Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹13.3 LAccepted-AOC HIMACHAL BUILDING SHOP NO 10 CD BARFYWALA ROAD JUHU LANE ANDHERI W MUMBAI 400058 | MUMBAI SUBURBAN | MAHARASHTRA | 400058 | L1 | Accepted-AOC L1 | |
| 2 | L2₹13.7 L+₹32,748 (2.44%)Rejected-Finance 702 A1 SHREE PRASAD TAWADEWADI SHREE DATTAGURU PARK KUMBHARWADA URAN DIST RAIGAD MAHARASHTRA 400 702 | URAN | RAIGAD | MAHARASHTRA | 400702 | L2 | Rejected-Finance REJECTED BEING NOT LOWEST | |
| 3 | L3₹16.4 L+₹3.0 L (22.4%)Rejected-Finance | L3 | Rejected-Finance REJECTED BEING NOT LOWEST | |
| 4 | L4₹17.1 L+₹3.7 L (27.7%)Rejected-Finance 1 A BASEMENT 30 31 RAJA HOUSE NEHRU PALACE NEW DELHI 110 019 | SOUTH EAST | DELHI | 110019 | L4 | Rejected-Finance REJECTED BEING NOT LOWEST | |
| 5 | L5₹17.3 L+₹3.9 L (29.4%)Rejected-Finance | L5 | Rejected-Finance REJECTED BEING NOT LOWEST |
| Sl No | Description | Qty | Unit | Sagar Electricals L2 | ELECTRO ASSOCIATES L3 | MONA GENERATOR SEVICES PVT. LTD. L4 | AIRDOT ENGINEERING L5 | M/s PIONEER CONTRACTORS L1 |
|---|---|---|---|---|---|---|---|---|
| 1.00 | Supply, installation, testing and commissioning of copper wounded transformer step up/step down outdoor type capacity 250 KVA, 22 KV, 3 Phase, ISS : 1080(2014) Part-I & Latest, E.E. Level -II, Amendment No 4, 50 C/S oil immersed, Natuarally cooled, out door type step down Transformer having a No load Voltage Ratio 22000/433V, Vector group DYN 11 with plus minus 2.5 plus minus 5% of Circuit Tappling as under taken out on the HT side and connected to 22KV off circuit Tapping switch, HT winding connected in Delta & LT winding connected in Star and the Neutral brought out & connected to a Separate terminal for earthing with outdoor open porcelain bushing on HV side & cable box on LV side with the temperature rise not exceeding 40 degree centrigrade by thermometer in oil and 45 degree centrigrade by resistance & Ambient temp 40 degree centrigrade with first filling of Oil with following :-
(i) Fitting and accessories :- (a) First fill on Trnasformer oil (b) 22 KV of circuit tapping switch (c) Oil conservator tank with drain plug and filling cap (d) Silica gel dehydrating breather charged with sillica gel (e) Oil level gauge. (f) Oil filter valve (g) Oil drain valve. (h) Thermometer pocket with thermometer (OTI). (j) DIagram and rating plate (k) Two earthing aggrangements (i) lefting lugs (m) four Bidirectional plain roller (n) Air vent plug (o) Explosion vent (p) Barebushing on HV side. (q) Cable box on LV side (r) colling radiators. (s) C. I rollers (t) Additional neutral terminal brought out side the LV cable box earthing
(ii) Extra fittings :- (a) Oil temp Indicator (OTI) (b) Inspection cover.
(iii) Inspection :- Transformer factory inspection carried out by department and test certificate will be furnished for all routine test inclusding oil test. | 1 | Each | 11,40,000 ₹11,40,000 | 12,70,000 ₹12,70,000 | 13,50,661 ₹13,50,661 | 13,40,000 ₹13,40,000 | 11,07,000 ₹11,07,000 Lowest |
| 2.00 | M & L in replacement for earthing complete with copper earth plate electrode 600 x 600 x 3.15mm buried directly in ground with top edge of the plate not less than 1.5mtrs below normal ground level and connected to earth test point by means of copper strip 20 x 3 mm all as specified and show in electric plate No 3 of MES SSR Part-I 2009 including earthwork, PCC Chamber CI cover, protection and waterring pipe, funnel, mesh etc all as required at site and alll as directed note (i) 7.5 M Copper strip is deemed to be cluded in quoted rates beyond 7.5 RM shall be measured and paid separately (2) Earth resistance of earth pit should be less than 0.5 Ohms. On testing after completion if desired earth resistance is not obtained, the earthing will be redone at no extra cost (3) Rate qouted by the tenderer is deemed to be included salt & charcoal upto & above 450mm top of copper plate. | 4 | Each | 16,500 ₹66,000 | 20,000 ₹80,000 | 22,356 ₹89,424 | 16,000 ₹64,000 Lowest | 16,200 ₹64,800 |
| 3.00 | M & L for plateform for transformer of size 2000mm x 1500mm x 1200mm with brick masonry construction in cement mortar 1:4, PCC (1:4:8) type D-2, 150mm thick as in foundation, PCC (1:2:4) type B-1, 40mm thick as in floor over sub base PCC (1:3:6) type D-2, 75mm thick, brick masonry step on one side to made access to the top of platform including excavation & earth work in any type of soil including 15mm plastering to brick masonry in CM 1:4 and applying two coats white wash on plasterd surface completed as as specified and as directed by Engr-in-Charge. | 1 | Each Job | 60,003 ₹60,003 | 70,000 ₹70,000 | 86,754 ₹86,754 | 20,000 ₹20,000 | 18,000 ₹18,000 Lowest |
| 4.00 | Excavation in trenches, not exceeding 1.5m wide and n.exc 10 sqm on plan and n.exc 1.5m depth and getting out in soft/loose soil complete all as specified and as directed by Engr-in-Charge. | 44 | Cum | 220 ₹9,680 | 349 ₹15,356 | 189 ₹8,316 | 200 ₹8,800 | 180 ₹7,920 Lowest |
| 5.00 | Returning filling in including spreading levelling, watering & well ramming in layers not exceeing 25cm thick in soil complete all as specified and as directed by Engr-in-Charge. | 39 | Cum | 180 ₹7,020 | 55 ₹2,145 | 84 ₹3,276 | 100 ₹3,900 | 45 ₹1,755 Lowest |
| 6.00 | Removing excavated soil to a distance n. exc 50m and deposting where directed at a level n exc 1.5 metre above the starting point complete all as specified and as directed by Engr-in-Charge. | 5 | Cum | 150 ₹750 | 80 ₹400 | 43 ₹215 Lowest | 100 ₹500 | 54 ₹270 |
| 7.00 | Suppy, spreading in trenches fine dry river sand for cable protection and ramming/punning down by hand complete all as specified and as directed by Engr-in-Charge.
Note :- Punned thickness shall be measured & paid. | 13 | Cum | 1,000 ₹13,000 | 1,800 ₹23,400 | 1,202 ₹15,626 | 4,300 ₹55,900 | 900 ₹11,700 Lowest |
| 8.00 | Supply and laying un reinforced precast concrete cable cover class LV, type-I, flat size 250mm x 150mm x 40mm laid in trenches complete all as specified and as directed by Engr-in-Charge. | 1,093 | Each | 18 ₹19,674 Lowest | 29 ₹31,697 | 18 ₹19,674 Lowest | 37 ₹40,441 | 18 ₹19,674 Lowest |
| 9.00 | Supply, laying and testing in replacement of cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy durty) 1100 Volts grade with stranded aluminium conductor of size 240 sq mm 3.5 core. | 45 | RM | 600 ₹27,000 Lowest | 1,500 ₹67,500 | 1,478 ₹66,510 | 1,900 ₹85,500 | 1,152 ₹51,840 |
| 10.00 | Supply, laying and testing in replacement of cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy durty) 1100 Volts grade with stranded aluminium conductor of size 70 sq mm 3.5 core. | 100 | RM | 210 ₹21,000 Lowest | 555 ₹55,500 | 490 ₹49,000 | 780 ₹78,000 | 396 ₹39,600 |
Tender Value
₹17.2 L
EMD Value
₹34,340
Closing Date
16 Jun 2025, 6:00 pmClosed
COL S P SINGH
CWE AF LOHEGAON, PUNE - 411032
SPL REPAIR REPLACEMENT OF VINTAGE TRANSFORMER AT SITE R AT AF STN THANE
2025_MES_709206_1
82698/E8
Open Tender
Civil Works
Item Rate
180 days
GE AF THANE
Please refer Tender documents.
6 documents required · 6 mandatory
₹500
GE AF THANE
₹34,340
Yes
28 Aug 2025
20 May 2025
23 Jun 2025
20 May 2025
16 Jun 2025
4 Jun 2025
Amount
Supply, installation, testing and commissioning of copper wounded transformer step up/step down outdoor type capacity 250 KVA, 22 KV, 3 Phase, ISS : 1080(2014) Part-I & Latest, E.E. Level -II, Amendment No 4, 50 C/S oil immersed, Natuarally cooled, out door type step down Transformer having a No load Voltage Ratio 22000/433V, Vector group DYN 11 with plus minus 2.5 plus minus 5% of Circuit Tappling as under taken out on the HT side and connected to 22KV off circuit Tapping switch, HT winding connected in Delta & LT winding connected in Star and the Neutral brought out & connected to a Separate terminal for earthing with outdoor open porcelain bushing on HV side & cable box on LV side with the temperature rise not exceeding 40 degree centrigrade by thermometer in oil and 45 degree centrigrade by resistance & Ambient temp 40 degree centrigrade with first filling of Oil with following :- (i) Fitting and accessories :- (a) First fill on Trnasformer oil (b) 22 KV of circuit tapping switch (c) Oil conservator tank with drain plug and filling cap (d) Silica gel dehydrating breather charged with sillica gel (e) Oil level gauge. (f) Oil filter valve (g) Oil drain valve. (h) Thermometer pocket with thermometer (OTI). (j) DIagram and rating plate (k) Two earthing aggrangements (i) lefting lugs (m) four Bidirectional plain roller (n) Air vent plug (o) Explosion vent (p) Barebushing on HV side. (q) Cable box on LV side (r) colling radiators. (s) C. I rollers (t) Additional neutral terminal brought out side the LV cable box earthing (ii) Extra fittings :- (a) Oil temp Indicator (OTI) (b) Inspection cover. (iii) Inspection :- Transformer factory inspection carried out by department and test certificate will be furnished for all routine test inclusding oil test.
M & L in replacement for earthing complete with copper earth plate electrode 600 x 600 x 3.15mm buried directly in ground with top edge of the plate not less than 1.5mtrs below normal ground level and connected to earth test point by means of copper strip 20 x 3 mm all as specified and show in electric plate No 3 of MES SSR Part-I 2009 including earthwork, PCC Chamber CI cover, protection and waterring pipe, funnel, mesh etc all as required at site and alll as directed note (i) 7.5 M Copper strip is deemed to be cluded in quoted rates beyond 7.5 RM shall be measured and paid separately (2) Earth resistance of earth pit should be less than 0.5 Ohms. On testing after completion if desired earth resistance is not obtained, the earthing will be redone at no extra cost (3) Rate qouted by the tenderer is deemed to be included salt & charcoal upto & above 450mm top of copper plate.
M & L for plateform for transformer of size 2000mm x 1500mm x 1200mm with brick masonry construction in cement mortar 1:4, PCC (1:4:8) type D-2, 150mm thick as in foundation, PCC (1:2:4) type B-1, 40mm thick as in floor over sub base PCC (1:3:6) type D-2, 75mm thick, brick masonry step on one side to made access to the top of platform including excavation & earth work in any type of soil including 15mm plastering to brick masonry in CM 1:4 and applying two coats white wash on plasterd surface completed as as specified and as directed by Engr-in-Charge.
Excavation in trenches, not exceeding 1.5m wide and n.exc 10 sqm on plan and n.exc 1.5m depth and getting out in soft/loose soil complete all as specified and as directed by Engr-in-Charge.
Returning filling in including spreading levelling, watering & well ramming in layers not exceeing 25cm thick in soil complete all as specified and as directed by Engr-in-Charge.
Removing excavated soil to a distance n. exc 50m and deposting where directed at a level n exc 1.5 metre above the starting point complete all as specified and as directed by Engr-in-Charge.
Suppy, spreading in trenches fine dry river sand for cable protection and ramming/punning down by hand complete all as specified and as directed by Engr-in-Charge. Note :- Punned thickness shall be measured & paid.
Supply and laying un reinforced precast concrete cable cover class LV, type-I, flat size 250mm x 150mm x 40mm laid in trenches complete all as specified and as directed by Engr-in-Charge.
Supply, laying and testing in replacement of cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy durty) 1100 Volts grade with stranded aluminium conductor of size 240 sq mm 3.5 core.
Supply, laying and testing in replacement of cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy durty) 1100 Volts grade with stranded aluminium conductor of size 70 sq mm 3.5 core.
Supply, laying and testing in replacement of cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy durty) 1100 Volts grade with stranded aluminium conductor of size 50 sq mm 3.5 core.
Sagar Electricals (BID ID -3317437)
ELECTRO ASSOCIATES (BID ID -3322659)
MONA GENERATOR SEVICES PVT. LTD. (BID ID -3324904)
AIRDOT ENGINEERING (BID ID -3317674)
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .