Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹35.4 CrAccepted-AOC UDAYAVANI BUILDING UDAYAVANI ROAD PRESS CORNER MANIPAL 576104 UDUPI D KARNATAKA | UDUPI | KARNATAKA | 576104 | ₹35.4 Cr | L1 | Accepted-AOC Being L1 Bidder |
| 2 | L2₹39.9 CrRejected-Finance | ₹39.9 Cr | L2 | Rejected-Finance Not Being Lowest |
| 3 | L3₹39.9 CrRejected-Finance | ₹39.9 Cr | L3 | Rejected-Finance Not Being Lowest |
| 4 | L4₹42.0 CrRejected-Finance 11 JAMES HICKEY SARANI FORMALLY KNOWN AS DACRES LANE 2ND FLOOR KOLKATA 700069 | KOLKATA | KOLKATA | WEST BENGAL | 700069 | ₹42.0 Cr | L4 | Rejected-Finance Not Being Lowest |
| 5 | L5₹43.9 CrRejected-Finance 18A PARK STREET 6 0 1 STEPHEN COURT LIFT NO 1 KOLKATA WB 700071 | KOLKATA | KOLKATA | WB | 700071 | ₹43.9 Cr | L5 | Rejected-Finance Not Being Lowest |
| Sl No | Description | Qty | Unit | Adhunik Infrastructures Pvt Ltd L6 | D R STEEL CONSTRUCTION COMPANY PRIVATE LIMITED L4 | M/s Manipal Energy and Infratech Ltd. L1 | Narayan Kumar Infrastructure Pvt Ltd L7 | PROSPECTS INFRA PVT LTD L3 | NARULA INFRASTRUCTURE PRIVATE LIMITED L2 | COAL MINES ASSOCIATED TRADERS PRIVATE LIMITED L5 |
|---|---|---|---|---|---|---|---|---|---|---|
| 1.00Note:- 1. The bidders/contractors are advised to read tender document & all Corrigendum /ammendments and General Condition of Contracts before entry/quoting the rates. 2. It is highlighted that the certain condition of General Condition of Contracts (IAFW-2249) has been modified as per direction of MoD i.e. inclusssion of Performance Security, deletion of Risk & Cost Provisions and increase in defect liability period all as per tender documents. The tenderers should keep in mind while quoting their offer. NOTE (Applicable for all items/parts):- The bidders/contractors are advised to refer Notes on BOQ/SCH'A' before entry/quoting the rates. Lumpsum price workedout by the tenderer for BUILDINGS WORKS as listed in Schedule ‘A’ Part-I.(A) [Design and Construction of Building] | ||||||||||
| 1.01 | Design and Construction of Building for Children Schoool including Canteen Cum Stationary/ Xerox Shop, Static Terrace Tank (Roof Top) of 10,000 Lit Capacity and Ramp with RCC framed Structure and permanent specification including all fitting and fixtures etc. Complete all as specified and all as shown on drawing. | 1 | Each Block | 39,85,00,000 ₹39.9 Cr | 28,07,94,441.5 ₹28.1 Cr | 22,28,46,250 ₹22.3 Cr | 46,50,00,000 ₹46.5 Cr | 27,65,00,000 ₹27.6 Cr | 27,75,00,000 ₹27.8 Cr | 30,97,12,450 ₹31.0 Cr |
| 1.02 | Design and Construction of Building of Pump House with RCC framed Structure and permanent specification including all fitting and fixtures etc. Complete all as specified and all as shown on drawing. | 1 | Each Block | 30,00,000 ₹30 L | 26,56,925 ₹26.6 L | 17,49,929.5 ₹17.5 L | 40,50,000 ₹40.5 L | 18,75,000 ₹18.8 L | 18,75,000 ₹18.8 L | 21,33,250 ₹21.3 L |
| 1.03 | Design and Construction of Sentry / Guard Post with all fitting and fixtures etc. Complete all as specified and all as shown on drawing. | 2 | Each | 1,12,000 ₹2.2 L | 2,28,425 ₹4.6 L | 1,40,745 ₹2.8 L | 7,65,000 ₹15.3 L | 1,50,000 ₹3 L | 1,50,000 ₹3 L | 1,61,938 ₹3.2 L |
| 1.04 | Construction of CYCLE STAND (BLOCK OF 100 CYCLE) (04 BLOCKS) with RCC framed Structure and permanent specification including all fitting and fixtures etc. Complete all as specified and all as shown on drawing. | 1 | Each | 51,00,000 ₹51 L | 99,93,775 ₹99.9 L | 50,00,000 ₹50 L | 54,62,500 ₹54.6 L | 54,50,000 ₹54.5 L | 50,00,000 ₹50 L | 60,09,984 ₹60.1 L |
| 1.05 | Construction of CAR PARKING (BLOCK OF 20 CARS) (01 BLOCK) and BIKE / SCOOTER PARKING (BLOCK OF 80 BIKE) (01 BLOCK) with RCC framed Structure and permanent specification including all fitting and fixtures etc. Complete all as specified and all as shown on drawing. | 1 | Each | 62,50,000 ₹62.5 L | 1,06,14,700 ₹1.1 Cr | 65,00,000 ₹65 L | 65,03,700 ₹65.0 L | 65,00,000 ₹65 L | 65,00,000 ₹65 L | 71,62,158 ₹71.6 L |
| 1.06 | Design and Construction of UG Sump of 50,000 Gallon Capacity with all fitting and fixtures etc. Complete all as specified and all as shown on drawing. | 1 | Each | 13,50,000 ₹13.5 L | 45,68,315 ₹45.7 L | 45,00,000 ₹45 L | 12,50,000 ₹12.5 L | 45,00,000 ₹45 L | 45,00,000 ₹45 L | 35,97,533 ₹36.0 L |
| 1.07 | Design and Construction of Badminton Court with all fitting and fixtures etc. Complete all as specified and all as shown on drawing. | 4 | Each | 3,25,000 ₹13 L | 5,75,345 ₹23.0 L | 3,00,000 ₹12 L | 16,00,000 ₹64 L | 2,65,000 ₹10.6 L | 3,00,000 ₹12 L | 3,38,382 ₹13.5 L |
| 1.08 | Design and Construction of Incinerator with all fitting and fixtures etc. Complete all as specified and all as shown on drawing. | 1 | Each | 10,00,000 ₹10 L | 62,885 ₹62,885 | 15,00,000 ₹15 L | 1,10,000 ₹1.1 L | 14,00,000 ₹14 L | 15,00,000 ₹15 L | 1,49,244 ₹1.5 L |
| 1.09 | Design and Construction of Flag Staff with all fitting and fixtures etc. Complete all as specified and all as shown on drawing. | 1 | Each | 75,000 ₹75,000 | 52,325 ₹52,325 | 1,25,000 ₹1.3 L | 1,28,000 ₹1.3 L | 1,25,000 ₹1.3 L | 1,25,000 ₹1.3 L | 1,46,404 ₹1.5 L |
Tender Value
₹41.5 Cr
EMD Value
₹15 L
Closing Date
26 Aug 2025, 6:00 pmClosed
HQ CE KOLKATA ZONE
Shri Somesh Kumar, IDSE Chief Engineer Address HQ Chief Engineer Kolkata Zone Military Engineer Services Ballygunge Maidan Camp Gurusaday Road Kolkata 700019
Provn of Children School at Panagarh Mil Stn
2025_MES_720529_1
89100/E8
Open Tender
Civil Works
820 days
PANAGARH
Class SS Cat a i
8 documents required · 8 mandatory
₹3,000
GE(P) PANAGARH
₹15 L
Yes
HQ CE Kolkata Zone
15 Oct 2025
15 Jul 2025
2 Sept 2025
15 Jul 2025
26 Aug 2025
12 Aug 2025
31 Jul 2025
Amount
Note:- 1. The bidders/contractors are advised to read tender document & all Corrigendum /ammendments and General Condition of Contracts before entry/quoting the rates. 2. It is highlighted that the certain condition of General Condition of Contracts (IAFW-2249) has been modified as per direction of MoD i.e. inclusssion of Performance Security, deletion of Risk & Cost Provisions and increase in defect liability period all as per tender documents. The tenderers should keep in mind while quoting their offer. NOTE (Applicable for all items/parts):- The bidders/contractors are advised to refer Notes on BOQ/SCH'A' before entry/quoting the rates. Lumpsum price workedout by the tenderer for BUILDINGS WORKS as listed in Schedule ‘A’ Part-I.(A) [Design and Construction of Building]
Design and Construction of Building for Children Schoool including Canteen Cum Stationary/ Xerox Shop, Static Terrace Tank (Roof Top) of 10,000 Lit Capacity and Ramp with RCC framed Structure and permanent specification including all fitting and fixtures etc. Complete all as specified and all as shown on drawing.
Design and Construction of Building of Pump House with RCC framed Structure and permanent specification including all fitting and fixtures etc. Complete all as specified and all as shown on drawing.
Design and Construction of Sentry / Guard Post with all fitting and fixtures etc. Complete all as specified and all as shown on drawing.
Construction of CYCLE STAND (BLOCK OF 100 CYCLE) (04 BLOCKS) with RCC framed Structure and permanent specification including all fitting and fixtures etc. Complete all as specified and all as shown on drawing.
Construction of CAR PARKING (BLOCK OF 20 CARS) (01 BLOCK) and BIKE / SCOOTER PARKING (BLOCK OF 80 BIKE) (01 BLOCK) with RCC framed Structure and permanent specification including all fitting and fixtures etc. Complete all as specified and all as shown on drawing.
Design and Construction of UG Sump of 50,000 Gallon Capacity with all fitting and fixtures etc. Complete all as specified and all as shown on drawing.
Design and Construction of Badminton Court with all fitting and fixtures etc. Complete all as specified and all as shown on drawing.
Design and Construction of Incinerator with all fitting and fixtures etc. Complete all as specified and all as shown on drawing.
Design and Construction of Flag Staff with all fitting and fixtures etc. Complete all as specified and all as shown on drawing.
Design and Construction of Foot Ball Ground / Hockey Ground with all fitting and fixtures etc. Complete all as specified and all as shown on drawing.
Design and Construction of Volley Ball Court with all fitting and fixtures etc. Complete all as specified and all as shown on drawing.
Lumpsum price workedout by the tenderer for BUILDINGS WORKS as listed in Schedule ‘A’ Part-I.(B) [Preprised By MES]
Construction of Refuse Bin with all fitting and fixtures etc. Complete all as specified and all as shown on drawing.
Construction of Fire Point with all fitting and fixtures etc. Complete all as specified and all as shown on drawing.
Construction of Basket Ball Ground with all fitting and fixtures etc. Complete all as specified and all as shown on drawing.
Lumpsum price workedout by the tenderer for SITE CLEARENCE, AREA DEVELOPMENT, EARTH WORK & EXCAVATION as listed in Schedule ‘A’ Part-II.
Lumpsum price workedout by the tenderer for INTERNAL ELECTRIFICATION as listed in Schedule ‘A’ Part-III.
Lumpsum price workedout by the tenderer for INTERNAL WATER SUPPLY as listed in Schedule ‘A’ Part-IV.
Lumpsum price workedout by the tenderer for REFRIGERATION AND WATER COOLER as listed in Schedule ‘A’ Part-V.
Lumpsum price workedout by the tenderer for FIRE FIGHTING AND FIRE ALARM SYSTEM as listed in Schedule ‘A’ Part-VI.
Lumpsum price workedout by the tenderer for DIRECT GENERATOR SET (DG SET) as listed in Schedule ‘A’ Part-VII.
Lumpsum price workedout by the tenderer for ROAD/PATH/CULVERT/HARD STANDING as listed in Schedule ‘A’ Part-VIII.
Lumpsum price workedout by the tenderer for AREA DRAINAGE as listed in Schedule ‘A’ Part-IX.
Lumpsum price workedout by the tenderer for SEWAGE DISPOSAL as listed in Schedule ‘A’ Part-X.
Lumpsum price workedout by the tenderer for EXTERNAL WATER SUPPLY as listed in Schedule ‘A’ Part-XI.
Lumpsum price workedout by the tenderer for EXTERNAL ELECTRIC SUPPLY as listed in Schedule ‘A’ Part-XII.
Lumpsum price workedout by the tenderer for CHAIN LINK FENCING & GATE as listed in Schedule ‘A’ Part-XIII.
Lumpsum price workedout by the tenderer for RAIN WATER HARVESTING / RECHARGE PIT as listed in Schedule ‘A’ Part-XIV.
Lumpsum price workedout by the tenderer for HORTICULTURE as listed in Schedule ‘A’ Part-XV.
Sch 'A' Part-XVI (MISC B&R AND E&M ITEMS) Note : This schedule is not pre-priced by MES and the pre-priced rate indicated as "Rs 0.00" under Col. 5 siginifies this fact only. COMMON ITEM FOR ALL SCHEDULE
Material & Labour for mixing of Fly ash, Clinker & stone dust in proportion of 1:3:6 ( i .e 10 % Fly ash, 30% Clinker and 60% Stone dust) laying , watering , ramming and compacting with vibratory roller to get min CBR value 8% and Dry density 97 % placed at required camber and gradient complete as specified and as directed.
INTERNAL ELECTRIFICATION
Supply and fixing modular metal flush box 8 Module complete all as specified and as directed.
Supply and fixing power unit 6 module flush type with starter, DP MCB and plug top with indicator complete all as specified and as directed.
Supply and fixing RJ-11 Telephone Socket 1 Module complete all as specified and as directed.
Supply and fixing Coaxial TV Socket 1 Module complete all as specified and as directed.
Supply and fixing coaxial cable CCA copper cotted alloy 100 M GHz 75 Ohm Durect TV Dish Cable TV, Antena, Satelite, DVR and Amplifiers complete all as specified and as directed.
Supply and fixing MCB 40 Amps, FP, 240 Volt "C" series, breaking capacity 10 KA including making incoming and outgoing connections complete all as specified and as directed.
Supply and fixing MCB DB TPN 4 ways (double door) IP-43, IK-9 protection with MCCB incommer including bus bar neutral link, earth bar and din rail, recessed with wall surfaces by chase cutting and making good surfaces of wall complete all as specified and as directed
Supply and fixing MCCB triple pole and neutral (Four pole) 100 Amp, 415 volts, 50 Hz, having thermal setting range 70% to 100% and fixed magnetic setting and breaking capacity 16 KA including making incoming and outgoing connections complete all as specified and as directed.
INTERNAL WATER SUPPLY
Supply and fixing chromium plated soap dish holder complete all as specified and as directed.
Supply and fixing wall mounted heavy duty stainless Steel Grab Bar rails (Set of Two) of 23 inch size suitable for use in bathroom of physical handicapt children fixed with CP screw complete all as specified and as directed.
Supply and fixing 15mm bore two way bib taps cast copper alloy chromium plated with crutch or butterfly handle, screwed down, screwed for any type of pipe suitable for connecting with health faucet complete all as specified and as directed.
Supply and fixing chromium plated Peg set of three complete all as specified and as directed.
Supply and fixing hand shower (health faucet) (brass chromium palted) with 8mm dia, 1m long, flexible tube fixed with wall hook complete all as specified and as directed.
REFRIGERATION AND WATER COOLER
Supply and fix Voltage stabilizer for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 170V to 250 V with output voltage stabilized at 230 V with accuracy of ± 2.5% and of capacity 2KVA complete all as specified and as directed.
DIRECT GENERATOR SET (DG SET)
Supply and installation testing and commissioning silent Diesel Engine generating set 415 volts 50 KVA 3 phase 0.8 power factor, 50 Hz, 1500RPM self exicited self regulated brushless AC generator installed including AMF panel, control panel having meter and sound proof canopy as per CPCB norms and foundation etc.suitable for ambient condition at Panagarh and confirming to condition under ISO 3046, IS:10001/ 10002,BS 5514/5000 with capacity of 10% overloading for one hour in every twelve hour duration and including the following accessories :- (A) Alternator:- Synchrounous alternator rated at 50 KVA suitable for continuous operation at 1500 RPM generating 415 volts at 0.8 p.f (lag) suitable for 50 Hz, three phase, 4 wire system.The alternator shall be brushless, single bearing, self excited/ self regulated with an AVR. The alternator will be suitable for climate and shall generally confirm to IS: 4722 :2001. The salient features of the alternators are :- (a) +-1% voltage regulation (max) in static conditions. (b) IP:23 protections with class 'H' insulation. (c) Permanent lubricating bearing. (B) Diesel Engine:- Adquate capacity of diesel engine water cooled to drive independently above alternator and after considering de-rating as per site conditions after generating and reducing power consumed by accessories directly coupled through flexible coupling multi cylinder multi stroke direct injection, cold starting 1500RPM, as per latest CPCB 4 + norms compliance upto latest ammendment complete with standard accessories.
FIRE FIGHTING AND FIRE ALARM SYSTEM
Supply and fixing Cast Iron Air Valves with double air Outlets, conforming to IS 14845 of size 50 mm dia bore and fixing up in Water supply mains pipe complete all as specified and as directed.
Supply and laying of control cable PVC insulated PVC sheathed galvanised steel strip or wire armoured with stranded copper conductor of size 1.5 sqmm 2 core 11 Volts grade complete all as specified and as directed.
Supply, installation,testing and commissioning of micro processor based,digital,distributed processing real time,multi tasking and multi - user type 4 loops as per Analogue addressable type fire alarm control panel (FACP) and control panel shall have the following features including supply of all fixing materials interconnections earthing complete as required. (1) FACP shall be suitable for operating on 230V 50HZ AC supply and smoke detectors shall be powered using FACP based smoke detection circuits.Devices shall receive power and communication from the same pair of conductors. (2) FACP shall provide for resetting smoke detectors fault isolation and sensor loop operation. (3) FACP shall be suitable for mixing different fire devices and beam smoke detectors with in the same loop to optimize field wiring.
(4) FACP shall have alarm indication of individual sensors detector trouble alarm indication for dust accumulation.The panel shall check detectors once in every 24 hours for contamination for this purpose. (5) The FACP shall regularly supervise all the sensors and devices on the loop and initiate fire or trouble alarm whenever required. (6) FACP shall be with repeater interface and suitable 24V battery with built in software and 2x40 character alphanumeric LCD display and necessary front panel control keys.FACP shall display the date time and description for Anologue sensors to indicate alarm and trouble situations. (7) FACP switch shall allow authorised personal to accomplish the following:- a) Initiate general alarm condition b) Silence the local audible c) Silence the alarm signals d) Reset all zones /points (8) FACP shall have walk-test facility
(9) Shall have facility for programming from the key board or utililsing PC set up software via lap top/desk top computer. (10) Shall have memory data for panel configuration and operation reside in non - volatile memory(EPROM) (11) FACP shall have facility for speech processor (to record pre-recorded message of 20 S) and also have auto dialer facility.(Can dial upto 8 different lines) (12) All addressable units shall be connected to the FACP through the loop cards and shall be addressed through individualized numbers.The FACP shall be able to obtain Analogue value for all detectors in the circuit through a pulsed digitized current data.The FACP shall be able to analyze all Analogue inputs from all addressable units and through its own software and ambient level screening.The FACP shall be able to identify fire,possible fire or fault conditions.The unit supervision shall be dynamic and continuos.
(13) The FACP shall itself have all loop cards in it.No isolated mother board or transponder shall be considered (14) Short / open circuit units shall also be reported at the FACP in such cases,the system through the use of fault isolators shall be able to isolate that segment between the two fault isolators.The missing detector /device shall also be reported to the FACP with identification of the location. (15) The FACP shall have the facility to set smoke sensor sensitivity remotely to either high sensitivity manually or on a pre - programmed sequence(ie Day/Night) period. (16) When an alarm condition is sensed at the FACP from smoke or heat detector ,a delay time /alarm verification period shall be started. If the sensor is still in alarm after the delay time expired an alarm condition is reported.The delay time shall be adjusted from 0 to 990 seconds.
(22) It shall be able to with stand the temperature varition from 0 deg.C to 50 deg C.and further RH (non condensing type )up to 95% shall not hamper its performance.The voltage rating shall be from 17V DC to 31V DC though the voltage may change depending upon the working voltage of proprietary FACP (23) The FACP shall be totally enclosed ,dust and vermin proof type made of minimum 16 SWG dust inhibited sheet with oven finish.The FACP shall be completely solid stage design (24) The logic circuitry shall be based on high noise immunity solid state hardware employing modular construction. Logic cards shall be of epoxy fiber glass construction. (25) The FACP shall have EN 54/UL/FM approval. (26) The panel shall have extra loop card to serve as stand by in case of burntout or malfunctioning of any operating loop cards.
Supply and fix, ABC Powder 6 Kg Fire Extinguisher containing Mono Ammonium Phosphate Powder 50, Stored Pressure Type, Pressure Gauge, fittted with discharge hose, wall mounting bracket etc., Discharge Time less than 15 Secs, Controllable discharge mechanism, Range minimum 4 Meters, ISI approved as per IS:15683:2006 complete all as specified and as directed.
Supply and fix, ABC Powder 9 Kg Fire Extinguisher containing Mono Ammonium Phosphate Powder 50, Stored Pressure Type, Pressure Gauge, fittted with discharge hose, wall mounting bracket etc., Discharge Time less than 15 Secs, Controllable discharge mechanism, Range minimum 4 Meters, ISI approved as per IS:15683:2007 complete all as specified and as directed.
Supply and fix, ABC Powder 25 Kg Fire Extinguisher Trolley mounted containing Mono Ammonium Phosphate Powder 50, Stored Pressure Type, Pressure Gauge, fittted with discharge hose, wall mounting bracket etc., Discharge Time less than 15 Secs, Controllable discharge mechanism, Range minimum 4 Meters, a, ISI approved as per IS:15683:2008 complete all as specified and as directed.
Supply and fix, Water Fire Extinguisher Stored pressure type ISI marked conforming to IS: 15683. Capacity 6 litre. Complete with delivery hose, squeeze grip release valve, locking arrangement, pressure gauge, operation manual and bracket. Operating Temperature: +5ºC to + 60ºC complete all as specified and as directed.
Supply and fix, Mechanical foam unit of 9 lts. Capacity with water inlet and foam water out let, foam maker, foam branch pipe etc. complete. Unit shall be fabricated by M.S. sheet with FRP lining inside and whole unit mounted with rubber wheels of suitable size and handle for movements complete all as specified and as directed.
Supply and fix, CO2 type Fire Extinguisher ISI marked conforming to IS: 15683. Capacity 3 Kg. Complete with delivery hose horn, wheel type release valve, locking arrangement, operation manual and bracket. Operating Temperature: - 30ºC to + 60ºC complete all as specified and as directed.
Supply and fix CO2 type Fire Extinguisher Trolley mounted ISI marked conforming to IS: 15683. Capacity 22.5 Kg. Complete with delivery hose horn, wheel type release valve, locking arrangement, operation manual and bracket. Operating Temperature: - 30ºC to + 60ºC compete all as specefied and as directed.
Supply and fix Fire bucket stand suitable upto 4 bucket of 40kg weight compete all as specefied and as directed.
Supply and fix Heavy-Duty Leak-Proof ISI marked Fire buckets (FILLED WITH SAND) round bottom type enamel painted, white inside & Red out side and Letter "FIRE" in black out side and handle with mounting bracket compete all as specefied and as directed.
Supplying and installing of perforated Hot dip Galvanised Iron cable tray Corrosion resistant polyester flame retardent (Galvanisation thickness not less than 50 microns) with perforation not more than 17.50%, in convinient sections, joined with connectors, suspended from the ceiling with GI suspenders including GI bolts and nut etc of 100 mm width x 50mm depth x 2.0 mm thickness compete all as specefied and as directed.
Supply , install, testing and commissioning of cubical housing cabinet type CPRI approved Confirming to IP55 LT panel board outdoor type, platform mounted factory made, totally enclosed dust and vermin proof openable from both front and rear side made out of 3.15 mm thick CRCA MS Sheet and built upon suitable size MS angle iron frame work, having front and rear hinged doors, lifting lugs (2 Nos), earthing strips at rear side, bottom detachable gland plate complete with suitable size zinc plated and passivated nut, bolts, spring and washers. The cabinet and all members should be chemically treated with MSR solution for anticorrosive treatment and apply spray paint with two coat of synethetic enamel paint over a coat of red oxide primer. The panel should be suitable for 415 volts, 50Hz, 3 phase 4 wire system and internal connection should be provided with aluminium strips of suitable size and necessary foundation work and comprising following (For Fire Pump) :-
SEWAGE DISPOSAL
Material and Labour for Design and Construction of RCC Septic tank coventional type designed to carry sewage and sullage water, excavation in any type of soil, PCC 1:4:8 below foundation, RCC M-30 Design Mix in Walls, Base Slab , Baffle walls and Roof Slab including beams etc with Vent shaft, manhole openings with cover connection etc. complete with effective depth of 1.5 meter and overall depth of 3 meter for 150 users complete as directed.
Material and Labour for Design and Construction of Soakage wells excavation, in any type of soil, foundation in PCC 1:3:6, walls of honey combed masonry with top ring of M25 concrete including intercepting chamber and screen chamber made of Brick masonary in CM, RCC cover slab in M25/ SFRC cover, interconnecting pipes of RCC/DWC complete filled with brick bats of size 2.4 M dia X 4.5 M effective depth for 150 users complete as directed.
EXTERNAL WATER SUPPLY
Supply and laying of pipe ductile Iron, socket & spigot type, Class “K-9”, 150 mm nominal dia complete all as specified and as directed.
Supply and laying of pipe ductile Iron, socket & spigot type, Class “K-9”, 100 mm nominal dia complete all as specified and as directed.
Supply and laying of pipe ductile Iron, flanged type, Class “K-9”, 150 mm nominal dia complete all as specified and as directed. (For borewell to UG Sump )
Supply and laying of pipe ductile Iron, flanged type, Class “K-9”, 100 mm nominal dia complete all as specified and as directed. (For UG Sump to IRP )
Material & labour for DI specials like Bends (any type, radius and angle) tapers any type (straight, bend, increasing,decreaing or double socket etc) Tee pieces single branch "Y" junction, double branch, cross for DI pipe upto 200 mm bore complete all as specified and as directed.
Supply and fixing 80mm bore Gun metal gate valve with iron wheel head and gun metal spindle screwed both ends complete all as specified and as directed.
Supply and fixing 100mm bore cast iron foot valve with bolts, nuts and washers conforming to IS-4038, PN 0.2 complete all as specified and as directed.
Material and labour for Construction of brick masonry chamber of 90 cm x 90 cmx 90 cm [internal dimensions] suitable for 150 mm/200 mm bore sluice valve with PCC 1:4:8 type D2 using 40 mm graded stone aggregate for foundation brick wall with sub class ‘B’ brick, old size built in CM 1:6 PCC [1:2:4] type B1 [using 20 mm graded stone aggregate for coping rendering in CM [1.4] 15 MM thick including provision of MS sheet cover 3 mm thick including handle, hinges locking arrangements etc with two coats of synthetic enamel paint over a coat of red oxide primer to steel surfaces and locking arrangement including necessary excavation and earth work in any type of soil complete all as specified and as directed.
Material and labour Construction of brick masonry chamber of 60 cm x 60 cmx 60 cm [internal dimensions] suitable for 50mm bore sluice valve with PCC 1:4:8 type D2 using 40 mm graded stone aggregate for foundation brick wall with sub class ‘B’ brick, old size built in CM 1:6 PCC [1:2:4] type B1 [using 20 mm graded stone aggregate for coping rendering in CM [1.4] 15 MM thick including provision of MS sheet cover 3 mm thick including handle, hinges locking arrangements etc with two coats of synthetic enamel paint over a coat of red oxide primer to steel surfaces and locking arrangement including necessary excavation and earth work in any type of soil complete all as specified and as directed.
Drilling of bore (Trial Bore) of size 250 mm dia upto 200 mtr depth by direct rotary/ DTH mechanical system for injection well in any kind of soil strata including hard stone/boulders and submitting the strata detail both graphically recorded as well as strata results including testing of yield , complete all as specified and as directed.
Reaming of bore well from 250 mm dia to 525 mm dia hole in three steps from 250 mm to 350 mm, 350 mm to 450 mm and 450 mm to 525 mm dia bore siutable for lowering ERW Mild steel casing pipes and gravel packing for the required length (i.e 40 mtr depth) below the ground level, complete all as specified and as directed.
All as per item no 24.11 here-in-before but exceeding 40 mtr and upto 150 mtr depth, complete all as specified and as directed.
Supply, assembling, lowering and fixing in position 250 mm nominal (10") bore ERW MS housing pipe, ISI marked, of 8 mm wall thickness, screwed and socketed in random length upto 6 mtr including fitting of centralizer at regular interval into bore hole to a depth upto 40 mtr from ground level, as per IS 3589, painted both inside and outside with black bituminous paint suitable for drinking water purpose including necessary fittings & fixtures by jointing electric welding, complete all as specified and as directed.
Supply, assembling, lowering and fixing in position 200 mm nominal (8") bore ERW MS housing pipe, ISI marked, of minimum 6.0 mm wall thickness, screwed and socketed in random length upto 6 mtr including fitting of centralizer at regular interval into bore hole to a depth exceeding 40 mtr and upto 150 mtr from ground level, as per IS 3589, painted both inside and outside with black bituminous paint suitable for drinking water purpose including necessary fittings & fixtures by jointing electric welding, complete all as specified and as directed.
Supply, assembling, lowering and fixing in position 200 mm bore, low carbon galvanized (LCG) strainer 'V' wired type of 7 mm thickness with 1 mm continuous slot to offer not less than 56% open area, beveled end, but jointed and welded in suitable length with MS flat iron 50 mm x 6 mm coupler ring all around the pipe. complete all as specified and as directed.
Supply and fixing mild steel reducing socket suitable for (250 x 200 mm ) bore casing pipe, 10 mm thick, fitted to casing pipe as per IS 2800 by means of electric welding ,complete all as specified and as directed.
Material and labour for carrying out electro logging test upto complete drilling depth of tube well for fixing water strata and submitting of Report including its interpretation by a qualified Hydrologist/ground water expert, complete all as specified and as directed.
Material and labour for Yield test with the help of V notch for bore well by continiously pimping for 16 hrs to determine safe pumping yield, complete all as specified and as directed. (Note : Rate quoted by contractor shall deemed to be inclusive the rate of Pump, DHPP and required T&P )
Supply and fixing mild steel bail plug assembly having 3.00 m length suitable for 200 mm bore casing pipe internal threaded with strong iron hook, screwed and welded to casing pipe as per IS 2800, complete all as specified and as directed.
Supply, filling and packing washed pea gravels of size 2 mm to 4.6 mm all around casing pipe and slotted pipe, complete all as specified and as directed
Supply and fixing mild steel housing clamps 1200 mm long 100 mm wide, made out of 20 mm thick MS plate made to shape for 250 mm bore casing pipe with necessary bolts, nuts and washers at ground level, complete all as specified and as directed.
Developing of tube well by means of air compressor, for number of hours, until sand free clear potable water is obtained including testing by using diesel engine driven turbine pump to get maximum yield and discharge including supply of yield test result, complete all as specified and as directed. (Note : Rate quoted by contractor shall deemed to be inclusive the rate of DHPP and required T&P )
Supply and fixing pressure gauge with isolation cock suitable for a working pressure of 7 Kg/cm² (Liquid based High Intensity), complete all as specified and as directed.
Supply and fixing mild steel wire chains with dia of links 10mm, for securing sbmersible pump set, complete all as specified and directed.round strand steel wire rope dia 12 mm and connected clamp nut bolts fixed, complete complete all as specified and as directed.
Supply and fixing 80 mm bore galvanized steel tubing medium grade, 6.00 metre long in twin arrangements as in gravel filling arrangement to bore well fixed 5 metre below ground level and 1 metre above ground level, inclined at an angle of 40 degree from horizontal plane of ground, including PCC (1:2:4) foundation of size 1m X 1m X 0.75m complete all as specified and as directed. Note- PCC foundation block for the pipes will be measured and paid separately under respective items in this schedule.
Supply, fixing and lowering 100 mm bore MS column pipe (seamless) both end flanged 3.00 metre long, fitted with flanges at both ends made out of heavy garde pipes of not less than 5.4 mm wall thickness ISI marked (IS: 1239 Part-1) complete with bolts,nuts,gaskets etc. as required complete all as specified and as directed.
Supply and fixing well cap made out of 5 mm thick MS plate with provn of suitable holes for passing two runs of flat 3 core PVC insulated sumersible cable motor and one run of SWR, 100 mm dia column pipe and suitable for fixing 250 mm nominal bore ERW heavy duty MS of 8.0 mm wall thickness casing pipe complete all as specified and as directed.
Testing of bore well raw water for all parameters, chemicals, bacteriological and arsenic aspect from any Govt approved recommended laboratory complete all as specified and as directed.
Supply, install, lowering, testing & commissioning of Submersible pump set 8 stage Suitable for minimum head 40 Mtr with 300 LPM discharge electric driven 7.5 HP, 415 V AC, TP with operational efficiency performance and durability wide voltage range 350-440 Volts super finished water lubricated bush bearing , with less speed drop motors with teflon bearing and sand guard complete all as specified and directed. (One running and one stand by)
Supply and lowering PVC insulated sheathed 3 core flat submersible cable with copper conductor 10 Sqmm 1100 Volt grade including cable clips for fixing complete all as specified and as directed.
Supply and fixing submersible cable straight through jointing kit for 10 Sqmm 3 core flat cable complete all as specified and as directed.
Supply and fixing sample box for displaying samples for strata made out of teak wood plants 25 mm thick board, of size (outer size of box) 1000mm x 1000mm provided with sample box (inside) of sizes 100mm x 100mm x 100mm complete all as specified and directed.
Supply, install, connecting, testing & commissioning of high pressure single head adjustable chemical dozing system of the following specification:- a) Adjustable high pressure 100 PSIG power input 230 V, 50 Hz, max flow rate 02 US GPD to 40 US GPD with mandatory assecceries like lead tubing connecting ferrules, check valves, etc. alongwith 100 Ltr capacity FRP tnk as preperation tank. b) Prepration tank, dozing tank, consist of water inlet line, outlet with Y strainer, overflow conical bottom for sludge deposition and agitator as per OEM Specification.
Supply and Installation of Iron remover plant complete with pressure filter, catalytic media, air compressor, back washing facility including RCC foundation of capacity 5000 gallon/hrs, Consisting of following: (a) Supply, installation, testing and commissioning of down flow MULTIGRADE FILTER having capacity 22700 LPH/5000 GALLON PER HOUR consisting vertical cylindrical mild steel pressure vessel with dished end, having size of 1000 mm dia X 1875 mm height Vertical type one set of 80 mm dia nominal bore frontal mild steel pipe work for inlet, outlet, back wash and rinse line and 5 No butter fly valve having hand lever type complete all as specified and directed. Note: - (i) The pressure vessel shall be made of medium Grade MS Sheet 4 mm thick (ii) Dished ends shall be machine made of medium Grade MS Sheet 5 mm thick (iii) The filter plant shall ensure even distribution across the surface area of the filter bed, header, lateral system & bottom collecting system. (iv) The plant shall have Air release arrangement with 2 No pressure gauge to monitor head loss across the filter and sampling cocks on inlet and outlet ends. The filter plant shall have full charge of filter media as per manufacturer’s design (v) Depth of filter media shall 915 mm and total media quantity shall be as per OEM specification. (Gravels, Pebbles, Silex, Core Silex & Sand). (vi) The filter have man hole, hand hole and supporting legs.
(vii) The job shall include necessary surface dressing, PCC/RCC foundation as required complete all as specified & as directed by manufacturer & the same duly approved by officer. (viii) The vessel shall be painted internally with 2 coats of anticorrosive and nontoxic black bituminous paint (compatible with drinking water) and external surface shall be painted with 2 coats of Synthetic Enamel paint over a coat of red oxide primer (ix) The plant shall be designed for a flow of 22700 LPH (x) The MULTIGRADE FILTER shall have first fill of filter as per manufacturer’s instruction. (xi) The TURBIDITY after treatment from should be <=1 PPM. (xii) The backwash frequency shall be every 12 hours (twice a day) for continuous operating unit. If unit is operated intermittently, the total operating time in service cycles shall be limited to 5-6 hours before next back wash & back wash time 15-20 minutes. TECHNICAL SPECIFICATION: MULTIGRADE FILTER FLOW RATE(m3/hr) - 35 QUANTITY(NOS) - 1 FILTER DIA(MM) - 1000 FILTER HEIGHT(MM) – 1875 SHELL THICKNESS(MM) - 4 DISHEND THICKNESS(MM) - 5 FRONTAL PIPE WORK(MM) - 80 MEDIA DEPTH(MM) - 915
MEDIA QUANTITY - 1746 KG BACKWASH TIME - 20-30 Minutes (b) Inter connecting pipe work-MSEP for Multigrade Filter (c) Supply, installation, testing and commissioning of down flow OXIDIZATION PLANT having capacity 22700 LPH/5000 GALLON PER HOUR consisting vertical cylindrical mild steel pressure vessel with dished end, having size of 850 mm dia X 1875mm height Vertical type one set of 80 mm dia nominal bore frontal mild steel pipe work for inlet, outlet, back wash and rinse line and 5 No butter fly valve having hand lever type complete all as specified and directed. Note: - (i) The pressure vessel shall be made of medium Grade MS Sheet 4 mm thick (ii) Dished ends shall be machine made of medium Grade MS Sheet 4 mm thick (iii) The filter plant shall ensure even distribution across the surface area of the filter bed, header, lateral system & bottom collecting system. (iv) The plant shall have Air release arrangement with 2 No pressure gauge to monitor head loss across the filter and sampling cocks on inlet and outlet ends. The filter plant shall have full charge of filter media as per manufacturer’s design (v) Depth of filter media shall 915 mm and total RESIN quantity shall be as per OEM specification. (vi) The filter have man hole, hand hole and supporting legs.
(vii) The job shall include necessary surface dressing, PCC/RCC foundation as required complete all as specified & as directed by manufacturer & the same duly approved by officer. (viii) The vessel shall be painted internally with 2 coats of anticorrosive and non toxic black bituminous paint (compatible with drinking water) and external surface shall be painted with 2 coats of Synthetic Enamel paint over a coat of red oxide primer (ix) The plant shall be designed for a flow of 22700 LPH TECHNICAL SPECIFICATION: IRON REMOVAL FILTER - FLOW RATE(m3/hr) - 35 QUANTITY(NOS) - 1 FILTER DIA(MM) - 850 FILTER HEIGHT(MM) - 1875 SHELL THICKNESS(MM) - 4 DISHEND THICKNESS(MM) - 4 FRONTAL PIPE WORK(MM) - 100 MEDIA DEPTH(MM) - 915 MEDIA NAME - MNO2 MEDIA QUANTITY(KG) - Shall be as per OEM specification BACKWASH TIME - 20-30 Minutes.
(d) Interconnecting pipe work-MSEP for Oxidation Chamber (e) Supply, installation, testing and commissioning of Sodium Hypochlorite Dosing Pump capacity 0-6 LPH & 0.4kg/cm2 with 150 ltr LDPE Dosing Tank Note:- (1) The CGW report shall be made available to the department. (2) The Capacity of Iron removal plant is indicative. The Iron removal plant shall be designed based on the water testing report. (3) Necessary chlorination plant must be catered for the treatment of bore well water in addition to above items (4) The vessel must be filled up with specially grade MnO2 (minimum 65% purity) and gard coke catalyst media of quantity as per manufacturer instructions with supporting under bed media.
Supply, Install, testing and commissioning of air compressor reciprocating type, horizontal model of capacity as recommended by OEM of IRP coupled with electric motor of suitable capacity for 440 Volts, 3 phase 502 Hz complete with Air receiver safety valve including copper cable connection from main panel to starter and starter to motor, DOL starter panel, PCC/RCC foundation, earth workand providing 15mm dia GI pipe medium grade from compressor to oxidation chamber including air filter etc complete all as per specification of manufacturer and as directed by Engr-in- Charge.
Supply, install, commissioning and connecting of water level indicator made out of stainless steel (scale min 150mm width & 1 m in length) including floats, PVC rope, SS pully, pully cover, etc complete all as specified and as directed.
EXTERNAL ELECTRIC SUPPLY
Supply & fixing junction box with 3 phase terminals and size of box 155x210x92 or nearest higher size grade of polycarbonate body with IP 66/67 degree of protection, dust proof water tight, shock proof fire retrant with internally embeddedgasket fitted with heat treated bakelite terminals blocks and PVC glands for cable entry complete all as specified and as directed.
Supply & fixing Three core 1.5sqmm (nominal area) service wire PVC insulated copper conductor FRLS, multi stranded, unsheathed 1100 volts grade IS-694 marked for connection from junction box to street light fitting through steel pole with necessary clamps, bolts, etc required for fixing complete all as specified and as directed.
Supply , install, testing and commissioning of cubical housing cabinet type CPRI approved Confirming to IP55 LT panel board outdoor type, platform mounted factory made, totally enclosed dust and vermin proof openable from both front and rear side made out of 3.15 mm thick CRCA MS Sheet and built upon suitable size MS angle iron frame work, having front and rear hinged doors, lifting lugs (2 Nos), earthing strips at rear side, bottom detachable gland plate complete with suitable size zinc plated and passivated nut, bolts, spring and washers. The cabinet and all members should be chemically treated with MSR solution for anticorrosive treatment and apply spray paint with two coat of synethetic enamel paint over a coat of red oxide primer. The panel should be suitable for 415 volts, 50Hz, 3 phase 4 wire system and internal connection should be provided with aluminium strips of suitable size and necessary foundation work and comprising following (For Sentry post & Street Light) :-
Supply, installation and commissioning of Compact Secondary Substation (CSS) 315KVA comprising to following parameters:- (a) CPRI approved CRCA Sheet steel housing 3.15 mm thick with corrosion resistance and all side openable hinged door and lock and key arrangements. (b) Steel parts are tested as per IS 6988. (c) Engineered for smooth air flow for natural cooling. (d) No access to High voltage parts. (e) GI strip earthing for lightening protection and lightening spike etc. (f) Separate earthing for lightening protection and lightening spike etc. (g) Seperation steel sheet wall for CB/ Transformer / LT Panel. (h) Heavy lifting lugs with all equipments load. (j) Slopped roof. (k) Necessary danger plates outside of the CSS. (l) Necessary HT and LT cable / Earth strips opening. (m) Vacuum Circuit Breaker (VCB): Non extensible RMU consisting of 1 no. Mannually operated 11 KV/630 Amps VCB in SF6 isulated stainless enclosure,commissioning of with metering module with necessary CTs and PT, comprising the following :- (Complete unit is to be installed inside CSS, protection accessories, Enclosure: Metal Clad, IP-54 Protection.Protection Relay : Self Powered Alfapneumatic LCD disply type Internal are tested for 1 sec, Fully compartmentalized sheet steel enclosure with automatic safety shutters, GI foundation bolts with provision of cable terminating facilities with powder coated smooth glossy finish and as per follows:
(i) Rated Voltage - 12 KV (ii) Rated Frequency -50Hz. (iii) Rated continuous current rating - 630 Amps (iv) Rated Interrupting Current - 21 KA (v) Rated making current for VCBs - 52 KA. (vi) Rated making current for Isolators-62 KA (vii) Rated short time current for 3 sec -26.3 KA (viii) Operating duty -0-0.3 sec -CO 3 min – CO (ix) Power frequency withstand voltage - 28 KV (x) Impulse withstand voltage - 75 KV. (xi) Bus bar rating - 120% of continuous current. (xii) Operation: Spring closing mechanism - DC moter operated with 24 volt supply, Breaker Closing - Manual & Electrical through TNC switch. (xiii) Shunt Trip coil - 24 V DC (xiv) Safety Interlock Locking facility – Required (xv) Breaker panel indication - ON (RED) / OFF( Green) (xvi) Accessories:Mechanical counter, Space heater with Thermostat, Fuse and ON/OFF switch,Aux relays for remote trip/ indication for PC interface etc, cubicle illumination lamp LED 9 watt retrofit type 230 V AC, T-N Switch, Anti pumping contractor etc. (xvii) Mimic Diagram: An operating mimic diagram shall be provide on the front side of each cubicle
(xviii) Battery Bank with charger for RMU is included in the item rate and rating of battery as described by OEM. (Note:- VCB complete will be obtained directly from the OEM and not from the authorized system assemblers of OEM. The installations, calibration and testing of VCB will be conducted in the presense of authorized representative of OEM by the Contractor.) (n) Transformer 315 KVA Copper wounded dry resin cast distribution type 11/0.433 KV , 3phase, 4 wire LT output 50 Hz DYN 11 suitable for indoor installation of load tape changer with step +7.5% upto (-)7.5% in step of 2.5 % on HT side all technical specification comprising to IS 11171 update version part with all necessary standard fittings and accessories complete after necessary testing after completion with the following specification: (i) Standerd KVA Rating - 315 KVA (ii) Primary Voltage - 11 KV AC (iii)Secondry Voltage - 433 Volts (iv) Neutral earthing should be solidly earth system. (v) Rated Frequency - 50 Hz with +(-) 3% Tolerance.
Materials and labour for undeground boring upto 80 mm dia using trenchless technology for passing through cable without cutting the existing upper surface of raod complete all as specified and as directed.
Supply and fixing LED street light fitting 45 Watt 230 V AC outdoor type having system lumen not less than 110 Lm/W and potted driver with high pressure die cast aluminum housing and heat resistant complete with driver, lamp bracket 40mm dia 1.2m long with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete all as specified and as directed.
Supply, fixing, testing and commissioning of solar street light fitting LED 24 Watt high AIO power LED delivers system lumen output > 120LM/W including minimum life upto 50,000 hrs, confirming to IP-65, Power Suppply > 80%, galvanised steel pole in built, Lithium FERRO PHOSPHATE battery not less than 100 Ah solar panel, charge controller with dusk down sensor with built in mono crystaline panel complete with all necessary accessories as directed. Note:- All excavation earthwork and PCC shall be measured and paid seperately under respective item.
HORTICULTURE
Supply and planting of trees Ashoka Polyalthi longifolia, Thuja orientains, Ficus benjamina (Green black, golden) Thevetia peruviana (Yellow & pink), 4 feet height complete all as specified and as directed.
Supply and planting of shrubs/bushes calliandra haemotocephla & hybrida, caesalpinia, pulcherrima and flava croton (codiaeum diff varieties) Eranthemum sp Excocecaria, Bicolor and ticolor, hibiscus (Jaba diff varieties) Ixora (db pink & red) Tabaemaemontana cornaria (Tagor), ticoma gaudi chaudi etc. 1'6" height complete all as specified and as directed.
Supply and planting of hedge/Edge cropton (Small/board leaves) Alternanthera, Duranta, Kamini (Murraya exotica) 1 feet height (Min 10 branches/pieces in one bunch) complete all as specified and as directed.
Supply and planting of creepers/climbers passiflor db red, thunbergia sp Ipomoea etc 2 feet height complete all as specified and as directed.
Labour only for preparing sweet soil and cow dung mix at the ratio of 80:20 (80% & sweet soil and 20% & cow dung) and same to spread at depth of 60 cm wherever directed and watered distance not exceeding 250 mtr complete all as specified and as directed.
Labour only for preparing for planting grass and placing sweet soil and cow dung mixture and spread with the help of harrow or other suitable devices upto of 60cm and obtained mixing materails from above item distance not exceeding 250 mtr complete all as specified and directed.
Supply and planting of Kolkata / America grass complete all as specified and directed.
Supply and laying of fly ash brick, brick on edging laid in a pattern to separate the horticulture area from working area complete all as specified and directed.
Supply and fixing 25mm dia flexible pipe for watering the plants complete all as specified and directed. Note: Rate of plant/grass are including for preserve tree/plants/grass upto min 3 month from the completion of work.
NARULA INFRASTRUCTURE PRIVATE LIMITED (BID ID -3406848)
PROSPECTS INFRA PVT LTD (BID ID -3406390)
D R STEEL CONSTRUCTION COMPANY PRIVATE LIMITED (BID ID -3398981)
COAL MINES ASSOCIATED TRADERS PRIVATE LIMITED (BID ID -3399224)
Adhunik Infrastructures Pvt Ltd (BID ID -3397353)
Narayan Kumar Infrastructure Pvt Ltd (BID ID -3406805)
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid