EXECUTIVE ENGINEER
Electrical Division HPPWD Palampur
Construction of Indoor Auditorium Chamba in Tehsil and Distt. Chamba (Sh Providing 40 KVA UPS system therein).
2026_PWD_136667_2
Electrical Division HPPWD Palampur
Open Tender
Electrical Works
Percentage
Chamba
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
₹27,992
18 Jun 2026
15 Jun 2026
21 Jun 2026
15 Jun 2026
21 Jun 2026
15 Jun 2026
Capacity (in kVA / kW) 40 kVA/ 40 kW 3-Phase Input / 3-Phase Output Technology and Capability:a) True Online configuration with double conversion UPS b) DSP based technology with reduction in electronic components. c) Fully rated power (kVA=kW) for maximum power availability. d) Possibility of enhancing UPS capacity / redundancy by operating UPS in N+X Parallel Redundant Configuration(PRS). e) Capability of Independent or Common battery bank operation of the UPS when operated in PRS. f) UPS should be designed at Rated PF of 1 i.e. 40kVA / 40kW UPS rating. g) UPS shold have IGBT topology for both PFC (power factor correction), Rectifier and inverter. h) Should have Dual Aux power design.
Model Name & Number:
40 kVA / 40 Kw::Make / Model / Part No to be specified by the vendor
Input
Input facility -Phases / Wires
Input Voltage Range:220/380V,230/400V,240/415V (3Φ4W) Range (Full Load) 173~276 / 300~477VAC Range (Derating to 70% Load) 132~173 / 228~300VAC
Input Frequency Range:45 to 65 Hz
Input Power Factor:> 0.99 (Full Load)
Current Harmonic Distortion(ITHD):< 3%
Generator Compatibility:Compatibility to genset supply required
Input Protection (Thru In-built 1P MCB):Should be provided at the input of the UPS suitable for the full rated capacity of the UPS
Output
Nominal Output voltage:220/380V,230/400V,240/415V (3Φ4W)
Output Voltage Regulation:± 1 %
Nominal Output Frequency:50/60 Hz
Output Frequency Regulation:± 0.05Hz
Output Frequency Slew Rate:<1Hz/sec
Output Wave Form:Pure sine wave
Output Voltage Distortion (THDu):< 1.5 % (linear load)
Crest Factor:'3:1
Output Short circuit Protection:Electronic Protection
Transient Response / Recovery
Transient Response: Dynamic Regulation for 10% to 90% step linear load:'±7%
Transient Recovery to steady state condition after 10% to 90% step linear load:< 1 cycle
Transfer Time
Transfer Time (Mode of operation):Zero ms from Mains mode to Battery Mode Zero ms from Battery Mode to Mains mode
Transfer Time (Inverter to Bypass / Bypass to Inverter):<1ms (Synchronized Mode)
Automatic & Bi-directional static by-pass (In-built):Bypass To Inverter ±10 % (Rated Voltage) Inverter To Bypass ±7 % (Rated Voltage)
Maintenance Bypass:1.UPS should have option for manual maintenance bypass 2. Maintance bypass cover removal sensing. 3.The maintenance bypass should provide for Hot-swap of the faulty UPS PWB for repairs / service.
Efficiency (At Nominal Voltage & Resistive Load up to kW rating of UPS):
Overall Efficiency (AC to AC) - Online (Double Conversion).
Overall Efficiency (AC to AC) - ECO Mode (Bypass feeding the load under normal conditions):96%
Overload
Inverter Overload capacity :≤105 %: continuous,106% ~ ≤125%: 10 minutes; 126% ~ ≤150%: 1 minute; >150%: 1 second
Display Panel (In-build LC Display & LED )
Measurements (On LCD):Input: Voltage / Frequency,Bypass: Voltage / Frequency,Output: Voltage / frequency,Battery: Remaining time / Battery Level Indicator,Load: Percentage / Load Level Indicator,Battery Voltage Capacity/Status/Test Result,System Date/Time Setting,Current Time,PFC Fuse Open,Battery Temperature Too High,Battery Over Charge,Battery Out of Date,INV Short Circuit,Output Breaker Off,kVA,kW,output current,Battery current.
Fault Indication (On LCD):Main Input Sequence Fault,Power Module General Fault,Battery Ground Fault,Bypass Static Switch Fault,Parallel Fault,System General Fault,Provide Bypass O/P Even If UPS Fault.
Indications (LED):Normal-Green/Battery-Orange/Bypass-Green/Fault-Red
Alarms
Audible Alarms:Battery Low beep / DC Fault beep/ UPS Overload beep/ o/p short ckt fault beep/ Shutdown beep
Battery Backup / Battery Bank & Charger
Backup Required:30 minutes 31200VAH
Battery Bank Voltage:Flexible 384 VDC to 600VDC
Battery Bank VAh :Minimum 31200 VAH
Batteries Type:Sealed Maintenance Free (SMF) - 12V Cells
Battery Makes:Amara Raja / Exide / Rocket.
Number of Battery Banks:Maximum Two Banks in parallel
Minimum Charger Rating (Including internal / external):The charger should be able to deliver charging current equivilanet to 10% of Battery Ah rating offered.(In case of external chergers, suitable monitoring of the chargers should be provided in the UPS. Also all external chargers taking AC input must have PFC - Power factor correction)
Charger type / Charging Method & Charging Voltages:Constant Voltage Constant Current Solid state SMPS charger Float Charge 270V±(2V) Boost Charge 280V±(2%V)
Battery recharge time (After complete discharge) to 90% capacity:10-12 hours
Battery Housing (Vendor to provide the GA drawings of the offered Battery Rack):Should be compact and space saving MS steel open racks complete with interconnectors :
Battery End Cell Voltage:1.75 V/cell:
Interfaces
Serial Communication RS232 Port (Option of USB Port should be available):RS2323 Port should be provided as standard in the UPS. However there should be provision for USB port also in the UPS.
REPO(Remote Emergency Power OFF) / ROO(Remote ON - OFF) Port:Provide both onsite & remote EPO to shutdown UPS when emergency situation happens. REPO Port with a user-supplied switch
Interface to NMS (Network Management System) - To be quoted as option:SNMP (IPV6) Card for connecting the UPS to LAN thru Ethernet port & monitoring thru NMS should be available (The cost of SNMP Card / NMS software to be quoted separately)
Interface to BMS (Building Management System) - To be quoted as option
Interface to DCS (Distributed Control System) - To be quoted as option :Relay I/O Card or PFC (Potential free contacts) for connecting to UPS to DCS / PLC / SCADA system for communicating UPS operating status
UPS status information presented as 3 contact closures:UPS should have configurable input signal as shutdown UPS or battery test dry contact.
Restart / Testing Capability
Cold Start:UPS should start up On AC Supply (Mains) without DC Supply (Batteries) On DC Supply (Batteries) without AC Supply (Mains)
Automatic Restart:UPS should start up automatically on mains resumption after battery low shutdown
Self Diagnosis:UPS should be capable to carry out self test of Rectifier / Charger /Battery & Inverter module during start-up
Physical
Operating Temperature:0℃ ~ 40℃
Storage Temperature:-20℃ ~ 40℃
Operating Humidity:< 95%
Operating Altitude:0 to 3000m(0 To 10000ft)
Forced Air:
Noise Level:< 55dBA at 1 Meter
Air Filters:UPS should have internal anticorrosion air filters for dust filtration (Optional)
Dimension (w x d x h) in mm:To be furnished by the vendor
Weight - in kg:To be furnished by the vendor
Reliability:MTBF greater than 100000 hours
Packaging Material / Vibration Withstand & Drop Test:Recyclable (No CFC) & 1. Vibration testing as per ISTA -1G Non-operational with Packing
Standard Package of UPS to include the following minimum accessories:1.SMART Slot 2.MINI Slot 3.Parallel Port 4.RS232 Port 5.REPO Port 6.Charger Detection Port 7.Input Dry Contact 8.Output Dry Contact 9.USB Port
Parallel Configuration:UPS should have capabilty for parallel 4 units.
DC bus Capacitor:UPS DC bus capacitor have minimum life of 5 years@40°ambient.
Certifications
Manufacturer Certifications:QMS: As per ISO 9001: 2008 EMS: As per ISO 14001: 2004 OSHAS: As per ISO 18001: 2007 TL 9000
Product Safety Certifications (Mandatory):ESD:IEC61000-4-2: level4 RS : IEC61000-4-3: level3 EFT: IEC61000-4-4:level4 SURGE: IEC61000-4-5:level4 CS: IEC61000-4-6: level3 IEC 61000-2-2 EN 62040-2 EN 61000-3-2
ROHS compliance:UPS should be ROHS compliance
MAKE PREFERENCE - UPS VERTIV/ DELTA / APC-SCHNIEDER
MAKE PREFERENCE - SMF BATTERIES:EXIDE / AMRON -QUANTA / LEOCH
Supply & laying of 3 core Multistrand 2.5 sq mm annealed copper conductor speaker cable in existing pipe / channel I/C connection etc. Approved Makes :Finolex/Polycab/Havells
Supply Installation Testing & Commissioning of PVC pipe32mm dia ISI marked ( Medium ) recessed in wall / ceiling etc. including the cost of PVC bends , inspection boxes , iron hooks and cement concrete etc. complete in all respect upto the entire satisfaction of Engineer-in-charge of work Make: Diplast /Polyplast/polycab
Fabrication, Installation, Testing and Commissioning of floor mounting compartmentallised cubical panel board with locking arrangement front openable, totally enclosed, dust & vermin proof fabricated out of 2mm thick cold rolled carbon annealed, sheet steel, with 200 Amp 4 strip Al. bus bar, cable alley on one side, powder coated paint of approved shade and earthing copper strips complete with following incoming and outgoing switchgears including making connections/ inter connections with lugs/ thimble for switchgears and control wiring with 2.5 sq.mm PVC insulated FRLS copper conductor cable, including Angle baser upto 100 mm above ground level including necessary grouting / fixing on floor ,( MCCB's Ics=100 %=Icu & all MCCB's shall have spreader link & rotory handle).
MAIN Incomer and Outgoing to UPS:
160 Amp. 25 KA breaking capacity TPMCCB with Thermal Magnetic Release - 01 Nos.
LED type phase indicating - (R, Y & B) Lamps with backup protection 6 A SP MCBs- 3 Nos
Digital Multifuctional meter (VAF+PF )-01 No.
Incomimg From UPS :
160 Amp. 25 KA breaking capacity TPMCCB with Thermal Magnetic Release - 01 Nos.
Busbar:
Four Strip aluminium bus bars of minimum of 300 Amps capacity with heat shrinkable coloured sleeves and including DMC/SMC bus bars supports at required intervals complete for cross section,size support& their spacing etc. for with standing fault level of 31 MVA for one second - 01 Set.
Outgoing:
100 Amp. MCB TPN - 03nos.
63Amp MCB DP - 6nos.
stage.html
html • 0.02 MB
cancelled_1.pdf
pdf • 0.18 MB
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.37 MB
DECLARATION.pdf
Additional Documents • 0.01 MB
BOQ_202299.xls
BOQ • 0.38 MB
40UPS.pdf
Tender Documents • 3.63 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .