GM (Civil)/TA
Town Admn Deptt , CCL HQ , Ranchi
Providing and installation of VRF system (variable refrigerant flow) at ERP centre and CMPF office at old press building CCL, DHC, Ranchi on turnkey basis and comprehensive Maintenance of plant for ten years.
2022_CCL_258565_1
CCL/TA/Tender/EnM/ 22-23/3144-56 Dt.07.10.2022
Turnkey
Electrical and Maintenance Works
Item Rate
3800 days
Darbhanga House campus, CCL, Ranchi
As per NIT
9 documents required · 9 mandatory
₹3.3 L
Town Admn Deptt , CCL HQ , Ranchi
17 Jan 2023
10 Oct 2022
9 Nov 2022
11 Oct 2022
8 Nov 2022
14 Oct 2022
11 Oct 2022 - 28 Oct 2022
13 Oct 2022
Amount
A. OUTDOOR UNIT
Supplying, installation, Testing & Commissioning, modular type Variable Refrigerant Flow/Variable Refrigerant Volume aircooled Outdoor units suitable for cooling and heating,having all hermetically sealed inverter type Scroll Compressor(s) ,minimum two compressors for above 14HP modules, microprocessor based Controller, top discharge, type condensing unit(s), with R410A Refrigerant, vibration isolators, with suitable foundation etc. complete as required. The unit shall deliver therated capacity at AHRI Conditions and work evenat 50°C ambient temperature without tripping.The unit shall be suitable to work on 400V+/-10%,3Phase,50 Hz AC power supply.The unit shall be filled with first charge of the refrigerant and ready for useas required.The CO Pat AHRI conditions shall not be less than 3.1 and IEER not less than 6.5 etc. all complete as per instruction of EIC. (Minimum capacity should be 190 HP) (Tentative BOQ to be executed is detailed in Volume II).
B. INDOOR UNIT- CASSETTE UNIT
Supply,installation,testing and commissioning of ollowing minimum capacity 4,way flow VRV/VRF Cassette Type Indoor ceiling mounted unit equipped with synthetic washable mediapre-filter, fan section with low noise fan/dynamically balanced blower, multispeed motor, coil section with DX Copper coil, electronic expansion valve, outer cabinet, drainpump, grill, necessary supports, vibration isolation ,cordless remote controletc.,suitable for operationon single phase2 30V±10%, 50Hz AC supply, complete, asrequired. The unit shall have automatic force shutdown provision incase of ireon receiving signal from BMS System. The cooling capacity of indoor unit will be at air inlet conditions of 27 Degree CDB and 19 Degree CWB temperature etc. all complete as per instruction of EIC. (Minimum capacity of total cassette unit- 134.4 Tr, Individual capacity of cassette unit should vary from 1 Tr to 4Tr as per site requirement) (Tentative BOQ to be executed is detailed in Volume II.)
C. Installation and commissioning
(a) Refrigerant Piping:- Supply,Installation,testing and commissioning including vaccumiazation and Nitrogen testing of different nominal sizes of soft/hard drawn copper refrigerant piping for VRV/VRF system, complete with fittings, with suitable adjustable ring type hanger supports, jointing/ brazing including accessories, insulated with XPLE Class-O tubular insulation/ with Class-O closed cellelastometric nitrile rubber tubular sleeves sections of specified thickness as given below for Suction and Liquid lines, all accessories as per specifications etc. as required (Minimum pipe size 6.4 mm OD, pipe size will be as per site requirement) (b) Drain Piping with uPVC as required(c) Earthing with suitable no earthpit and connections as required (d) Communication cabling between indoor and outdoor as required (e) Suitable power supply arrangement to indoor and outdoor as per requirement (f) Fabrication of structure for outdoor base (g) Repairing of false ceiling as per requirement etc. all complete as per instruction of EIC. (Tentative BOQ to be executed is detailed in Volume II)
D. COMPREHENSIVE MAINTENANCE
Comprehensive Maintenance for 9 (nine) years after completion of one year free maintenance etc. all complete as per instruction of EIC. Refer Clause 2.0 of Vol II
Total impact of GST for the purpose of CTC
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .