Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹27.0 LAccepted-AOC | L1 | Accepted-AOC L1 bidder | |
| 2 | L2₹36.4 L+₹9.5 L (35.1%)Rejected-Finance MOSAT HARIPUR RD VILL P O HARIPUR DIST HOOGHLY PIN 712701 | HARIPUR | HOOGHLY | WEST BENGAL | 712701 | L2 | Rejected-Finance Rejected_Fin | |
| 3 | L3₹36.7 L+₹9.7 L (36.0%)Rejected-Finance | L3 | Rejected-Finance Rejected_Fin | |
| 4 | L4₹37.6 L+₹10.7 L (39.5%)Rejected-Finance 2 SURI LANE KOLKATA 700 014 | KOLKATA | KOLKATA | WEST BENGAL | 700014 | L4 | Rejected-Finance Rejected_Fin |
Tender Value
₹32.0 L
EMD Value
₹64,100
Closing Date
6 Apr 2024, 12:00 pmClosed
O/O Exe. Engr, Kolkta South Health El. Divn, PWDte
75 D H Road Khidderpore Kolkata 23
IPGMER SSKM H Modification and Upgradation of 5th floor Western Side the provision of Head Neck OT Recovery Male and Female ward at Chest and Cancer Building Internal Electrical Installation Work
2024_WBPWD_684352_1
WBPWD/EE-I/KSHED/Q97/23-24
Open Tender
ELECTRICAL WORKS ORG
Item Rate
SSKM Hospital Kolkata
Please refer Tender documents.
3 documents required · 3 mandatory
₹64,100
O/O Exe. Engr, Kolkta South Health El. Divn, PWDte
4 Apr 2025
13 Mar 2024
8 Apr 2024
19 Mar 2024
6 Apr 2024
21 Mar 2024
21 Mar 2024
Amount
Part A - Internal Electrical Installation
Dismantling the existing damaged VTPN DB,PDB, BDB, switch board, wiring, cable, fittings & fixture as required very carefully & carrying the same to safe place as per direction of EIC.
Supply & Fixing Double Door Type 8 Way Vertical TPN PDB in S.S. enclosure with IP-42/43 protection (Cat no 6079 14) on wall consisting with 1 no 160 A., 4-Pole MCCB (36KA, 420096) as incomer,,8 nos. 63A. TP MCB as outgoing. and both side cable end box in wall embedded complete with all connection with suitable size of Cu. wire with proper socketing as per direction of E.I.C.
Supply & Fixing Double Door 6-Way TPN MCB DB in S.S. enclosure (min 1.5mm thick) with IP-42/43 protection flushed in wall consisting with 1 No. 63 A. 4-Pole MCB as incomer & 18 nos., 16 - 32 A. SP MCB as outgoing, complete with DIN Channel, Neutral Bar, Earth Bar , both side cable end box in wall embedded and other accessories & connection with suitable size of Cu. wire with proper socketing incl. necsy. earthing attachment. .
Supply & Fixing Double Door 2+12 Way SPN MCB BDB comprising with 1 No. 250V. 32 A. DPMCB and 12 nos. 250 V. 6 - 16 A. SP MCB as outgoing, complete with DIN Channel, Neutral Bar, Earth Bar and other accessories in wall embedded, incl. necsy. earthing attachment as per direction of EIC.
Distribution wiring in 1.1 KV grade 2x22/0.3 (1.5 sqmm) single core stranded 'FRLSH' PVC insulated & unsheathed copper wire (Brand approved by EIC ) partly in 20mm size PVC rigid conduit 'FR' (Brand approved by EIC) [for ceiling portion only] and in 19mm bore, 3mm thick polythene pipe [for horizontal & vertical run embedded in wall], with 1x22/0.3 (1.5 sqmm) single core stranded 'FRLSH' PVC insulated & unsheathed copper wire (Brand approved by EIC ) for ECC, to light/fan/call bell points with Modular type switch (Make - Brand approved by EIC)fixed on 2 row 12 Module GI Modular type switch board in wall complete with 2 no. “Ph & N” copper bar incl. 2 row 12 Module GI Modular type cover 3 mm thick and incl. 75x100x65mm inspection box, making earthing attachment, painting the MS box and mending good the damages to original finish(As per direction of EIC) [only PVC Rigid Conduit on ceiling and remaining portion concealed] - Av. Run 9 Mtrs.
On Board
Supply & Fixing 240 V, 3 nos. 6 A, 3 pin Modular type plug socket & 1 No 6/ 16A universal 6 pin Modular type plug socket with 3 nos.6A Modular type switch & 1 nos.16A Modular type switch (Brand approved by EIC), without plug top on 2 row 12 Module GI Modular type switch board with 2 row 12 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy.connections with PVC Cu wire and earth continuity wire etc.( As per direction of EIC).
Supply & Fixing 240 V, 2 No 16 A, 3 pin Modular type plug socket,& 2 nos. 16 A, 6 pin universal Modular type plug socket with 2 nos. 16A Modular type switch (Brand approved by EIC) with 2No 6A Modular type switch, without plug top on 2 row 12 Module GI Modular type switch board with 2 row 12 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc.(As per direction of EIC)
Supply & Fixing 240 V, 2 nos. 6 A, 3 pin universal Modular type plug socket with 2 nos. 6A Modular type switch (Brand approved by EIC), on 6 Module GI Modular type switch board with 6 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc(As per direction of EIC).
Supply & Fixing 240 V, 1 nos. 16 A, 6 pin universal Modular type plug socket with 1 nos. 16A Modular type switch (Brand approved by EIC), without plug top on 4 Module GI Modular type switch board with 4 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc.(As per direction of EIC)
Supplying & Fixing Industrial Plug & Socket board with 415 V, 32A, TPN & Earth Metal Industrial Plug socket & 30A Industrial top incl. S&F 32 A TPN/FP MCB breaking capacity 10kA (C- Curve) in SS enclosure fixed on wall and necessary connection.
Supply & Fixing 240V., T.L. Fittings complete with all accessories and necy. connection by 2 x1.5mm² PVC insulated Cu. Wire & painting as follows:-
Single industrial box type luminaire with CRCA body . incl S&F 1x 18/20 watts 4 ft LED tube lamp
Twin industrial box type luminaire with CRCA body incl. S&F 2x 20 watts 4 ft LED tube lamp
Supply & fixing of Energy efficient recessed mounted LED luminaire suitable for240v 2'x2' grid ceiling including all fixing materials ina way that the fitting suspended from by suitable size of GI wire by means of two Nos. MS L-Clamp fastened at ceiling with necy. interconnection by 3x1.5 mm² PVC insulated S/C Cu. Wire.
Supply & fixing of 2'x2' LED Light Fittings Frame with the fitting suspended from by suitable size of GI wire by means of two Nos. MS L-Clamp fastened at ceiling with necy. All accessories.(As per direction of EIC)
Supply & Fixing of 240 V, 1feet ×1 feet square slim panel LED light fittings to be fixed on false ceiling incl. cutting of false ceiling very carefully with necy. interconnection by 3x1.5 mm² PVC insulated S/C Cu. Wire.
Supply of 240 V, 18W square dura slim panel LED light fittings to be fixed on false ceiling incl. cutting of false ceiling very carefully with necy. interconnection by 3x1.5 mm² PVC insulated S/C Cu. Wire.
Supply & Fixing only of 240 V. 1200 mm. Sweep, A.C. Ceiling Fan incl. Down Rod, Canopy, Fan Blades etc. and interconnection complete in all respect.
Supply & Fixing of 240 V., 230 mm. (9") Dia, 1370 rpm A.C. Exhaust Fan incl.cutting hole on wall , S&F Cowl with Nuts, Bolts, washer and mending good the damages to original finish.
Supply & Fixing of 240 V., 300 mm. (12") Dia, 1420 rpm A.C. Exhaust Fan incl.cutting hole on wall , S&F Cowl with Nuts, Bolts, washer and mending good the damages to original finish.
Supply & Fixing 240V, Modular Socket (2 Module) type fan regulator (Step type) (Brand approved by EIC) on existing Modular GI switch board with top cover plate incl. making necy. connections etc.
S/F MS two piece type RC fan clamp ( Reputed make/ Quality)fabricated from 40X9mm MS flat as per GS.
S & F Heavy Duty Fan Down Rod ( Minimum 14 SWG) for new fan incl. 3 x 1.5 Sqmm Copper wire
Supply & Fixing of perforated GI cable tray with perforation not more than 17.5% suspended from ceiling incl. S&F GI connector, 6mm dia MS suspender, bolts & nuts, steel fastener etc. as required of the following size. Incl. Al painting of MS support.
(a) [200x50x1.25mm (18SWG)With 25x25x3mm angle iron support]
(b) 300x50x1.25mm (18SWG)With 25x25x3mm angle iron
Supply & Fixing 1.5 ft length Angle Support [Dimension: 40 x 40 x 6 mm] on wall for passing the cable with fastener and proper saddle arrangement with two coat RO primer and enamel painting as per GS
S & Laying 1.1KV gr. XLPE Ar./Al. Cable (As approved by EIC) with 2 Nos 25×6 mm flat bar in wall with S/F MS saddle incl. making connections as per direction of EIC.
(a) 4 Core 70 sq.mm (For Panel to VTPN)
(b) 4 Core 35 sq.mm (for VTPN to TPN DB )
Supplying and fixing compression type gland complete with brass gland, brass ring (Reputed make) & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables as below
(a) 4 Core 70 sq.mm
(b) 4 Core 35 sq.mm
Finishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowells make), tapes, anticorrosive paste & jointing materials
(a) 4 Core 70 sq.mm
(b) 4 Core 35 sq.mm
Wiring in 1.1 KV grade single core stranded 'FRLSH' PVC insulated & unsheathed copper wire (Brand approved by EIC) of following sizes in 19/25mm PVC Rigid Pipe only PVC Rigid Conduit on ceiling and remaining portion concealed (Brand approved by EIC) incl. necy. PVC clips, fittings etc.
(a) 3 x 1.5 mm² for Separate Plug point.
(b) 2 x 2.5 & 1x 1.5 mm² for Sep Power Plug & Computer board.
(c ) 2 x 4 & 1 x 2.5 mm² for Combined Power Plug
(d) 2 x 6 & 1 x 4 mm² from (TPN DB to SPN DB & Industrial socket).
(e)2 x 10 mm² for Spl. earthing.
4 x 16 & 2 x 10 mm² for UPS & Autoclave.
Finishing of the PVC insulated wire ends by socketing with pin/ring type copper sockets and insulated tapes etc., including supplying sockets, tapes.
(a) 3 x 1.5 mm² for Separate Plug point.
(b) 2 x 2.5 & 1x 1.5 mm² for Sep Power Plug & Computer board.
(c)2 x 4 & 1 x 2.5 mm² for Combined Power Plug
(d) 2 x 6 & 1 x 4 mm² from (TPN DB to SPN DB & AC M/C IDU & Industrial socket).
(e)2 x 10 mm² for Spl. earthing.
(f) 4 x 16 & 2 x 10 mm² for UPS Connection.
Supply & Fixing 5KW,440Volt,3Ph, Direct on Line starter on flat iron frame / angle iron frame on wall for autoclave
Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat 25 mm x 6 mm on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required
Supplying & fixing earth busbar of copper flat 25 mm x 6 mm on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required for special earthing.
Connecting the equipment's body to earth busbar including S & F 25 mm x 6 mm galvanised (Hot Dip) MS flat on wall/floor with GI saddles as required and connection to equipment's incl. drilling holes, with bolts, nuts, washers etc.
(Lighting Protection System)
S & F Lightning Conductor Air Terminal made of 20 mm dia 1000 mm long GI pipe (ISI Medium) having five discharge prongs of 4 SWG GI (Hot Dip) wire at top duly soldered/ welded with 7/16 stranded GI (Hot Dip) wire and 85 mm dia 6 mm thick GI base plate at bottom incl. necessary holes etc. complete duly grouted on the parapet etc. in CC mortar ( 4:2:1), including thimble joints of 7/16 SWG wire and (25 x 6) mm GI strip with SS nuts, bolts & washers.
Supply & fixing of 25 mm x 6 mm thick GI (Hot Dip) flat / strips for Horizontal & Vertical run on wall / floor with GI saddles as required including drilling holes, bolts, nuts, washers, etc./ and mending good the damages to building works .
Cutting cornices/ steps etc. including cutting recess in buildings etc. & supply & fixing 15 mm bore (ISI-Medium) GI pipe protection as below and mending good damages to the building works: i) Length upto 0.5 Mtr
Hiring charges for scaffolding arrangement including dismantling at the end of work and carriage, for LC installation, per storey of building per vertical run.
Supply & Fixing of Testing Joints by 25 mm x 6 mm thick GI (Hot Dip) strip 125 mm long on wall after making suitable arrangement to establish a clearance of 50mm from wall for making junction connection with vertical conductor and conductor from earth electrode complete with S & F GI bolts, nuts, check-nuts, spring washers etc. as required.
Earthing with 65 mm dia GI pipe 3.0 Mts. long with welded 2 nos. half circle bracket made of GI strip (65 x 8) mm. with two holes on extended portion of the each strip of length min. 250 mm , and 1 No. 50 mm x 6 mm galvanized (Hot Dip) steel strip (4 Mts. long), 20 mm dia x 125 mm long galvanized bolt, double nuts, double washers including finishing both ends by making holes etc. and S & F 65 mm dia GI pipe (ISI-Medium) protection (3 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level to an average depth of 3.65 Mts.
Extra for providing masonry enclosure on the top of the earth electrode of overall size 86.36 cm x 86.36 cm x 46 cm deep (below Ground level) complete with cemented brick work(1:6) of 25 cm width duly plastered with cement morter (inside) CI hinged inspection cover of size 36.56 cm x 35.56 cm with locking arrangement, GI reducer including drilling of 46 nos. 12 mm dia holes on the GI pipe
Excavation of soil for installation of Earth Electrode and filling & ramming as to GS. (For morum soil) .
Supply, Laying & Fixing of 50mm x 6mm galvanized (Hot Dip) steel strip in underground trench for interconnection between the Earth Points by joining (As per item no 11).
Jointing for Horizontal & vertical run of GI strip through welded joint of (25 x 6) mm or (50 x 6) mm GI Strip to Lap joints/ 'T' joints, etc. and painting the joints with 2 (two) coats of bituminous paint. (NS)
UPS System
Testing,Commisioning,Repairing/Replacement of any Damage parts by OEM(If Required) & Reinstalling existing 40KVA UPS in parallel operation (NUMARIC Make KEORT model) 3phase in 3phase out,440Volt,50HZ.incl Caring Cost.
Total cost for supply & installation of 12V, 65AH Battery with FR for UPS (Make : Exide/Quanta ) incl. Buy -back for unserviceable batteries as per direction of EIC.
Geyser
SITC of 240V,50HZ,25 Litres Geyser(Brand Approved BY EIC) with Hot & Cold water line,Thermostat,Tempurature regulator with knob,tempurature show display incl all accessories as per direction by EIC. Minimum 2 Years Warranty.
AHU & Fire Panel interlocking
S&F of control panel for interlock between Fire Alarm system and AHU of AC system in SS encloser (1.6 mm thick) with power coated with S&F following electrical accessories & front door locking arrangement with all connections by finishing the ends of suitable copper wire with dowells solderless socket by crimping method as to GS, earthing attachment on wall icl necessary connections as per direction of EIC:- [NS] a) 230V, 6A, 10KA, MCB C-curve -- 1no b) 2A, 230V/ 24V DC SMPS(Make-approved by EIC) -- 1no c) Auxiliary Contactor/Relay with 2NO+2NC contract block, 24V DC / 230V AC )-- 1no d) LED indication lamp for ON & OFF -- 2 nos h) Control terminal cor Fire Alarm -- 1 No. b) Power terminal for Incoming & Outgoing (Make : ELMAX ) - 3 nos
Glow Sign Board
Supply & fixing of angle iron frame fabricated from 40mm x 25mm x 5 mm thick hollow rectangular bar with sufficient cross and radial support including MS angle iron frame (by 40 mm x 25 mm x 5 mm ) for holding the sign board and support from wall by 50 mm x 50 mmx 6 mm MS angle of 6 fts apart with necessary hooks. Back side shall be covered by S&F of 22 SWG GI sheet. The above structure should be painted with synthetic enamel paint over one coat of primer. The above sign board to be fixed on wall or Parapet as per direction of EIC. (Size : 12 ft x 2 ft x 6inch )
Supply & Installation of 4 mm thick polyvenile coated Aluminium Composite Panel board ( Aludecor / Alstone / Pratap Bond) of blue colour as the base for fixing raised letter duly fixed on the MS structure as per direction of EIC. The riser structure should be covered with ACP sheet incl. side portion on the board. (Size : 12 ft x 2 ft x 6inch )
Supply & fixing of Superior Quality acrylic dimensional letters (Size - 4" for "INSTITUTE OF OTORHINOLARYNGOLOGY AND HEAD-NECK SURGERY, CENTRE OF EXCELLENCE" & Size-6" for '' OPERATION THEATRE'') as per direction of EIC, on the pre- fabricated existing ACP board. The computerised processed letter in bold English fonts and milky white in colour shall be placed in horizontal line maintain suitable space with Male & Female attachments for each letter and necessary interconnections as per direction of the EIC.
The matter as follows and should be approved at the time of construction from the appropriate authority.
INSTITUTE OF OTORHINOLARYNGOLOGY AND HEAD-NECK SURGERY CENTRE OF EXCELLENCE OPERATION THEATRE
S&F of imported 12 V DC IP-65 LED modules having three LED in a single base module and the LEDs will emit mild attractive blue colour light and the two run of LED for each letter base area and shall be properly fixed in the male part of the Acrylic letters including necessary interconnections. Specification of the LEDs is given as below : a) LED-white, GE/Samsung b) Type-Straight, 3 Nos. Led per module c) Life – 70,000 burning hours. d) Visibility – 100 mtrs at least, for normal eye e) Power consumption – 1.5 watt per module
S&F of imported heavy duty 12V DC, 400 VA SMPS (Make-approved by EIC) with properly rated isolation transformer in suitable enclosure to be fixed with the signage frame for driving total LED system of the signage in a distributed manner for uniform load sharing in view of long run continuous use including necessary interconnections.
Scaffolding arrangement for working at 10 ft. height on entrance of the building by bamboo, ropes and wooden planks etc. and shifting of scaffolding materials after completion of work.
ELECTRICAL PANEL: for AC
S/Installation of floor cum-wall mounted cubicle type outdoor compartmentalized 415V., 50 Hz. dust, moisture & vermin proof LT Distribution panel board with following electrical accessories fabricated from 14 SWG CRCA sheet with MS angle frame as required. The base of panel should be made with 75 x 40 x 4.4 mm MS channel. The panel should have adequate strength & space to accommodate the incoming & outgoing switches and bus-bars with all interconnection in between the switches and bus-bars with copper flat / copper flexible wire of suitable capacity . The panel should be provided with cable alley for facilitating connection of all the incoming & outgoing XLPE Cables with termination arrangement by S&F copper terminal stud / bolt of required sizes. The panel with earthing attachment. The panel is to be painted with powder coated paint as per direction of EIC. The panel board should consist with the followings:-
INCOMING
(A) 415V., 250 Amp. 36 KA 4-Pole MCCB with Microprocessor release (Range: 100- 250A), extended rotary handle and both side spreader terminals with mechanical interlock 2 Nos .
(B) BUSBAR CHAMBER:-
S&F 315 Amp capacity 99.9% - 99.5% electrolytic tinned copper 4 bar bus bar [size of flat 4 x 40 mm x 8 mm] mounted on non-hygroscopic porcelain insulator / hylam sheet having sufficient di-electric strength duly wrapped with colour PVC tapes (Red, yellow, blue & black) for phases & neutral identification & all connection made with required size cu bars - 1set.
(C) BUS COUPLER:-
415V., 250 Amp. 36 KA 4-Pole MCCB with Microprocessor release (Range: 100- 250A), extended rotary handle and both side spreader terminals with mechanical interlock ] - 1 No .
(D) OUTGOING:-
a) 415V., 160 Amp. 36 KA 4-Pole MCCB with Microprocessor release (Range: 63 - 160A), extended rotary handle and both side spreader terminals - 2 Nos. ( 1W + 1S)
b) 415V., 32A., 4P MCB in SS enclosure [Make:- L&T].- 8 Nos. (3 nos for Outdoor type AHU, 2 Nos(1W+1S) for chill water pump)
c) 415V., suitable rating Star-Delta starter for operation of 5.5 KW Pump Motor with over load relay, single phasing protection & Timer, ON & OFF switch & indicating lamp for ‘ON’ & OFF status (Make:- L&T) - 2 nos. ( 1W + 1S).
(E) METERING:-
(a) 500V., C.T. Coil (C.T. Ratio - 250/5A.) - 6 Nos.
(b) 500V., C.T. Coil (C.T. Ratio - 150/5A.) - 6 Nos.
(c) 500V., C.T. Coil (C.T. Ratio - 60/5A.) - 24 Nos.
(d) LED Indicator lamp - 28 Nos.(10 Nos for ON/OFF/TRIP & 18 Nos for RYB Phase indication)
(e) Digital Multifunction Meter Class accuracy CI0.5S, RS485 port - 02 nos.(For Main Incomer).
f) Panel mounted digital Voltmeter in 96x96 mm² [0 - 500 V] - 2 no.
(i) Control MCB (single/three phase) with proper rating - 1 Item.
(j) Danger Board - 01 no.
Supply & Laying of 1.1 KV Gr. PVC/XLPE insulated, PVC- Sheathed cable, Aluminium armoured for Power cables incl 2 Nos 25×6 mm flat bar. to laid on wall surface by suitable clamping / existing cable tray, proper glanding & finishing the cable ends with solderless sockets for following cables & Copper armoured for Control cable
a) 4 Core 240 sqmm XLPE Ar/AI Cable for panel incomer.
Supply & fixing of Glanding & finishing the cable ends with solderless sockets for following cables & Copper armoured for Control cable . F-5/8 & F-4/7
a) 4 Core 240 sqmm XLPE Ar/AI Cable
Supplying and fixing 415V, 320AMP TPN SFU with sheet steel enclosure on flat iron/angle iron frame on wall with nuts bolts etc incl. S & F 3 nos. DIN type HRC fuse as per rating. D-3/4
S & F 250V 25A Timer controller for AC machine in SS double door (IP 42/43) 2+10-way DB enclosure (Make:- L&T/Schnider/ABB Elegance) with S&F following electrical accessories & front door locking arrangement with all connection by finishing the ends of 2x4 & 1x2.5 copper wire dowells solderless socket by crimping method as to GS earthing attachment on wall incl necessary connections as per direction of EIC :- i) 10kA, C-Curve, 240V, 25A DPMCB --- 1 No ii) 24 Hr programmable Digital Timer ---- 1 No iii) 3 pole power contractor 22/230V with 1 NO +1 NC additional contact block ---- 2 sets iv) 2 Modular AC motor stater ---- 1 No. v) 2 Module plate with cover -- 1 No vi) 20A Auto-Off-Bypass SPDT toggle switch (Approved/reputed make) ---- 2 Nos. vii) 10A SPST Modular type switch - 1 No. viii)Outgoing connector make ELMAX (Approved/reputed make) - 2 Nos (Twin timer)
S & F 250V 25A Timer controller for AC machine in SS double door (IP 42/43) 2+10-way DB enclosure(Brand approved by EIC) with S&F following electrical accessories & front door locking arrangement with all connection by finishing the ends of 2x4 & 1x2.5 copper wire dowells solderless socket by crimping method as to GS earthing attachment on wall incl necessary connections as per direction of EIC :- i) 10kA, C-Curve, 240V, 25A DPMCB --- 1 No ii) 24 Hr programmable Digital Timer ---- 1 No iii) 3 pole power contractor with 1 NO +1 NC additional contact block ---- 1 sets iv) 2 Modular AC motor stater ---- 1 No. v) 2 Module plate with cover -- 1 No vi) 20A Auto-Off-Bypass SPDT toggle switch (Approved/reputed make) ---- 2 Nos. vii) 10A SPST Modular type switch - 1 No. viii)Outgoing connector make ELMAX (Approved/reputed make) - 1 Nos
Defect Liabibility Period 1 (One) year
Make & model of each and every material to be approved by EIC
GHANASHYAM ELECTRIC STORES
T. K. ENTERPRISE
MAHESWAR ELECTRICAL INDUSTRIES
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .