Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹2.6 LAccepted-AOC | L1 | Accepted-AOC L1 bidder | |
| 2 | L2₹5.4 L+₹2.7 L (102.1%)Rejected-AOC | L2 | Rejected-AOC L2 bidder |
Tender Value
₹2.5 L
EMD Value
₹5,000
Closing Date
9 Apr 2018, 11:30 amClosed
Airprot Director Jabalpur Airport
Airprot Director Jabalpur Airport Airports Authority of India, Jabalpur, MADHYA PRADESH 482005 Ph 07612603454, FAX 0761-2603455
Supply and installation of material with testing and commissioning of two Earthings for protection of electronic systems and two Earthings with Lightening Arrestors at Jabalpur Airport
2018_AAI_8773_1
AAI/CNS/WR/VAJB/2018/NEW ATC/ELA/7
Open Tender
Electrical Goods/Equipment
Lump-sum
60 days
Jabalpur Airport
as per NIT document
2 documents required · 2 mandatory
₹1,180
Yes
Airports Authority of India
₹5,000
Yes
20 Jan 2020
16 Mar 2018
13 Apr 2018
19 Mar 2018
9 Apr 2018
19 Mar 2018
16 Mar 2018 - 5 Apr 2018
Amount
Items to be supplied
Copper plate_1foot X 1foot X 3mm_ Purity Not Less than 90% of material.
Copper strip 25mm X 3mm (Cross section Dimensions) _ Purity Not Less than 90% of material.
Galvanized pipe _3inchX1.5mmX10feet
Galvanized Pole _3inchX1.5mmX20feet
Iron Chamber _1.5’X1.5’X0.25’,of3mm sheet
Charcoal
Clay, Soft Soil
Copper Lightening arrestor Device Type:Copper Ball Mounted with five radiating out 2”long light arresting spikes. Or any other type as per the discretion of Incharge CNS. Total weight atleast 250gms & purity Not Less than 90% of material.
Works to be carried out
Digging of 5’X5’X10’(depth) sized pits on Semi rocky soil.
Masonry brick work of size 2.5’X2.5’X3’ and mounting of pole.
Placement in above four pits the above copperplates, GI pipes. Refilling of Salt, charcoal, and Softsoil. Measurement of “Earth resistance” at each earth pit without external connections. Note:-If value is beyond 1.5 Ω (Ω=ohms) in above measurements, the payments will not be made. Clamping and Fitting of copper strip with proper flat clamps. Brazing works of all joints in earthing and Lightening arrestor circuit.
Repair works of RCC Base 5’X5’X6”(depth) at four earthing sites and mounting of Iron chamber thereafter. Clearing of debris and removal of unwanted material around earth pits. Commissioning after completion of all works.
RIGHT ENGINEERING
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .