Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹44.0 LAccepted-AOC 306 SHIV BARI MARG PANCHVATI NAGAR BATHINDA 151001 PB | BATHINDA | BATHINDA | PUNJAB | 151001 | L1 | Accepted-AOC LI | |
| 2 | L2₹55.4 L+₹10.9 L (24.4%)Rejected-AOC | L2 | Rejected-AOC L2 | |
| 3 | L3₹59.4 L+₹14.8 L (33.3%)Rejected-AOC KOHLI NO 17509 GALI KHADDAR BHANDAR WALI BHI WALA ROAD BATHINDA PB 151001 | BATHINDA | BATHINDA | PUNJAB | 151001 | L3 | Rejected-AOC L3 | |
| 4 | L4₹60.6 L+₹16.1 L (36.1%)Rejected-AOC A 102 GOLDEN SAND APARTMENTS GAZIPUR DHAKOLI ZIRAKPUR PB 160104 | ZIRAKPUR | S A S NAGAR | PUNJAB | 160104 | L4 | Rejected-AOC L4 | |
| 5 | L5₹63.1 L+₹18.5 L (41.6%)Rejected-AOC | L5 | Rejected-AOC L5 |
Tender Value
₹75 L
EMD Value
₹1.4 L
Closing Date
15 Jun 2022, 6:00 pmClosed
CWE Bhisiana
HQ CWE Bhisiana
REPAIR OF CENTRAL AC PLANTS AND PACKAGE TYPE AC PLANTS AT AF STATION BHISIANA
2022_MES_519787_2
CWE(BHI)/BHI-04/2022-23
Open Tender
Civil Works
Item Rate
270 days
AF Bhisiana
AS PER COVER 01
6 documents required · 6 mandatory
₹1,000
Yes
GE AF Bhisiana
₹1.4 L
Yes
8 Jul 2022
26 May 2022
17 Jun 2022
26 May 2022
15 Jun 2022
3 Jun 2022
26 May 2022 - 31 May 2022
Amount
COOLING TOWER. Supply, Installation, Testing and Commissioning of Induced draft counter flow, vertical discharge-type FRP Cooling tower of 1.20 lacs kCal/hr heat rejection capacity with ultra-violet treated durable & highly efficient PVC fillings with integral louvers and drift eliminators, open pan suitable for water distribution complete with hot FRP water basin. The hot water shall be distributed to fills in each cell via open-type gravity basin or with spray nozzles or having self rotating sprinklers. Cooling tower shall be provided with statically and dynamically balanced one/two nos. anti-corrosion treated axial flow type fan - direct driven or driven through special bevelled reduction gear box with TEFC induction flame-proof motor with IP- 65 protection, IE-2, suction screen, make up and quick fill arrangement, overflow and drain connections and suitably inspected hot-dipped galvanized ladder, access arrangement for cooling tower interior, anti vibration mountings etc. complete as required. The unit shall be instate including testing on completion by Engineer in charge, flexible duct connector etc., complete as per following capacities. (a) Water Leaving Temperature : 90 deg F. . (b) Water Entering Temperature : 97.5 deg F. Water Flow Rate : 116 USGPM. . (d) Ambient Wet Bulb Temperature : 83 deg F. . . Note: Suitable arrangement of platform and connected accessories for mounting cooling tower and ensure noise restriction to adjoining buildings, inclusive PCC 1:3:6, plaster, brick works required to installation of cooling tower.
Note :- The unit rate quoted by the bidder shall be inclusive all control wiring, Display panel, Control panel, relay to match with existing system. The cost shall also inclusive of making water pipe/Electrical connection from Cooling tower to Existing pump & Motor & inlet and out let water pipe line. The contractor will ensure that the Cooling tower shall be fully/completely functional with the existing plant and the contractor is required to provide any material and equipment for this but no extra payment will be made on this account. If the contractor failed to make fully functional of control tower, no payment shall be released. The bidder is required to visit the site of plant 3001 building to accertain the nature and scope of the work and nothing extra shall be paid to the bidder on this account”
Supply in replacement of Air filter aluminum anodize frame, of size 590 x 590 x 50 mm thick non woven synthetic type of size (as per sample) suitable for dust filtration 10-20 micron having 90% efficiency and suitable for AHU etc complete all as specified and directed by Engineer-in-Charge. Make : Thermodyne
All as item No 15 above but of size 920 x 640 x 25 mm, complete all as specfied and as directed.
Taking down of old u/s cooling tower installed at 3001 bldg AC plant including dismantling og MS/GI pipe fixed in cooling tower all as specified and as directed. Note :- The cost shall be inclusive Dismantling of U/S cooling tower from Old platform and transport to MES Store.
M&L for Pump down the existing refrigerant in separate cylinder disconnecting of electric motor of compressor refrigerent line gauge pipe opening and dismantle of compressor for general overhauliing model No 05040S MAKE VOLTAS capacity 30 TR to carry out the inspection of compressor including replacement of springs, aluminium washer packing screw cleaning detergent cotton waste , etc and cleaning the suction filter oil filter replacement of defective parts assemblying the compressor testing and if found leakge rectify them. Re-charging of refrigerent R-22 compressor, Refilling oil and testing on connected load the compressor all as directed by Engr-In-Charge Note-1: The charging of gas will be measured and paid separately. Note-2: Spares of compressor and refrigerent shall be measured and paid as supply only as under:-
Supply only spare parts for pump set for fixing against item above follows:-
Gasket set suitable for 30 TR capcity
Loading un-loading solenoid valve
Suction reed
Piston Ring
Piston
Piston liner
Main bearing
CR Bearing
Discharge valve assembly
Piston Pin
Oil pump coupling
Oil pump repair Kit
Suction plate
shaft seal
Oil regulating valve
Piston pin bush
Discharge reed
Filter catrige
Crank shaft
M&L Replacement of new liquid line filter for 30 TR of existing size and make, all as specfied and as directed.
M&L Replacement of shaft seal assembly suitbale for refrigeration compressor 30 TR model 05040S make Accel sabore, complete all as specfied and as directed.
M&L Replacement of liquid line valve 3/8 inch size by replacing 'O' ring , gladnbush tephlon washer etc, complete all as specfied and as directed.
M & L opening compressor cover of both side including disconnecting of water pipe line for inlet and out let of the condenser of each plant removing scale /sludge Precipitated in the copper tube by push and pull method with iron rod connected with steel wire brush of suitbale size as per condenser copper tube size at the entire length of condenser that scraping down the sludge Precipitated in side the tube. closing both side of condenser and cirulating the descalling soulation in all tube of condenser of plant through the circulating pump and allow it for 30 mnt for chemical reaction. opening the condense both side and clean with iron rod connected with nylon brush of suitable size as per condenser coppper tube size at the entite length of condenser at both end and cirulatin clean water in all the tube of condenser of plant and drain out The process will be continued till the satisfaction of Engr-In-Charge then fixing new gasket for both ends of the plant capacity 30.0 TR at Tech Area, complete all as specfied and as directed.
Pressure testing for entire system of the AC plant of all condenser , compressor and circulating system with CO2/Nitrozen gas and retain to allow the pressure for three days. If found any leakage or reduction in the scale of pressure shall be located and arrest the leakge immediately by soldering or an appropriate measure to stop the leakage permanently 3 x 30 TR capacity, complete all as specified and directed by Engineer-in-Charge.
Pressure testing for entire system of the AC plant of all condenser , compressor and circulating system with CO2/Nitrozen gas and retain to allow the pressure for three days. If found any leakage or reduction in the scale of pressure shall be located and arrest the leakge immediately by soldering or an appropriate measure to stop the leakage permanently 52 TR capacity central AC plant, complete all as specified and directed by Engineer-in-Charge.
Pressure testing for entire system of the AC plant of all condenser , compressor and circulating system with CO2/Nitrozen gas and retain to allow the pressure for three days. If found any leakage or reduction in the scale of pressure shall be located and arrest the leakge immediately by soldering or an appropriate measure to stop the leakage permanently upto 25 TR capacity central AC plant, complete all as specified and directed by Engineer-in-Charge.
M&L for blocking the punctured tubes of the with brass pillet capacity 30 TR , complete all as specfied and as directed.
Suppply and fill in replacement of compressor oil non freezing type N-68 complete all as specified and directed by Engr-In-charge.
M&L for checking the leakge by vaccum plant for 24 hrs in both low and high side of the system by feeding dry nitrogen to maintain adequate pressure in the system . Plugging the leaks by providing of Teflon taps sealing of all refrigerent line valves like liquid lines valves /suction /discharge valves of compressor , gland packing of all angle valves flaring of all connections framing welding etc complete capcity 30.0 TR, complete all as specfied and as directed.
S & F Replacement of globe service valve from suction line of compressor common suction line at compressor, all as specifeid and directed.
S & F in replacement of ball/roller bearing from the blower shaft including greasing make of bearing NBC or equivalent complete all as specified and directed by Engr in Charge.
S&f replacement oil pressur cut out me all as specified and as directedAs per existing Make or Model, complete all as specified and directed by Engineer-in-Charge.
S&f replacement hand shut off valve /angle valve of size 1/4 inch ass as specified and as directed As per existing Make & model, complete all as specified and directed by Engineer-in-Charge.
Repair to liquid line valve 3/8 inch size by replacing 'O' ring , gladnbush tephlon waher etc, all as directed as as per existing make & Model, complete all as specified and directed by Engineer-in-Charge.
S&f replacement shaft seal assembly suitbale for refrigeration compressor 30 TR model 05040S make Accel sabore all as specified and as directed
M&L for cleaning the evaporator coils and fins -3 nos with cleaning agent such as acid , caustic soda solution and removing all dust and dirt etc, complete all as specified and directed.
M&L for Removing of ALPHA filter from its positionand layout at site for refixing after cleaning AHU cooling using chemical withbrass brush in- order to remove all type of sledge /dust precipitatated on the coil without any damage to tehcopper cooling coil then wash the cooling with fresh water and air blower upto the satisfactory of engr-in-charge cooling coil drain water shall be clean , if any type of obstacle on the flow of water iron body of the AHU inside and out side shall be scrap downand rub out with sand paper then apply one coat primer over a coat of synthetic ebameled paint including art of duct portion in the AHu shall be completed upto the satisfactory of engr-in-charge for the 17 TR capacity ac palnt, all as specified and as directed.
All as above but cap 10TR.
All as above but cap 25-30TR.
All as above but cap 52 TR.
S&F in replacement electrical contactor Kit suitbale for existing size and rating a (sample available in AGE E/M office) all as specified and as directed).
M & L for cleaning and removing all scales and dirt etc, from PVC tanks of capacity up to 2000-5000 Ltrs Ltrs and from mouth by emptying, drying, cleaning by scrubbing the dust with wire brush, after removing inlet and out let pipes (also cleaning the mouths of circulating pipe) and refixig including printing date of cleaning with synthetic enamel white paint in proper format and reconnecting all inlet and outlet pipes all as specified and as directed. NOTE: If float valve broken at the time of cleaning by the contractor has to replace it without any extra payment.
S&F in replacement Blower pully of up to 30 TR plant as per existing blower capacity (Sample availabe as AGE E/M office), all as specified and as directed. Note : The cost shall be included lathe work for blower pully and realignment and again fitted in existing AHU.
S&F in replacement short neck of duct made of canvas cloth minimum 3 mm thick connected with air blower to GI duct size of 50cm x50 xm x 10 cm complete fixing with air sealed to duct including nut boltts ,clamps . Note : If found leakge in plant the contractor has responsible to repair without any extra cost.
M&L for cleanig of rusted portion of duct and dust settled in existing duct & dampers in whole building where is passing of duct and all floors going from main duct to branch duct number unit duct and diffusers and plant by using suitable equipment or suction machine / compressor from AHU to neck duct. Note :- The cleaning shall be carried out in complete portion of duct using Robots & Vacuum Machine to cleaning of inside and outside of duct.
M&L for Dismantling the Blower unit Complete of AHU unit and balancing the main shaft , cleaning the entire Cooling Coil with wire brush , cleaning and making the Air fins free from dirt and blockages , checking the fan belt tension , tightening the driver and drive pulleys and replacement of Shaft bearing for Central type AC Plant including reassembling the AHU unit & testing, Commissioning complete all as specified and directed by Engr in Charge.M&L for Comprhensive mainnence /overhauling /repair of complete air handling unit ambiator chamber including necessary oiling/greasing , cleaning and realignment motor with blower of existing plant of capacity 24000 -30000 CFM all as directed.
S&F in replacement Cellulose or celldek pads and supply and fix in air cooling tower new consists for cellulose wood fibres in paper form . having high quality standard and posses on efficiency of more than 85%, complete all as specfied and as directed. Note :- More than 85% minimum thickness of cellulose pad should be 150mm:- (a) Mode of Measuring:- Sqm of cellulose pad (L X B) with 150mm thickness of pad shall be measured. (b) Minimum number fins (i.e. laminar surfaces ) in a cellulose pad 150mm thick should be 12.
S&F in replacement aluminium grills for air supply made out of powder coated extruded aluminium grils adjustable type with variable angle and verticle and horizantal louvers and gape between louvers should be 25 mm with volume controls dampers complete all as directed.
S&F in replacement MS angle frame work for installation of GI duct of different sizes , made out of MS angle iron of any size including fabrication of suitbale frames for GI ducts different size ducts and making hole for fixing nut bolts complete all as directed.
S&F in replacement MCB 4 pole 63 amps, breaking capacity 10 KA, confirming to IEC60947-2, 415 volts, 50 Hz including making necessary incoming and out going electrical connection with suitable size of copper lugs etc, complete all as specfied and as directed.
S&F in replacement MCCB 3 pole 100 amp , breaking capacity 16 Ka, 415 volts, 50 Hz including necessary incoming and out going electric connection with suitable size of copper lugs etc, complete all as specfied and as directed.
M&L for attending complaint of Central/Package type AC Plant regarding gas leakage, control/panel wiring, compressor failure,sensor issue,blower issue, chiller , Display panel, PLC unit or any other issue resulting in non-functionality of Plant thoroughly by rep of concerned VOLTAS/BLUESTAR all as specified and directed by JE/AGE E/M, complete all as specfied and as directed. Note:- Material found defective will be paid separately
M&L for repair/grinding of blower shaft make Accel, Model SMC 2– 65 , Capacity 5/ 7.5/10TR to the required size as directed by Engineer-in-charge, complete all as specfied and as directed.
Material and labour for repair/grinding of blower shaft make Accel , Capacity 25-30 TR to the required size as directed by Engineer-in-charge, complete all as specfied and as directed.
S&F in replacement Digital panel mounted ampere meter 0-60 amp with CT complete all as directed , complete all as specfied and as directed.
S&F in replacement 3 pole contractors type NC-3, MNX -18 Rating 40 amps, 415 volts and coil voltage - 220 volts, complete all as specfied and as directed.
S&F in replacement 3 pole contractors type NC-3, MNX- 12 Rating 15 amps, 415 volts and coil voltage - 220 volts, complete all as specfied and as directed.
S&F in replacement 3 pole contractors type NC-3, MNX- 9 Rating 15 amps, 415 volts and coil voltage - 220 volts, testing complete all as directed by Engr in charge.
S&F in replacement 3 pole contractors type NC-3, MNX- 25 A , 415 volts and coil voltage - 220 volts, complete all as specfied and as directed.
S&F in replacement overload relay rating 19-32 amps, 415 volts, complete all as specfied and as directed.
S&F in replacement overload relay rating 0-9 amps, 415 volts, Type - MNX , complete all as specfied and as directed.
S&F in replacement MCCB 4 pole 250 amps 36 KA complete all as specified and as directed
S&F in replacement 3 pole contactors type ML-1.5, Rating 32 amps, 415 volts and coil voltage - 220 volts complete all as specfied and as directed.
S&F in replacement 3 pole contactors type ML-2, Rating 40 amps. 415 volts and coil voltage - 220 volts, complete all as specfied and as directed.
M&L for reconditioning of cooling tower fan motor set of any capacity including oiling ,gresing replacement of fan blade damaged shaft,internal winding,testing compelete all as directed by Engr in Charge.
M&L Servicing the condensor water Pump set of any capacity including oiling , greasing, replacement of gland paking , tightening the bolts and nuts , testing complete all as directed by Engr in charge.
Supply & Charging Refrigerant Gas R-22/F-22 in company's sealed cylinder returnable , complete all as specfied and as directed.
M&L for replacement of thermometer 12 mm dia , range 0-100 degree centrigraded suitable for fixing at condesor water outlet including removing of U/S thermpmeter, complete all as specfied and as directed.
M&L for replacement of Overload relay for compressor starter 13.2 A to 20 A, complete all as specfied and as directed.
M&L for replacement of V Belt size A-29, A-30, complete all as specfied and as directed.
M&L for replacement of V Belt size B-32,B-34 all as specified and directed by engr-in-charge.
M&L for replacement of V Belt size B-36 all as specified and directed by engr-in-charge.
M&L for replacement of V Belt size B-69, all as specified and directed by engr-in-charge.
Supply & Charging Refrigerant Gas R-407 in company's sealed cylinder returnable all as directed.
S&F in replacement Ball valves high Pressure of PTMT with epoxy coated Aluminium rod & highdenesity plastic ball screwed for iron Pipeand fixed of size 25 mm dia complete all as specified and directed.
Supply and fixing Expansion Valve Upto 12 Ton, complete all as directed.
Supply and fixing in replacement Butter fly Valve 50 mm dia with all acessories for iron Pipe and fixed all as specified and directed by Engr in Charge.
Supply and fixing in replacement Butter fly Valve 65 mm dia with all acessories for iron Pipe and fixed all as specified and directed by Engr in Charge.
Supply and fixing in replacement Butter fly Valve 100 mm dia with all acessories for iron Pipe and fixed all as specified and directed by Engr in Charge.
Supply and fixing in replacement Butter fly Valve 125 mm dia with all acessories for iron Pipe and fixed, complete all as specified and as directed.
M & L for Preparation of Old Surface of Central type AC plant of 7.5 TR to 52 TR capacity, preparing the surface by rubbing with fine emery paper and making the surface smooth and re-painting with two coats of super quality synthetic enamel paint by Spray gun fully matched with its original colour and making good all equipment and including Marking SM/MES No on Plants , LT panel with diffrent Paint maintaning colour code complete all as specified and directed by Engr in Charge to the following :- (i) Compressor and Motor with Channel including Foundation -03 nos (ii) Condensor Pump Set-02 Nos (iii) AHU-01 Nos (iv) LT Control Panel Complete (v) Liquid / Suction line (vi) Cooling Tower
All as per Item above here in before but Package type AC plants of 5.5 TR to 17 TR capacity consisting of the following :- (i) Package type AC Plants unit Complete-03 Nos (ii) LT Control Panel (iii)Out door condensing Unit Complete with Blower fan -03 Nos (iv) Liquid/Suction Line
Supply and Fix in replacement gate Valve Upto 25 mm Dia Complete with flanges,bolts,nuts, gasket etc, all as specified and directed .
Supply and Fix in replacement Gate Valve 32 mm Dia Complete with flanges,bolts,nuts, gasket etc, complete all as specfied and as directed.
Supply and Fix in replacement Y- strainer CI of 65 mm Dia, complete all as specified and directed.
Supply and Fix in replacement Y- strainer CI of 80 mm Dia, complete all as specfied and as directed.
S&F in replacement 3 pole contractors type MNX A2, MNX -12 Rating 30 amps, 415 volts and coil voltage - 220 volts make as per existing, complete all as specfied and as directed.
S&F in replacement Single Phase Preventor (VSP 3) ,415 VAC,50 Hz complete as per existing make, all as specified and directed by Engineer-in-Charge.
S&F in replacement Smoke and fire damper with indication of AHU,Actuator,fire & Smoke as per existing type and make complete all as specified & directed.
M & L for redownloading the Software for automation/running hours for Compressor of central/package type type AC Plant capacity 52 TR, Soft Ware installed as per Voltas Company norms by the Voltas Company soft ware Engineer including testing commissioning complete all as specified and directed by Engr in Charge.
S&F in replacement Electronic Actuator 24VAC,Model R-981-R of make Rapid Control complete all as specified & directed.
S&F in replacement Liquid level Controller 240VAC Having Sensitivity, Delay & Manual start Function Cat Part No.-4421AD1 complete.
S&F in replacement Air Break (Power) Contactor 3 Pole 415VAC,50Hz, coil voltage-230V, le AC 3: 32A, make-Siemens Complete.
S&F in replacement Contactor 3 Pole 415VAC,50Hz, coil voltage-230V, MO 25, 45A all as specified & directed.
S&F in replacement CT having ratio 100/5, class 1.0, 50Hz , complete all as directed.
S&F in replacement CT having ratio 200/5, class 1.0, 50Hz, complete all as specfied and as directed.
S&F in replacement standard duty can-type Capacitor 5 Kvar conforms to IS- 13340 complete all as specified & directed.
S&F in replacement Flow Switch in the chilled water line conforing to specification as per existing, complete all as specified & directed.
S&F in replacement 4 pole MPCB with DoL starter suitable for 5 HP motor,standard breaking capacity with toggle handle fixing on rail conforms to IEC 60947-1, all as specified & directed.
S&F in replacement 4 pole MPCB with DoL starter suitable for 3 HP motor,standard breaking capacity with toggle handle fixing on rail conforms to IEC 60947-1, all as specified & directed.
M & L for Rewinding of pump motor 415 Volt 3 phase 7.5 HP after disconnecting electric cable and eath lead, suction and delivery pipes, shifting to work shop, dismantling the motor assembly and removing the burnt out copper winding of stator and Rotor cleaning the stator slots and core assembly, rewinding to stator and rotor with suitable gauge super enamelled copper wire with insulating papers and insulation cloths, varnishing the winding and baking heating for achieving the required insulation resistance, re-assembling the motor and testing complete, incl transporting back to site and fixing motor to its original place, reconnecting electric cable and earth leads etc testing and commissioning complete in all respect all as specified and as directed by Engr-in-charge for the following capacity: - Note:- The U/S rewinding after opening of motor will be cut down if front of AGE E/M. If same motor burnt out by any defect within two years i.e. within defect liability period, the contractor will be bound to rewind the same free of cost and no extra amount will be paid to the contractor.
All as above Item No 88 but cap 10 HP
All as above Item No 88 but cap 03 HP
All as above Item No 88 but cap 40 HP
M&L for opening pump set split case monoblock type coupled to electric motor of capacity 5 HP, make Kirloskar Compton from motor coupling after isolating the electric and earth lead connections opening the pump set for repair/overhauling & proper alignment of shaft etc including replacing the items with new items given vide item below, reassemblying the pumpset greasing connecting, testing and commissioning complete including necessary Lathe works, complete all as specified and as directed. Note :- Supply only spare parts for up to 5 HP pumps set for replacing vide item above as follows:-
Supply only pump shaft sleeve
Supply only key for main shaft
Supply only check nut
Supply only water seal
Supply only pump Shaft
Supply ball/roller bearing complete
M&L for Dismantling the Condensor unit of Package type AC Plant of any capacity , descaling the copper tubing by using appropriate method as required with appropriate quality of descaling solution including replacement of gasket , assembling , testing complete all sa directed by Engr in Charge.
M & L for replacement of Spray nozzles for cooling tower of Size 20 mm dia complete all as specified and directed by Engr in Charge.
S&F in Replacement of Indicator Lamp Type E-8 (Neon lamps), complete all as specfied and as directed.
S&F in Replacement of water pressure gauge range 0-150Kg/cm2 or 0-400 Lb/in2 ISI Mark, complete all as specfied and as directed.
S&F in Replacement ofContactor type NC-1-40 Coil voltage 220-240 Volt CE suitable for 2x52 TR Central type AC Plant complete all as specified and directed by Engr in Charge., complete all as specified and directed by Engr in Charge.
M & L for Reprograming / redownloaded the Software for automation/running hours for Compressor of central type AC Plant capacity 30 TR installed at 3001 Sqn, Soft Ware installed as per Voltas Company norms by the Votas Company soft ware Engineer including testing commissioning, complete all as specified and directed by Engr in Charge.
M&L for in relapcement of earthing complete with galvanized steel earth plate electrode 600mm x 600mm x 6.30 mm thick buried directly in ground (earth pit not less than 2.25 meters deep below normal ground level) with top edge of plate not less than 1.5 meter deep below normal ground level connected to galvanized earth strip of size 25 x 4mm, 7.5m long means of bolts, nuts, check nuts and washers of galvanized iron or steel all as shown in electrical plate No - 3 of SSR part I 2009 connecting to earthing test point and testing on completion with and including PCC pit in mix 1:3:6 type c1 with RCC 1:2:4 type B-1, 40mm thick cover reinforced with 6mm dia MS bars 3 Nos both ways with lifting book made out of 6mm dia bar, watering arrangement with funnel and wire mesh and 20mm bore light grade GI watering pipe, common salt and charcoal filling, necessary excavation and earth work, complete all as directed.
Supply and laying in trenches/fixing on wall/pole,jointing and testing electric under ground LT XLPE cable 16 Sqmm 4 Core PVC insulated armoured heavy duty aluminium conductor cable 1100 volts grade in trenches, ducts, pipe on walls poles complete all as specified and directed.
M&L Replacement of Rotational moulded Polythylene water storage tanks 3 layers white colour (Cylindrical Vertical with closed top) hoisted and fixed in position of Capacity 5000 Litres, all as specified and directed by Engr in Charge.
S&F in Replacement of galvanised Iron Strip 25x4 mm with saddles and fixing screws etc complete all as specified and directed.
S&F in Replacement of Indoor/Outdoor typr Thermo/Hygrometer tripple display ( Temp,Humidity & Time ) including Battery 1.5 Volt ISI Mark, all as specified and directed by Engr in Charge.
M&L Excavation in trenches not exceeding 1.5 Mtr wide and not exceeding 1.5 Mtr in deep for foundation of poles/stays/cables/Pipe lines etc and getting out in soft/loose soil complete all as specified and as directed by Engineer-in-Charge.
M&L Returning, filling in including spreading, leveling, watering and well ramming in layers each not exceeding 25 cm thickness complete all as specified and as directed by Engineer-in-Charge.
M&L Removing surplus soil to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified and as directed by Engineer-in-Charge.
M&L Fazilka sand as in sand cushioning to under ground cable including punning down all as directed at site, complete all as specfied and as directed.
M&L in replacementbrick protection cover to electric cable with class 'B' bricks laid dry and flat abutting each other with gap between adjascent not exceeding 10mm, complete all as specfied and as directed.
S&F in Replacement of Synthetic Insulating Mat for Electrical Instrument of size 2mx1mx2mm, all as specified & directed.
S&F in replacement Sheet metal supply/return air duct made as per IS -655 of the following sizes of GI Sheet reolacing with existing duct in Central/Package AC room:-
24 Gauge galvanised Sheet steel
22 Gauge galvanised Sheet steel
S&F in Replacement of Sensor (automatic control for Compressor) Suitable for Central type AC Plants chilled water System complete all as specified and directed by Engr in Charge.
Supply and fix in replacement of Strip Heater of capacity 3 KW with ISI Marked including all electical connection complete all as specified and directed by Engr in charge.
S&F in Replacement ofhumidifier of rating 12KW heating element with all necessary connections including feeding supply from feeder box to humidifier by using copper control cable of 4sqmm 4core with GI pipe of Suitable dia. as per required all as specified and directed by Engr in Charge
S&F in Replacement of aluminium cable and laying of copper control cable of 4 sqmm 4 core all as specified and directed by Engr in Charge, all as specified & directed.
S&F in Replacement of aluminium cable and laying of copper control cable of 6 sqmm 4 core all as specified and directed by Engr in Charge.
S&F in Replacement of aluminium cable and laying of copper control aluminium cable & Supply and fix copper control cable of 10 sqmm 4 core all as specified and directed by Engr in Charg.
Supply and fix humidity Controller to maintain humidity within 50% + 5% for Central type AC Plant with all acessories complete all as specified and directed by Engr in charge.
Supplying ,laying in Replacement of MS PIpe given in sch, testing and commissioning of condensor water pipes of MS class 'Heavy grade B'as per IS-1239 inside building including necessary clamps , vibration isolators and fittings such as bends , tees etc but excluding strainer and gauges etc adequately supported on rigid supports including necessary welding works complete all as specified and directed , of following sizes :-
125 mm dia
65 mm dia
50 mm dia
M&L for repair of condenser and fixing of leakage by testing leakage by using CO2 gas ,rectifying the leakage all as specified and directed by engr-in-charge.
S&F in Replacement of DDC Panel PCB and supply and fix new factory sealed DDC Panel PCB with complete per existing make and model with complete rewiring and acessories all as specified and directed by engr-in-charge of any capacity of Pakage type AC Plant, complete all as specified and directed.
S&F in Replacement of Existing Board , Installation and Commissioning of LED Name board of (MES - 30 TR CAP CENTRAL AC PLANT 3001 MES AUDITORIUM 52 TR CAP CENTRAL AC PLANT ) with engineers monogram of ACP sheet for board and background colour is blue and LED acrylic letters in white colour and size of board 8`x 4`incuding Material and labour for supports frame / clamp and back plate fabricated from MS square pipe of size 50x50mm including nuts , bolts washers, welding bending cold or hot drilling holes for bolt in any shape of size as indicated or directed and inclusive of one primer coat , one under coat and one finishing of coat of paint complete all as specified and directed. Including cement concrete 1:3:6 type C-1 (using 20 mm graded stone aggregate) as in coping etc complete all as specified and directed.
M&L for descaling of cooling towers using descaling solution cleaning with brush pressure pump and complete washing of all tube and reassembling the condenser including replacement the gasket nut bolt complete all as specified and as directed by Engr in Charge.
M&L for replacement of 5/5.5 TR scroll type compressor including dism. The old from unit and then new compeletly with reharging the refrigrant suitable all as directed by Engr in Charge
M&L for replacement of 8.5/8.75 TR scroll type compressor including dism. The old from unit and then new compeletly with reharging the refrigrant suitable all as directed by Engr in Charge.
S&F in Replacement of Sprinkler and sprinklers blade and distribution pipe made for cooling towers of any capacity and size suitable size all as specified and directed by engr-in-charge.
S&F in Replacement off dryer assy including testing of leakage of pipes connecting to it all as directed by Engr in Charge.
S&F in Replacement of for blade assy. For cooling tower up to 52 TR AC plant all as directed by Engr in Charge .
S&F in Replacement of solenoid valve of upto 30TR capacity all as directed by Engr in Charge .
S&F in Replacement of 18mm thickness of Thermal insulation on ducts using dosed cell, anti-microbial class 'O’ Nitrile Rubber Elastomeric insulation Thermal Conductivity of 0,035 W/mK at 20 degree Celsius mean temperature and Mu > or = 10000 to be applied on ducts using manufacturers' recommended rubber-based Adhesive in a blend of solvents, complete as required.
S&F in Replacement of display unit with card having numerical control system for package type AC plant including blower unit ,condensor unit,compressor ON/OF and start/stop & settimg push button all as specified and directed by Engineer-in-Charge.
S&F in Replacement of 4 pole Isolator conforms to IEC60947-3.50 Hz,Rating 63 Amps Operating Voltage 240 V/415V, complete all as specified and directed by Eng-in-Charge.
S&F in Replacement of 4 pole Isolator conforms to IEC60947-3.50 Hz,Rating 40 Amps Operating Voltage 240 V/415V, complete all as specified and directed by Eng-in-Charge.
Supply and fix n replacement of MCB TPN Ç'curve,50 Hz Rating 63 Amps. 10 KA, Operating Voltage 240V/415V, complete all as specified and directed by Eng-in-Charge.
Supply and fix n replacement of MCB TPN Ç'curve,50 Hz Rating 40 Amps. 10 KA, Operating Voltage 240V/415V, all as specified and directed by Engr-in-Charge.
M&L for instruction Board how to operate AC Plant installation adn safety precaution writing in Hindi or Punjabi on practical board 30mm thick of size 1.5m x2.5 m with suitable aluminium framing complete all as specified and as directed. Note. Writting notes safety instruction will be given by the concern JE/AGE E/M, all as specified and directed.
M&L for CPVC pipe of dia 25 /40mm with all fittings complete all as specified and directed.
Supply fix and test Cable tray perforated of 150 mm width, 50 mm height and of 14 Gauge powder coated including coupler plate, bends, angle iron 40x 40x 5 mm size at suitable distance for support with wall etc , complete all as specified and directed.
M&L for dismantling the Motor and pump from the channels and all electrical connection, repair the foundation / plinth of pump and motor with PCC 1:3:6 , bearing, replace the UNSV channel with new channels , nut bolts, cut to ordinary length as per sample and and reassembling the motor pump and connection of all electrical accessories all as specified and directed by Engr-in-Charge.
S&F in Replacement of aluminium sheet 1 mm thick as in cladding on duct with and including all necessary fittings as required, complete all as specified and as directed.
S&F in replacement Air Filters Pre type having filteration efficiency of 10 micron and fine filter for 5 micron of Size 610 x 610 x 50 mm as per latest IS standard of aluminium frame all as specified and directed.
M&L for Dismantling and taking down of insulation of wall , floor and roof complete with glass wool, vapor varier , chiken wire mesh , plaster etc complete all as specified and directed by Engr in Charge.
M&L Dismantling and taking down of insulation of Chiller and hot MS Pipe complete with resin bonded glass wool,PUF slab, bituminuous compound, GI cladding with GI sheet etc of size upto 150mm dia. complete all as specified and directed by Engr in Charge.
Supply & fixing in replacement of insulation of Chiller and hot MS Pipe complete with resin bonded glass wool,PUF slab, bituminuous compound, GI cladding with GI sheet etc of size upto 100mm dia. complete all as specified and directed by Engr in Charge.
Supply & fixing in replacement of insulation of Chiller and hot MS Pipe complete with resin bonded glass wool,PUF slab, bituminuous compound, GI cladding with GI sheet etc of size 150mm dia. complete all as specified and directed by Engr in Charge.
Supply & fixing in replacement of insulation of Chiller unit of various capacity of ac plant Central plant complete with nitriole insulation 25 mm thick . complete all as specified and directed by Engr in Charge.
Supply & fixing in replacement of insulation of wall, floor and roof, 50 mm thick resin bonded glass wool insulation wrapped in Hussan cloth based vapor barrier and chicken wire mesh wrapped on insulation and finally covered with plaster of pairs 10 mm thick etc complete all as specified and directed by Engineer-in-Charge.
HOT WATER GENERATOR : M&L for overhauling of hot water generator of up to 32- 55 KW capactiy to checking heating element and if found unserviceable replacing the same as per direction of JE E/M and replacing of ON/OFF button and descaling of heating element including hot water tank and checkin the conditions of electric panel with control and relay to switch OFF and ON electric heater and all as specified a) Flow rate : 14.60 US GPM b) Inlet temperature of water : 40 deg celcius c) Outlet temperature of water: 60 deg celcius d) Working pressure: 100 PSIG Replacing of following spare parts is necesary (i) step controller, (ii) pressure gauge (iii) ball valve, (iv) pressure relief valve,(v) thermometer,(vi) low level cut out and auto vent (vii) DC Transformer (adopter) (viii) Displahy panel. and replacement of insulation of Generator shall be provided with 50mm thick resin bonded fiber glass wool cladded with 0.63mm thick aluminium sheet on MS frame welded to genrator body.
M & L for replacement of on-load Change Over of capacity 400A, 4 Pole 415 volts with suitable ms sheet enclosure as recommended by OEM , suitable for wall mounted including termination point for connection complete all as specified and directed. Note the cost shall be included for fixing of existing size 400 sqmm 3 .5 core aluminium conductor lt cable with lugs & thimbles made of Aluminium matrial incoming and out going.
R K GOYAL & COMPANY
M/s BHUPINDRA ENGINEERING WORKS
AP BUILDERS
Aman Enterprises
Singla Electricals
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .