Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹11.5 LAccepted-AOC | L1 | Accepted-AOC Lowest bidder | |
| 2 | L2₹11.6 L+₹14,865 (1.29%)Rejected-AOC 201 GANAPATI SANKUL AGASHIVNAGAR MALKAPUR KARAD SATARA MAHARASHTRA 415539 | SATARA | MAHARASHTRA | 415539 | L2 | Rejected-AOC Other than lowest bidder | |
| 3 | L3₹12.9 L+₹1.4 L (12.5%)Rejected-AOC | L3 | Rejected-AOC Other than lowest bidder | |
| 4 | L4₹13.0 L+₹1.5 L (13.4%)Rejected-AOC | L4 | Rejected-AOC Other than lowest bidder | |
| 5 | L5₹15.9 L+₹4.4 L (38.6%)Rejected-AOC | L5 | Rejected-AOC Other than lowest bidder |
Tender Value
₹12.0 L
EMD Value
₹24,100
Closing Date
13 Jun 2023, 6:00 pmClosed
COL S PRADEEP
Military Engineer Services, HQ Commander Works Engineer Jammu, PIN-900172
SPL REPAIR TO TRANSFORMER 33/11KV, 3.15 MVA INSTALLED AT 166 MH UNDER THE PROVN OF PARA 31(D) AND 38(C) OF DWP 2020 AT MIL STN JAMMU UNDER GE SATWARI
2023_MES_596337_1
CWE/JP-04/2023-24
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE SATWARI
Please refer Tender documents.
9 documents required · 9 mandatory
₹500
GE SATWARI
₹24,100
Yes
19 Oct 2023
18 May 2023
15 Jun 2023
18 May 2023
13 Jun 2023
1 Jun 2023
Amount
Disconnecting electrical connections, LA and taking down, transformers E 33/11KV, 3.15 MVA of make Powerware, outdoor type from PCC Platform by means of Crane of capacity 10 ton and keeping it on flat top truck. Transporting the same over flat top truck from 166 MH sub station to workshop and factory for repair/maint. Bringing out the same over flat top truck from workshop to 166 MH 33KV Sub Stn Yard after repair, Hoisting/lifting with the help of carne of capacity 10 ton and keeping it over PCC platform, connecting input output cables, earthing leads, LAS etc complete & testing of transformer as directed by Engineer-in-Charge. Note: If any damage to transformer/OH line/cables occur during handling, transportation or during hoisting/lifting, the same will be rectified by the contractor without any extra cost to the department.
Labor for transformer Opening the top cover of transformer capacity 33KV/11KV/3.15MVA, of any make, model & type out door, draining out oil, dismantling of cover & taking out damaged coils, fitting new coils, Paper, connection HT and LT Side,after removing all moisture content by keeping it in oven for a suitable period, refitting the covers after cleaning/treatment of oil, making all electrical connections fixing sundry items & reassembling after repairs to the entire satisfaction of the Engr-in-Charge, testing after repair complete all as specified. Note: New coils with allied material shall be measured and paid separately. However the rate quoted under Col 6 are inclusive for providing sundry items i.e. bolts, nut & washers etc.
M&L for winding of HT coils of transformers with super enamelled copper winding strip of appropriate gauge along with allied insulating material and sundry items, complete all as specified & directed by Engr-in-Charge.
Reconditioning of LV coils by replacing worn out insulation including supplying and providing new insulation, making the LV coils to its original shape and fixing to its position after insulation and sundry items complete all as specified and directed by Engr-in-Charge.
Replacement of sheet gasket (for top cover) of transformers of 33KV/11KV/3.15MVA capacities including taking out existing sheet gasket, complete all as directed by Engr-in-Charge.
Filtration/dehydration of transformer oil for increasing dielectric strength not less than 60 KV, if the results below 60 KV the oil shall be replaced with new oil. Note: New oil required for toping oil levels or for replacement shall be measured and paid separately.
Supply and filling new transformer oil in transformers for toping up levels or for replacement of unfit oil (New oil shall be confirming to IS-335) Dielectric strength not less than 60 to 65 KV of 33KV/11KV/3.15MVA capacities complete all as directed by Engr-in-Charge.
M&L for breather assembly suitable for 33KV/11KV/3.15MVA including silica gel complete and including taking out existing unserviceable, all as directed by Engr-in-Charge.
Taking out existing worn out bush rod with accessories & replacement of HT bushes (11 KVA) with rod assembly complete of metallic alloy (brass gun metal) of suitable dia & length including nuts, washers, insulator, packing oil sealing bushes for transformer of 33KV/11KV/3.15MVA capacities, complete all as specified and directed by Engr-in-Charge.
Taking out existing worn out bush rod with accessories & replacement of HT bushes (33 KVA) with rod assembly complete of metallic alloy (brass gun metal) of suitable dia & length including nuts, washers, insulator, packing oil sealing bushes for transformer of 33KV/11KV/3.15MVA capacities, complete all as specified and directed by Engr-in-Charge.
Overhauling of OLTC of Transforer 33KV/11KV/3.15MVA capacity of any make, model & type out door, overhauling of OLTC of transformer all as specified and directed by Engr in charge.
Prakash Trading Corporation
BMMJ TRADERS AND ENGINEERS
M/S Shesh Paul Gupta
Harsh Electricals
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .