etc. as required as per the Following Description.(IP:42) (UPS Output Panel) INCOMER MCCB 100 Amps 4 P with Breaking Capacity 36 KA Microprocessor Based with (Icu=Ics=100%)(1 Nos) Indicating Lamps RYB (1 Set) Aluminium Busbar 150 Amps FP E-91 E Grade Electrolytic Aluminium Digital Load Manager(1Nos) SP MCB 2 A(12 Nos) ON/OFF/TRIP(01 Sets) OUTGOINGS MCCB 63 Amps 4 P with Breaking Capacity 36 KA Microprocessor Based with (Icu=Ics=100%)(2 Nos) ON/OFF/TRIP(02 Sets) Load Bearing Members to be made out of 2.0 mm CRCA Sheet. Partitions to be made out of 1.6 mm CRCA Sheet Gland Plates to be 3.0 mm Thick.
Under Ground Cables and Accessories
Supplying and Laying of 1 No. DWC High Density Poly ethylene Pipe having Corrugation on Outer wall and Plain surface inner wall Conforming to IS: 14930 Part-1 and 2 Complete with accessories for Protection of 1.1 KV Grade under Ground cable Directly in Ground at a Depth of 50 CM including excavation and Refelling the Trench Etc.as Required .
Supplying and Laying of 1 No. PVC/XLPE insulated and PVC Sheathed /XLPE Power Cable of 1.1 KV Grade of Following Sizes in the existing RCC/Hume/DWC/Stone ware/Metal Pipe as Required.
3.5 C X 300 Sq.mm A2XFY
3.5 C X 16 Sq.mm A2XFY
Supply and Making end Termination with Brass Compression Gland and Auminium Lugs for the Following Sizes of PVC insulated and PVC Sheathed/XLPE Aluminium Conductor Cable of 1.1 KV Grade as Required
3.5 C X 300 Sq.mm A2XFY
3.5 C X 16 Sq.mm A2XFY
40 KVA UPS , Input 3 Phase 4 wire and output 3 phase 4 wire with 15 min. Back up
Supply, fixing, testing and commissioning of Early Streamer Emission type Lightning Protection complete with capturing head, adapter to fix, tested as per NFC 17-102 for anicipated emission time 30 Micro Seconds, to be installed at top of the building with the protection radius of 60 Mtr. (level 2 protection) as per specification enclosed SITC of Mast (Al/G.I. of suitable height) for mounting the terminal & adaptor to mount the Lightning rod with FRP copuler Supply, installation, testing and commissioning of Advanced Maintenance Free environment friendly Earthing system consisting of 1 no. of 3mtr length, 17.2 mm dia UL certified earth electrode made of high tensile low carbon steel circular rods, molecularly bonded copper on outer surface (minimum copper bonding thickness-250 microns) with Cu terminals to connect incoming strips, (Environment freindly backfill compound duly certified as per ANSI/NSF standard 60/Toxic content certificate as safe for use near potable ground water resources stricttly as per specification enclosed. Make- Jef Ecosafe(Loresco) or Equivalent SITC of Earth pit chamber (300mm x 300mm) with CI cover for the above(3 Nos) SITC of Lightning Strike Recorder- (Min 4 digits display) of not resettable type in an IP 55 enclosure with the minimum sensitivity of 250 A(01 Nos) SITC of Down conductor of 70 sq.mm single core insulated flexible Copper cable. SITC of Test Link Joint Kit in a IP 66 weather proof enclosure of suitable dimension SITC of Accessories to run the down conductor of above quantity.
SAJAD HUSSAIN AND SONS Prop. Sajad Hussain
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .