Ex Engineer (ENV) PCMC
Ex. Engineer (ENV) PCMC Main Building
Regarding inviting quotations for the preparation of a rate schedule for various types of screens required to improve the treatment process at STP and ETP within the Pimpri Chinchwad Municipal Corporation.
2025_PCMCP_1191315_1
Quotation Notice-ENV/08/2025-26
Open Tender
Civil Works - Others
Item Wise
180 days
PCMC Area
Please refer Tender documents.
2 documents required · 2 mandatory
₹0
Exempted
1 Jul 2025
18 Jun 2025
27 Jun 2025
18 Jun 2025
25 Jun 2025
18 Jun 2025
Amount
.J-Type Trash Screen - Detailed Quotation Notice Attached
1) Channel width:1600 mm, SWD: 1100 mm, Channel depth: 1600 mm, bar spacing: 40 mm, bar size 50X10 mm. Level Deference between Channel Bottom and Operating platform Greater than 10 - 12m
2) Channel width: 1600 mm, SWD: 1100 mm, Channel depth: 1600 mm, bar spacing: 40 mm, bar size 50X10 mm. Level Deference between Channel Bottom and operating platform Greater than 8-10 m.
3) Channel width: 1600 mm, SWD: 1100 mm, Channel depth: 1600 mm, bar spacing: 40 mm, bar size 50X10 mm. Level Deference between Channel Bottom and operating platform Greater than 6-8 m.
4) Channel width:1600 mm, SWD: 1100 mm, Channel depth: 1600 mm, bar spacing: 40 mm, bar size 50X10 mm. Level Deference between Channel Bottom and operating platform Greater than 4-6 m.
5) Channel width:1600 mm, SWD: 1100 mm, Channel depth: 1600 mm, bar spacing: 40 mm, bar size 50X10 mm. Level Deference between Channel Bottom and operating platform Greater than 3-4 m.
6) Channel width: 1300 mm, SWD: 1000 mm, Channel depth: 1500 mm, bar spacing: 40 mm, bar size 50X10 mm. Level Deference between Channel Bottom and operating platform Greater than 10-12 m.
7) Channel width: 1300 mm, SWD: 1000 mm, Channel depth: 1500 mm, bar spacing: 40 mm, bar size 50X10 mm. Level Deference between Channel Bottom and operating platform Greater than 8-10 m.
8) Channel width: 1300 mm, SWD: 1000 mm, Channel depth: 1500 mm, bar spacing: 40 mm, bar size 50X10 mm. Level Deference between Channel Bottom and operating platform Greater than 6-8 m.
9) Channel width: 1300 mm, SWD: 1000 mm, Channel depth: 1500 mm, bar spacing: 40 mm, bar size 50X10 mm. Level Deference between Channel Bottom and operating platform Greater than 4-6 m.
10) Channel width: 1300 mm, SWD: 1000 mm, Channel depth: 1500 mm, bar spacing: 40 mm, bar size 50X10 mm. Level Deference between Channel Bottom and operating platform Greater than 3-4 m.
Designing, Providing, Supplying, installing and commissioning of the manual bar screen with vertically spaced flat bars is used to prevent large &medium floating debris from entering the screening chamber. Typically installed parallel of a mechanical bar screen, it also serves as a standby for the mechanical screen. Cleaning is performed manually using a rake comb provided with the screen. The manual screen can be designed as a fixed Screen to be raised to the platform level for manual cleaning. The screen's height is designed to match the specified water depth. Entire screen assembly shall be made of SS 304 & shall be fixed at angle 45° to 60° with horizontal etc. Complete as directed by Engineer incharge.
1) Channel width:1600 mm, SWD: 1100 mm, Channel depth: 1600 mm, bar spacing: 20 mm, bar size 50X10 mm.
2) Channel width: 850 mm, SWD: 1250 mm, Channel depth: 1750 mm, bar spacing: 20 mm, bar size 50X10 mm.
3) Channel width:1300 mm, SWD: 1000 mm, Channel depth: 1500 mm, bar spacing: 20 mm, bar size 50X10 mm.
Designing, Providing, Supplying, installing and commissioning of Mechanical Multi –rake Coarse Screen vertically spaced is used to prevent large & medium floating debris from entering the screening chamber & angle of inclination 70 to 75 degree- Quotation Notoce Attached
1) Channel width:1600 mm, SWD: 1100 mm, Channel depth: 1600 mm, bar spacing: 20 mm, bar size 12x6x50 mm taper bar. Level Deference between Channel Bottom and Operating platform Greater than 10 - 12m.
2) Channel width: 1600 mm, SWD: 1100 mm, Channel depth: 1600 mm, bar spacing: 20 mm, bar size 12x6x50 mm taper bar. Level Deference between Channel Bottom and Operating platform Greater than 8 – 10 m.
3) Channel width: 1600 mm, SWD: 1100 mm, Channel depth: 1600 mm, bar spacing: 20 mm, bar size 12x6x50 mm taper bar. Level Deference between Channel Bottom and Operating platform Greater than 6 – 8 m.
4) Channel width:1600 mm, SWD: 1100 mm, Channel depth: 1600 mm, bar spacing: 20 mm, bar size 12x6x50 mm taper bar. Level Deference between Channel Bottom and Operating platform Greater than 4 – 6 m.
5) Channel width:1600 mm, SWD: 1100 mm, Channel depth: 1600 mm, bar spacing: 20 mm, bar size 12x6x50 mm taper bar. Level Deference between Channel Bottom and Operating platform Greater than 3 – 4 m.
6) Channel width: 750 mm, SWD: 700 mm, Channel depth: 1500 mm, bar spacing: 20 mm, bar size 12x6x50 mm taper bar. Level Deference between Channel Bottom and Operating platform Greater than 10 - 12m.
7) Channel width: 750 mm, SWD: 700 mm, Channel depth: 1500 mm, bar spacing: 20 mm, bar size 12x6x50 mm taper bar. Level Deference between Channel Bottom and Operating platform Greater than 8 - 10m.
8) Channel width: 750 mm, SWD: 700 mm, Channel depth: 1500 mm, bar spacing: 20 mm, bar size 12x6x50 mm taper bar. Level Deference between Channel Bottom and Operating platform Greater than 6 - 8m.
9) Channel width: 750 mm, SWD: 700 mm, Channel depth: 1500 mm, bar spacing: 20 mm, bar size 12x6x50 mm taper bar. Level Deference between Channel Bottom and Operating platform Greater than 4 - 6m.
10) Channel width: 750 mm, SWD: 700 mm, Channel depth: 1500 mm, bar spacing: 20 mm, bar size 12x6x50 mm taper bar. Level Deference between Channel Bottom and Operating platform Greater than 3 - 4m.
Designing, Providing, Supplying, installing and commissioning of The manual bar screen with vertically spaced flat bars to be used to prevent medium floating debris from entering the screening chamber at PCMC Site. Shall need to installed inlet chamber of the STP. Able to clean the screen by rake comb manually. The manual screen shall be a fixed Screen to be raised to the platform level for manual cleaning. The screen's height is designed to match the specified water depth. Entire screen assembly shall be made of SS 304 and shall be fixed at angle 45° to 60° with horizontal, etc. Complete as directed by Engineer incharge- Quotation Notoce Attached
1) Channel width: 1150 mm, SWD: 1250 mm, Channel depth: 1700 mm, bar spacing: 6 mm, bar size 50X10 mm.
2) Channel width: 840 mm, SWD: 1100 mm, Channel depth: 1700 mm, bar spacing: 6 mm, bar size 50X10 mm.
HNB ENGINEERS PVT LTD.PUNE (BID ID -6734385)
Excel Engineers (BID ID -6732748)
SHREE VINAY ENGINEERING SERVICES PRIVATE LIMITED (BID ID -6734777)
Micro Trsnsmission Systems (BID ID -6732487)
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .