| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹22.9 LAccepted-AOC | L1 | Accepted-AOC Being L1 Bidder | |
| 2 | L2₹24.0 L+₹61,563 (2.64%)Rejected-AOC | L2 | Rejected-AOC Not Being L1 Bidder | |
| 3 | L3₹26.4 L+₹3.0 L (13.0%)Rejected-AOC PLOT NO 15 JAYASURIYA STREET GANGAI NAGAR KALLIKUPPAM AMBATTUR CHENNAI 600053 | CHENNAI | CHENNAI | TAMIL NADU | 600053 | L3 | Rejected-AOC Not Being L1 Bidder | |
| 4 | Rejected-Technical | - | Rejected-Technical Not enlisted in b(ii) category |
| Sl No | Description | Qty | Unit | EASHWAR ELECTRICALS L1 | Banyan Engineers and Contractors L3 | SRIRAM ELECTRICALS L2 |
|---|---|---|---|---|---|---|
| 1.00 | M&L for Servicing HT VCB panel cum breaker 1250/800/630A 13.1KA rating Indoor type make of SEIMENS/ CROMPTON/ SCHINDER after taking proper shut down and disconnecting the cables from panel draw out VCB breakers, earth fault relay, checking alignment of VCB isolating contact, servicing of operating mechanism including tripping and closing system of the breakers, dehydrating, decarburizing of panel, bus bar section & circuit section including incoming/ outgoing cables, provide necessary HT insulation at joints. Removing perished monoplus compound cleaning and re-insulating with HT taps wherever necessary, with and including replacement of worn-out/defective spares like tension springs, torsion springs, nut bolts, washers of suitable size, lingers and de-carbonizing all joints, bus bar, CTs, PTs spout metal parts and making VCB perfect operation in manual and electric mode including all routine and preventive maintenance of breaker under the supervision of authorized dealer /representative and reconnecting the panel/breaker in its original position and testing all as specified and directed.
Note: - (i) The rate quoted inclusive of all minor spares and consumables etc. required at site.
(ii) Spares parts required other than mentioned here-in-after shall be deemed to be included in the quoted rate. | 28 | Each Job | 4,500 ₹1,26,000 | 6,500 ₹1,82,000 | 3,000 ₹84,000 Lowest |
| 2.00 | Supply and replace shunt trip coil 220/110 or 30 Volts DC | 2 | Each | 2,700 ₹5,400 | 5,000 ₹10,000 | 1,000 ₹2,000 Lowest |
| 3.00 | Supply and replace closing trip coil 220/110 or 30 Volts DC | 2 | Each | 3,600 ₹7,200 | 5,000 ₹10,000 | 1,500 ₹3,000 Lowest |
| 4.00 | Supply and replace panel space heater 80W complete all as specified | 3 | Each | 1,800 ₹5,400 | 1,500 ₹4,500 | 950 ₹2,850 Lowest |
| 5.00 | S&F in repair fuse element 20A-50A at 2/4pole 11KV structure unit complete all as specified and directed. | 3 | Each | 630 ₹1,890 | 1,000 ₹3,000 | 500 ₹1,500 Lowest |
| 6.00 | S&F in repair New vacuum interrupter 800/630A 11KV rating suitable for SEIMENS/CROMPTON/SCHINDER HT breaker all as directed by Engr-In-Charge | 2 | Each | 32,400 ₹64,800 | 20,000 ₹40,000 | 1,500 ₹3,000 Lowest |
| 7.00 | S&F in repair LED Indication lamps suitable for HT/LT breakers complete all as specified and directed. | 10 | Each | 270 ₹2,700 | 150 ₹1,500 | 100 ₹1,000 Lowest |
| 8.00 | S&F air ventilation fan with wiring of existing panel and taking down unsv ventilation fan with wiring complete all as specified and directed | 2 | Each Job | 2,700 ₹5,400 | 3,000 ₹6,000 | 1,000 ₹2,000 Lowest |
| 9.00 | S&F New air ventilation louver arrangement for existing VCB Panel including and taking down Unsv air ventilation louver all as specified and directed | 2 | Each Job | 2,700 ₹5,400 | 3,500 ₹7,000 | 1,000 ₹2,000 Lowest |
| 10.00 | S&F 200 watt heater for existing panel and taking down unsv heater complete all as specified and directed | 2 | Each Job | 1,800 ₹3,600 | 2,000 ₹4,000 | 600 ₹1,200 Lowest |
Tender Value
₹25 L
EMD Value
₹50,000
Closing Date
24 Oct 2025, 6:00 pmClosed
AGE I RD AVADI
AGE I RD AVADI, AVADI, CHENNAI 600054
REPAIRS AND MAINT OF HT / LT DISTRIBUTION NETWORK INCL REPAIRS TO HT VCBs, TRANSFORMERS, VOLTAGE STABILIZERS, LT CABLES, SWITCH GEARS AND REPAIRS TO LT PANELS, EARTHING AND CONNECTED WORKS AND IMPROVEMENT OF E/M INSTALLATIONS ETC AT CVRDE AVADI
2025_MES_725924_2
8699/E8
Open Tender
Civil Works
Item Rate
240 days
AVADI
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
AGE I RD AVADI
₹50,000
Yes
4 Dec 2025
16 Oct 2025
27 Oct 2025
16 Oct 2025
24 Oct 2025
17 Oct 2025
Amount
M&L for Servicing HT VCB panel cum breaker 1250/800/630A 13.1KA rating Indoor type make of SEIMENS/ CROMPTON/ SCHINDER after taking proper shut down and disconnecting the cables from panel draw out VCB breakers, earth fault relay, checking alignment of VCB isolating contact, servicing of operating mechanism including tripping and closing system of the breakers, dehydrating, decarburizing of panel, bus bar section & circuit section including incoming/ outgoing cables, provide necessary HT insulation at joints. Removing perished monoplus compound cleaning and re-insulating with HT taps wherever necessary, with and including replacement of worn-out/defective spares like tension springs, torsion springs, nut bolts, washers of suitable size, lingers and de-carbonizing all joints, bus bar, CTs, PTs spout metal parts and making VCB perfect operation in manual and electric mode including all routine and preventive maintenance of breaker under the supervision of authorized dealer /representative and reconnecting the panel/breaker in its original position and testing all as specified and directed. Note: - (i) The rate quoted inclusive of all minor spares and consumables etc. required at site. (ii) Spares parts required other than mentioned here-in-after shall be deemed to be included in the quoted rate.
Supply and replace shunt trip coil 220/110 or 30 Volts DC
Supply and replace closing trip coil 220/110 or 30 Volts DC
Supply and replace panel space heater 80W complete all as specified
S&F in repair fuse element 20A-50A at 2/4pole 11KV structure unit complete all as specified and directed.
S&F in repair New vacuum interrupter 800/630A 11KV rating suitable for SEIMENS/CROMPTON/SCHINDER HT breaker all as directed by Engr-In-Charge
S&F in repair LED Indication lamps suitable for HT/LT breakers complete all as specified and directed.
S&F air ventilation fan with wiring of existing panel and taking down unsv ventilation fan with wiring complete all as specified and directed
S&F New air ventilation louver arrangement for existing VCB Panel including and taking down Unsv air ventilation louver all as specified and directed
S&F 200 watt heater for existing panel and taking down unsv heater complete all as specified and directed
M&L for Inspecting electronic relay (over current relay and earth fault relay) from the 11 KV VCB and calibrating the relay with the help of secondary injection kit and proper setting of relays and refixing back in existing position testing of proper tripping/ functioning system complete all as specified and as directed.
M&L Taking proper shut down and disconnecting the cables from VCB, draw out faulty VCB breakers from panel 1250/800/630A 13.1 KA rating Indoor type make of SEIMENS/ CROMPTON/ SCHINDER after removing VCB spout and CT overhauling improving of IR value of hot air oven process and alignment of mechanism including installation in the same location and testing complete all as specified and directed.
M& L for Purification, filtration and Dehydration of transformer oil of transformer installed at various indoor/outdoor sub station by ultra high vacuum filtration machine with stream line filtration plant at a temp 60 to 70 deg. Celsius and achieving minimum dielectric withstand strength of 60 KV for 1 minute in 2.5 mm gap setting (for used oil) complete all as specified and directed by Engineer-in-Charge. Note: (i) Contractor shall ensure no wastage of transformer oil. (ii) Oil required for topping up the transformer will be measured & paid separately. (iii) Contractor shall be ensure that the conservator tanks are full to its level before starting the dehydration
Supplying and toping up new mineral grade transformer oil EHV type confirming to IS-335 to 1983 for filling and for topping up in transformer/Voltage stabilizer duly filtered with filer plant to obtain high dielectric not less 60 KV (Gap 2.5mm) complete all as specified and directed by Engineer In charge.
S&F in replacement of LT bush assembly brass complete with double check nuts, washers and oil seal all accessories with bushing insulators for transformer 100 to 500 KVA
S&F in replacement of HT bush assembly brass complete with double check nuts, washers and oil seal all accessories with bushing insulators for transformer 100 to 500 KVA
Taking out the unserviceable breather assembly complete form indoor/outdoor type transformer capacity up to 1000 KVA and supply and fixing the new breather assembly complete filled with fresh blue silica gel including connecting with proper rubberized gasket complete al as specified and directed
S&F new silica gel complete all as directed.
Material and Labour for preparing surfaces of transformer of capacity up to 2000 KVA by rubbing old paint and applying two coats of spray painting with grey duco paint from outside, complete all as specified and as directed. Note. Painting of transformer will be carried out for plinth mounted and pole mounted transformer, Necessary tools and plants shall be arranged by the contractor. Shut down schedule for painting of transformer will be submitted in advance to plan shut down in the station.
Material and Labour for surface dressing cutting removing of bushes, vegetations trimming of trees and removing the existing aggregate leveling the surface bedding thickness after leveling spreading the aggregate all around the main receiving station/panels/transformer installations and all substations, including clearing the site all as specified and directed
Supply and laying/spreading 40 mm graded gravel(stone aggregate) 40mmthick, bedding thickness of 100 to 150mm in any position at electrical 2/4 pole structure all as directed.
Material and Labour for defect rectification in HT 11 KV cable laid in trenches by locating fault with the help of electronic fault locator machine comprising of surge generator pulse fault location with high frequency distance calculator etc. Excavation in any type of soil strata exposing the cable fault removal of deteriorated position of cable treating of cable and keeping the same ready for jointing work for cables of size up to 240 Sqmm 3core. Notes : (i) The contractor shall bring the fault locating equipment at site with in 02 hours of instructions received from Engineer -in- charge and he shall ensure that the fault is rectified with in 24 hours of receipt of intimation from Engineer-in-charge failing which recovery of Rs. 500.00 per hour shall be recovered from the contractors dues w.e.f the time immediately after the expiry of 24 hours duration. (ii) For the purpose of payment one unit of “each job” shall comprise of detection of faults in a particular stretch of cable (i.e from breaker to breaker) which are identified in that particular stretch, irrespective of number of defects / faults in that particular stretch which are detected during fault detection and the contractors unit rate quoted shall be deemed to include for the same and all such defects / faults which are detected in that particular stretch shall be considered as one unit.
(iii) Joints, jointing materials and cable required shall be measured and paid for separately. (iv) The payment is not applicable for error fault finding location. (v) Quoted rate is deemed to be including removal of moisture from cable by standard engineering practices and no extra payment will be allowed in this regard.
Taking out old unserviceable under ground PVC/XLPE HT cable of any size from trenches/ wall/ roof/ road/ pipe/ pole including segregation of serviceable bricks for re-use complete all as specified and as directed.
Relaying/ rerouting of old serviceable under ground PVC/XLPE LT cable any grade and any size in trenches/fixed to wall/pole/roof/laid in floor including necessary connections and thimbling complete all as specified and as directed. (Earth work, brick & sand cushioning shall be measured and paid for separately under appropriate item).
Supply and laying HT XLPE insulated, screened PVC bedded, galvanized steel strip or wire armoured, electric power cable (heavy duty) with aluminum conductor 11000 volt grade, cross sectional area 150 Sqmm, 3 core (earthed) conforming to IS-7098 (Part-I) laid in trenches / under floor / roads / along poles/ducts etc. all as specified and directed
Supply and fix in repairs cable jointing kit for 11 KV cable for out door end termination Heat shrinkable with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm to 185 sqmm, indoor type all as directed.,
Supply and fix in repairs cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint with jointing material and accessories suitable for 3 core XLPE, armoured aluminium conductor of size 120sqmm to 185 sqmm cable complete all as specified and directed.
Supply and fix in repairs cable jointing kit for 11 KV cable for indoor end termination Heat shrinkable with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm to 185 sqmm, indoor type all as directed.,
Excavation in trenches not exc 1.5 Mtr wide and not exc 1.5M depth in soft/loose soil for laying of cable, pipes etc and getting out in soft/loose soil all as specified and directed.
Returning, filling, including spreading, levelling, watering and well ramming in layers not exc 25cms of soil complete all as specified and directed.
Removing the surplus excavated material/soil to a distance not exc 50Mtrs and depositing, where directed at a level not exceeding 2.5 Mtr above the starting point all as specified and directed.
Supply and spread sand for sand cushioning of cables in trenches all as specified in MES Schedule Part-I and all as directed. Note: Punned thickness only will be measured and paid.
Supplying and laying un-reinforced precast concrete cable cover, Class LV, Type I, flat, size 250 mm x 150mm x 40mm
Re-laying old PCC cover for cable protection cover, laid flat and dry in trenches over the cable , perpendicular to the direction of cable complete all as specified and as directed.
Supply and fix or passing through pipe/wall/floor/trenches XLPE insulated PVC bedded, galvanized steel strip or wire armoured electric power cable (heavy duty) 1100 volts grade with glanded aluminium conductor of following size:-
10 sq mm 2 core
16 sq mm 4 core
25 sq mm 4 core
35 sqmm 3.5 core
50 sqmm 3.5 core
70 sqmm 3.5 core
95 Sqmm 3.5 core
120 sqmm 3.5 core
Supply and Fix in replacement of PVC insulated PVC sheathed multistranded single core copper conductor 1100 Volts grade of size 185 Sqmm with suitable heat shrink sleeves, copper lugs, glands, Bolts and Nuts etc complete all as specified and as directed.
Taking down old damaged HDPE pipe and S&F double Wall Corrugated’ (DWC) pipe 110 mm outer diameter size conforming to IS 16205 Part 24 round shape jointing with necessary fitting complete as per site requirement laid in trenches/ floor for UG cable protection complete all as specified and directed.
Taking down old damaged HDPE pipe and S&F double Wall Corrugated’ (DWC) pipe 90 mm outer diameter size conforming to IS 16205 Part 24 round shape jointing with necessary fitting complete as per site requirement laid in trenches/ floor for UG cable protection complete all as specified and directed.
Taking down damaged HDPE pipe and S&F double Wall Corrugated’ (DWC) pipe 50 mm outer diameter size conforming to IS 16205 Part 24 round shape jointing with necessary fitting complete as per site requirement laid in trenches/ floor for UG cable protection complete all as specified and directed.
Taking down damaged HDPE pipe and S&F double Wall Corrugated’ (DWC) pipe 40 mm outer diameter size conforming to IS 16205 Part 24 round shape jointing with necessary fitting complete as per site requirement laid in trenches/ floor for UG cable protection complete all as specified and directed.
Supply and lay GI tubing 80 mm bore, light grade, galvanised, ISI marked with all specials for cable protection on road crossing/floor etc duly sealed at both ends after drawing cable all as specified and directed.
Supply and lay GI tubing 50 mm bore, light grade, galvanised, ISI marked with all specials for cable protection on road crossing/floor etc duly sealed at both ends after drawing cable all as specified and directed.
S&F in repair Earthing complete with galvanised steel earth plate electrode 60x60cm x 6.0mm thick buried directly in ground (earth pit not less than 2.25 mtr deep below ground level) with top edge of the plate not less than 1.5 mtr below normal ground level, connected to and including using of 25x4 GI strip as earthing lead by means of bolts, nuts, check nuts and washers of galvanised steel , connected to earthing test point, all as specified & indicated, including testing on completion including earth work and excavation in any type of soil/rock, PCC 1:3:6 type C1, earthing chamber, precast RCC slab 50mm thick in cement concrete 1:2:4 type B1 reinforced with welded steel wire fabric weight hot less than 4 Kg/Sqm, funnel with GI watering pipe of 20mm bore, medium grade wire mesh and lugs, GI protection pipe of 15mm bore light grade upto 7.50 mtr long test point etc all as specified and directed.
Material & labour for repairing existing earthing any type incl making & cleaning of earth pit, repair of pits, fixing of new funnel , pit cover, painting on pit with cement base white paint complete all as per direction of Engr-in-charge. Note: (i) Cost of funnel, pit cover, cement work, PCC work and painting etc incl is quoted rate.
Supply and fixing of Earth continuity strip or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 24x4 mm GI strip complete all as directed by Engr-in-Charge.
M & L for maintenance of APFC panel any type and size, dismantling opening and taking down of all incoming and outgoing cables, cutting burnt edge of the cable whatever is required, providing thimble lugs and glands of suitable required for different size of cable including taking out loop of the cables, including replacement of bolts nuts & washers and reconnecting the all incoming and outgoing connections, checking of serviceability of capacitors and testing of panels on full load all as specified and as directed. Note: Capacitors shall be measured under relevant items.
Supply only repair suitable capacitor 5 KVAR 440V complete on existing APFC Panel and testing all as specified and directed
Supply only repair suitable capacitor 7.5 KVAR 440V complete on existing APFC Panel and testing all as specified and directed
Supply only repair suitable capacitor 10 KVAR 440V complete on existing APFC Panel and testing all as specified and directed
Cutting of road to a width of 30cm and depth not exceeding 90cm for laying of protection pipe / cable including returning and filling, spreading levelling, watering and well ramming in layers and making good with PCC 1:2:4 type B1 for top 100mm thick complete all as specified and directed.
M&L for attending any breakdown in LT UG cable by excavating , identifying core fault and carry out jointing work including straight through heat shrinkable type joint of cable size 6-16 Sqmm 4 core complete all as specified and as directed. Note: Excavation, returning filling , removal & taking down of the cable shall be measured under relevant items.
All as per item No 51 above but 3.5Core 25-50 Sqmm all as specified and as directed.
All as per item No 51 above but 3.5Core 70-120 Sqmm all as specified and as directed.
All as per item No 51 above but 3.5Core 150-185 Sqmm all as specified and as directed.
Opening /disconnecting the electrical connection of defective/burnt out underground LT cable of any size any core from main DB/feeder pillar / LT panel/ L T O/H line etc. Taking out the required length of cable from existing loop, cutting the defective portion of cable ,providing required thimbles/connectors at cable end and reconnecting the cable in previous location with existing main DB/Feeder pillar/LT panel/O/H line etc all as directed. Note:-cement work to match the existing surface is deemed to be included in quoted rates and nothing extra should be paid on this account. (ii) Additional cable/ protection pipe required at site shall be measured and paid separately.
S&F in repair MCCB 3 Pole, 415 V, fixed thermal and magnetic type, 25 to 100A with breaking capacity 16 KA with suitable spreaders on existing LT Panel/Feeder pillar box include taking down complete all as specified and directed.
S&F in repair MCCB 4 Pole, 415 V, fixed thermal and magnetic type, 125A with breaking capacity 16 KA on with suitable spreaders existing LT Panel/Feeder pillar box include taking down complete all as specified and directed.
S&F in repair MCCB 3 Pole, 415 V, fixed thermal and magnetic type, 160 Amps with breaking capacity 36 KA with suitable spreaders existing LT Panel/Feeder pillar box complete all as specified and directed.
S&F in repair MCCB 4 Pole, 415 V, Adjustable thermal and magnetic type, 200 Amps with breaking capacity 36 KA with suitable spreaders on existing LT Panel/Feeder pillar include taking down complete all as specified and directed.
S&F in repair MCCB 4 Pole, 415 V, Adjustable thermal and magnetic type, 400 Amps with breaking capacity 36 KA with suitable spreaders on existing LT Panel/Feeder pillar box include taking down complete all as specified and directed.
S&F in Extended Rotary Handle suitable for MCCB any rating/ make as per site requirement complete all as specified and directed.
S&F in repair MCB TPN 63A 10KA breaking capacity, 'C' curve complete all as specified and directed.
S&F in repair change over switch manual type with sheet metal enclosure 200 A rating TPN 415V complete all as specified and directed.
Supply and Fix in replacement of Power contactor (MNX 43) AC 4 Pole 415 Volts of capacity 400 Amps with auxiliary contactor including necessary fixing accessories complete all as specified and as directed.
M & L for servicing and repairs to ACB of any capacity up to 1250 Amps of any type after careful disconnection of all electrical connections, repairs to operating mechanism, auxiliary contacts, replacement of intelligent controller, shunt release & UV coil etc including repairs to main body and handle complete all as specified and as directed.
M&L for taking down cable of any type of size of existing cable 16 sqmm to 185 Sqmm from trench/duct/wall etc including old bricks/PCC cover and re routing/relaying in trench/Cable Tray/Floor/Wall including termination/ connection complete as specified and directed. Note: Excavation, sand items shall be measured under relevant items.
M&L for replacement of hinges for both internal & external partitions with necessary welding/sheet metal work including necessary repairs to locking arrangements etc as per site requirement for smooth closing /opening of existing LT Panel/Feeder pillar box, spray painting with 2 coats of synthetic enamel paint over one coat of red oxide primer complete all as specified and directed.
M & L for repair/ maintenance of LT feeder pillar /LT panel board any type and size indoor/outdoor by dismantling opening and taking down of all incoming and outgoing cables of any size, cutting burnt edge of the cable whatever is required, different size of cable including taking out loop of the cables, cleaning of bus bars by means of rubbing grinding etc and providing PVC sleeves of suitable rating on bus bars maintaining colour code (RYB & N), repairs to panel board wiring for all controls with suitable copper wires including replacement of bolts nuts & washers and reconnecting the all incoming and outgoing connections and testing of panels on full load all as specified and as directed. Note : MCCBs required will be measured and paid separately. Quoted rate is deemed to be inclusive of misc consumable items like heat shrink sleeves, Lugs, double compress type cable glands of suitable size for both incoming and out going, insulation tape, Bolts and nuts etc as required at site complete.
M&L for preparation old painted surface, painted with 2 coats of synthetic enamel paint over a red oxide primer on surfaces of LT Panel any size complete all as specified and directed.
Refilling of CO2 gas in the existing CO2 fire fighting cylinders of capacity 4.5 Kg per cylinders and painting & marking complete all as specified and directed by Engineer in charge .Note: Dismantling, transportation and hydro testing for the cylinders by CCE approved gas filling agency are deemed to be included in the quoted rate
SRIRAM ELECTRICALS (BID ID -3464341)
Banyan Engineers and Contractors (BID ID -3463075)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.52 MB
BOQ_823626.xls
BOQ • 0.40 MB
Tenderdocuments.pdf
Tender Documents • 1.33 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .