| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹12.8 CrAccepted-Finance | ₹12.8 Cr | L1 | Accepted-Finance OK |
| 2 | L2₹13.0 CrAccepted-Finance B402 SOMDUTT CHAMBERS 1 SMS INDIA PRIVATE LIMITED 5 BHIKAJI CAMA PLACE NEW DELHI 110066 SOUTH WEST DELHI DELHI 110066 | NEW DELHI | DELHI | 110066 | ₹13.0 Cr | L2 | Accepted-Finance OK |
| 3 | L3₹13.4 CrAccepted-Finance | ₹13.4 Cr | L3 | Accepted-Finance OK |
| 4 | L4₹13.7 CrAccepted-Finance | ₹13.7 Cr | L4 | Accepted-Finance OK |
| 5 | Rejected-Technical | - | - | Rejected-Technical Technically Disqualified |
Tender Value
₹10.4 Cr
EMD Value
₹21 L
Closing Date
16 Feb 2021, 5:00 pmClosed
SE Contracts
Shakti Bhawan Sector 6 Panchkula
Creation of 132kV cum 66kV S/Stn. Nanakpur along with Creation of 2no. 66kV line bays and providing of one no. additional 12.5/16MVA 66/11kV transformer (to be provided by HVPNL) at existing 220kV substation Pinjore
2020_HBC_152773_1
EPC-D 13 PD and C Dated 7.12.2020
Open Tender
Electrical Works
450 days
Nanakpur Panchkula
As per Tender Documents
8 documents required · 8 mandatory
₹11,800
₹21 L
Yes
29 Nov 2021
8 Dec 2020
2 Mar 2021
8 Dec 2020
16 Feb 2021
8 Dec 2020
1) 12.5/16MVA, 66/11kV T/Fs (to be provided by HVPNL)
2) 10/16 MVA 132/11kV T/Fs (to be shifted from 220kV s/stn. Pinjore)
3a) Time synchronization equipment for 66KV
3b) Time synchronization equipment for 132KV
4) 66 kV SF-6 Breaker along with 20% extra SF-6 Gas
5) 132 kV SF-6 Breaker along with 20% extra SF-6 Gas (3No. to be shifted from 220kV s/stn. Pinjore)
6) 66 kV Isolator with E/Switch
7) 66 kV Isolator without E/Switch
8) 132 kV Isolator with E/Switch
9) 132 kV Isolator without E/Switch
10) 132 Kv Bus post Insulators
11) 66 kV Surge Arrestor
12) 132 kV Surge Arrestor to be shifted from 220kV s/stn. Pinjore
13) 66 kV CTs for Line & Bus Coupler (600-300-150/1-1-1A)
14) 132 kV CTs for Line (600-300-150/1-1-1A)
15) 66 kV T/F CT (300-200-150/0.577-1-1A)
16) 132 kV T/F CT (250-150-100/0.577-1-1-1A)
17) 66 kV CVT for line
18) 132 kV CVT for line
19) 66 kV NCT (300-200-150/1A)
20) 132 kV NCT (250-150-100/1)
21) 11 kV NCT for 66/11kV (1200-900/5A)
22) 11 kV NCT for 132/11kV (1200-900/5A)
24) 11 kV 13 Panel Board (1250A) one SEM on each T/F I/C Panel (including one no. bus sectionalizer panel)
25 a) 66kV C&R Panels :- Bus Coupler Protection and Circuit Breaker Panel (Without Auto Reclose)
25 b) 66kV C&R Panels: Line Protection and Circuit Breaker Panel (Without Auto Reclose)
25c) 66kV C&R Panels: Transformer Protection and Circuit Breaker Panel (Without Auto Reclose)
26 a) 132 kV C&R Panels: Line Protection and Circuit Breaker Panel (Without Auto Reclose)
26 b) 132 kV C&R Panels:- Transformer Protection and Circuit Breaker Panel (Without Auto Reclose)
27) 4600KVAR 11kV Automatically Switched Capacitor Bank along with allied equipment
28) 220V 200AH Battery (VRLA)
29) a) 220 V 200 AH Battery charger
b) D.C.D.B.
30) 415 V LT AC Distribution Board 300 A
31) Mechanical Operated hoist as per clause 1.2.1(m) section-1
32) 11/0.4 kV Station T/F 200 KVA
33a) 1.1 kV Copper Control Cable unarmoured for 66kV & 132kV bays of size 7Cx4mm2, 4Cx4mm2, 2Cx4mm2,2Cx6mm2, 3Cx2.5mm2, 16Cx2.5mm2, 10Cx2.5mm2 & 7Cx2.5mm2 including junction box etc. refer Section-6 of copper & control cable & Section-7 for switchyard erection.
33b) Stainless steel MK (200 TB)
33 c) Stainless steel MK (250 TB)
34) 11 kV Power Cable XLPE 1C x1000mm2 for T/F to 11kV incomer with termination kit for both ends.
35) 11 kV Power Cable XLPE 3C x 185sq mm for Capacitor Bank with termination kit for both ends
36) 11 kV Power Cable XLPE 3C x 50 sq mm for station T/F with termination kit for both ends.
37) 650/1100 Volts 3.5 core 240 mm2 aluminium power cable from Aux. T/F to ACDB
38) 650/1100 Volt 3.5 core 70 mm2 aluminium cable for oil filtration set.
39) 650/1100 Volt 4core 16mm2 unarmoured with copper power cable for MLDB and other cable required as per contract for 66kV bays.
40) Earthing Mat Material. The earth mat will be designed/ quoted for soil resistivity of 50ohm m In case soil resistivity is more than 50ohmm then the earth mat will be designed for actual soil resistivity. The payment of extra material to be used for earth mat shall be made on pro rata basis. The approximate area of earth mat to be laid is given in the corresponding columns of the substations. However, item will remain a Lot item. Approxtmate area 5100m2
41) Fire Fighting equipments as per section-6 i) 22.5 Kg Capacity FE CO2 type, Trolley Mounted
ii) 25 Kg Capacity FE DCP type, Trolley Mounted
iii) DCP 9 Kg Capacity, Wall mounted
iv) FE CO2 6.5 Kg Capacity, Wall mounted
v) DCP 6 Kg Capacity, Wall mounted
vi) Foam Type 9 Litre Capacity, Wall mounted
vii) Water CO2 9 Litre, Wall mounted
viii) Fire Buckets (12 Nos. with stand in one set)
42) Complete lightning of control room building, switch yard area, road and street as per section-7 of the specification. a) Supply and installation of 2 fittings of 240W LED lamps with all accessories for Complete lighting of outdoor Switch yard area as per clause 16.0 of section 7 of the specifications.
b) Supply and installation of 35W LED tube on tubular steel poles along with the boundary wall at a distance of 30 meter as per as per clause 16.0 of section 7 of the specification
c) Complete lighting of road and street by providing 90W LED lamps on tubular steel poles at a distance of 15meter along the roads and streets as per as per clause 16.0 of section 7 of the specification.
d) Supply and installation of post top lantern 40W LED Lamps with all complete accessories at the entrance gate of sub-station.
e) Supply and installation of 40W LED Lamps with all complete accessories on corners of control room building.
43) Complete Substation automation system of 132/11kV & 66/11kV substations including hardware (along with transducers) for 4 No. 66kV present bays and software (for present bays as well as 1 No. future T/F bays) & 132 /11kV substations including hardware (along with transducers) for 3 No. 132kV present bays along with associated equipment for the bays (bay as defined in the technical specification, sec-sub-station automation system) as per technical specification Note: signals from protection relays in 11kV incomer would also be wired to substation automation system (SAS)
44 a) High wall type split AC unit of 2 Ton capacity for SCADA room (as per technical specification)
44b) High wall type split AC unit of 2 Ton capacity for C&R panels in electrical room.
1) Bolted type 11kV Single tension string assembly with 3 numbers Anti FOG type disc insulators (E&M strength 9000 kg) per string with all hardware accessories including ball & socket connections and tension clamp sets suitable for twin zebra conductor. Alternatively the bidder may quote silicon polymer composite insulator string in place of Disc Insulators (type of insulator whether disc or polymer insulator to be identified at the time of bidding and quoted accordingly which will not be altered at later stage by the bidder).
2) 66 kV Bolted type single tension string assembly with 6 numbers Anti FOG type disc insulators (E&M strength 9000 kg) per string with all hardware accessories including ball & socket connection and tension clamp set suitable for single zebra conductor. Alternatively the bidder may quote silicon polymer composite insulator string in place of Disc Insulators (type of insulator whether disc or polymer insulator to be identified at the time of bidding and quoted accordingly which will not be altered at later stage by the bidder).
3) 66 kV bolted type single suspension string assembly with 5 numbers Anti FOG type disc insulators (E&M strength 9000 kg) per string with all hardware accessories including ball & socket connections and suspension clamp set suitable for single zebra conductor. Alternatively the bidder may quote silicon polymer composite insulator string in place of Disc Insulators (type of insulator whether disc or polymer insulator to be identified at the time of bidding and quoted accordingly which will not be altered at later stage by the bidder).
4) 132 kV Bolted type single tension string assembly with 10 numbers Anti FOG type disc insulators (E&M strength 9000 kg) per string with all hardware accessories including ball & socket connection and tension clamp set suitable for single zebra conductor. Alternatively the bidder may quote silicon polymer composite insulator string in place of Disc Insulators (type of insulator whether disc or polymer insulator to be identified at the time of bidding and quoted accordingly which will not be altered at later stage by the bidder).
5) 132 kV bolted type single suspension string assembly with 9 numbers Anti FOG type disc insulators (E&M strength 9000 kg) per string with all hardware accessories including ball & socket connections and suspension clamp set suitable for single zebra conductor. Alternatively the bidder may quote silicon polymer composite insulator string in place of Disc Insulators (type of insulator whether disc or polymer insulator to be identified at the time of bidding and quoted accordingly which will not be altered at later stage by the bidder).
6) Boltless C-Type Wedge connectors matching with conductor size.
7) Copper lugs glands, PVC ferrules for control cabling.
8) Fibre cleats, Aluminium clamps, bolts, nuts, washers etc., for fixing control cables in trenches.
9) Galvanized iron perforated tray with side coupler plate bolts, nuts, washers and clamps etc. of size 75x25x2 mm, 150x25x2mm, 100x25x2mm etc. & G.I. Conduits of 50mm/100mm dia from equipment to main trench as per Section-7, Switchyard erection.
10) ACSR Zebra Conductor
11a) 7/3.15 GS Earthwire Lot ( to be supplied by HVPNL , item lying in DD store , panipat)
11b) Spacers for Twin zebra Conductor
12) U-bolt 20mm dia
Mandatory spares for hardware/ mechanical/ Electrical auxiliaries to be supplied. 10 % of the finally approved quantities for item mentioned from Sr. No. 64 to 68.
Item for associated structure work ‘Lattice type steel structure for 132kV cum 66kV Substation Nanakpur. Supply of material, preparation of fabrication drawing, galvanizing and delivery of lattice type steel structure for tower and beams for 66/11kV & 132/11KV switchyard fabricated from steel conforming to IS:2062 including nuts-bolts gusset plates foundation bolts and other accessories as per drawings supplied by the owner. A) Main S/Stn. tower and beam a) Tower type CT-4
b) Tower type CT-5
c) Tower type CT-6
d) Tower type CT-8
e) Beam type CB-6
f) Beam type CB-7
g) Tower type DT-2
h) Tower type DT-3
i) Beam type DB-2X
j) Tower type BT-1
k) Tower type BT-3
l) Tower type BT-6
m) Beam type BB-1
n) Beam type BB-2
B) Equipment Structure a) 66 kV CT Drg. No. HTD/ST-88R
b) 132 kV CT drg. No. HHW/ST-67
c) 66 kV NCT Drg. No.HTD/ST-145(if required )
d) 132 kV NCT (if required )
e) 66 kV CVT Drg. No. HHW/ST-66
f) 132 kV CVT drg. No. HHW/ST-67
g) 66 kV Surge Arrestor Drg. No. HTD/ST-89
h) 132 kV Surge Arrestor drg. No. HSW/ST-63R 9 No - to be shifted from 220kV s/stn. Pinjore)
i) 66 kV Isolator/L&E Drg. No. HTD/ST-87R
j) 132 kV Isolator/L&E/ drg. No. HTD/ST-90R
k) 132kV Bus Post Insulator drg.No.HTD/ST-144
l) i) 11 kV NCT Drg. HTD/ST-149( if combined structure used )
ii) 11 kV NCT Drg. HTD/ST-149( if combined structure used ) 1No. to be supplied by HVPNL, item lying in panipat store)
m) 11 kV NCT Drg. HTD/ST-88R( if required )
PLC Terminal (2 No. to be supplied by HVPNL, item lying in ballabgarh store)
PLC Terminal ( to be shifted from 220KV S/Stn Pinjore)
i) Wave Trap (630A) to be shifted from 220KV S/Stn Pinjore
ii) Wave Trap (400A) (to be supplied by HVPNL, item lying in ballabgarh store)
iii ) Wave Trap (400A)
LTU (to be shifted from 220KV S/Stn Pinjore)
48V Battery
Battery Charger (to be supplied by HVPNL, item lying in Sewah store)
HF cable
CIVIL WORKS for 132 cum 66KV S/Stn. Nanakpur 1 EARTH WORK 1.1) Earth filling with good earth (as per satisfaction of Executive Engineer/Civil Works Division), laying in layers (as per specification), dressing, including carriage, irrespective of lead, loading, unloading, watering and compaction in layers with roller including compensation of earth complete in all respect.
1.2) Earth work in cutting for re-routing of Barsati Nala & spreading of cut earth within sub-station or outside in layers (as per specification clause 3.5), dressing, including carriage, irrespective of lead, loading and unloading, watering and compaction in layers with roller within sub-station area including yard, roads, approach road etc. or disposal complete in all respect.
2. FOUNDATIONS: Design engineering, supply of labour, T&P, material and construction of RCC footings & pedestals etc. for steel gantry and equipment structures complete in all respects as per technical specifications including cost of excavation, concreting, cement, reinforcement steel, form work, grouting, holding down bolts, backfilling etc. and other items not mentioned herein but required for the completion of work. A. GANTRY TOWER i) BT-1
iii). BT-6
vii). CT-8
viii). DT-2
B EQUIPMENT 132kV side i) LA
ii) CVT
iii) CT
iv) Post Insulator
v) Isolator & L&E
vi) NCT
vii) CT(M)
viii) PT(M)
66KV side i) LA
ii) CVT
iii) CT
iv) Isolator & L&E
11KV SIDE i) NCT
3) BREAKER FOUNDATION: Design, engineering, supply of labour, material for construction of breaker foundations including all associated works such as PCC, RCC, structural steel, steel reinforcement, form work etc. or any other items not specifically mentioned herein but required for completion of work as per approved equipment(s) and technical specifications. i)132kV, SF-6 Breaker
ii) 66kV SF-6 Breaker
4. CAPACITOR BANK FOUNDATIONS: Design, Engg. & supply of labour, material & construction of foundations for following rating capacitor bank with capacitor unit, series Reactor & allied equipments , including chain link fencing 1.8M height around cap. bank complete in all respect including any other items not specifically mentioned herein but reqd. for completion of job as per tech. spec. iii) 4600KVAR 11kV Capacitor Bank
5 TRANSFORMER FOUNDATION: 5.1 Design, engineering, construction of transformer foundation including all associated works, RCC, PCC, reinforcement steel, misc. structural steel and other items not mentioned herein but required for completion of work as per technical specifications. In case extra foundation (s) has/have to be constructed (as per approved T/F drawing) to complete the job, nothing extra would be paid on this count. i)10/16MVA, 132/11kV T/F foundation
ii) 12.5/16MVA 66/11kV T/F foundation
5.2) Design, Engg., supply of labour, T&P and material including RCC, PCC, Reinforcement steel, misc. structural steel & other item(s) not mentioned herein but required for the completion of work as per tech. specs. for construction of below mentioned T/F foundations. 200 KVA 11/0.4 kV T/F foundation
6. CABLE TRENCH: Supply of labour, material such as cement, Reinforcement steel, GI angles, flats, PCC & brick pillars below cable trenches for construction of Out-Door Cable Trenches (ODCT) of required depth/ type with pre-cast RCC covers including associated works like Cable Trench Culverts crossings for roads and sumpit-cum-pump chamber with 2HP motor of reputed make, starter volt meter, amp-meter etc. as per approved Trench layout plan, HVPNL drgs. & tech. specs. complete in all respect.
7. SITE SURFACING: 7.1) Providing, supplying & laying 100mm thick PCC (1:4:8) using 20mm nominal coarse aggregates & 100mm thick layer of 40mm nominal size uncrushed/crushed/broken stone/ pebbles over the PCC including construction of toe wall (exposed wall plastered with cement mortar 1:5) to hold 40mm size uncrushed/crushed/ broken stone/pebbles wherever required in the bays covered under the present scope as detailed in the GELO & instructions of XEN/CWD.
7.2) Providing, supplying & laying of 100mm thick uncrushed/crushed/broken stone/ pebbles gravel fill in two layers. The first layer after compaction shall make min. 50mm thickness course/layer of 40mm nominal size, including dressing, rolling & compaction complete as per specs., GELO and instructions of XEN/CWD.
8 ROADS & PCC PAVEMENT:- 8.1) Supply of labour, material and construction of cement concrete roads and walkways/shoulders from NH/SH/etc. to Switch yard/Switch house building as per GELO/CLO as per sectional detail drawing no. HCD/SK-181 R1 and technical specification. i) 6.0M from approach road to gates
ii) 3.66M wide
iii)PCC in front and rear of parking area of SH Building as per tech. specification and drawing HCD/SK-172.
9. ROAD CULVERTS: Design, Engineering and const. of Pipe culvert(s) at suitable locations under the approach road (from main PWD/ HUDA/Municipal/Village road to the sub-station entry point) including, cost of labour, material complete in all respects as per I.R.C. Standards.
10 BOUNDARY WALL 10.1) Supply of labour, material and construction of front, C & U/C boundary walls above DPC including main gate foundations as per GELO/CLO, technical specifications. & HVPNL drawing including DPC complete in all respect .i) 6 ft. high with GI barbed wire on angles at top.
ii) 4½ ft. high front wall with grill at top.
iii) 4½ ft. high side U/C wall.
10.2)Supply of labour, T&P, material & construction of front, side & U/C boundary walls (brickwork below DPC level) as per GELO/CLO, tech. spec. & HVPNL drgs including excavation, PCC, back filling etc. complete in all respects.
11) RCC retaining wall: The design, engineering and construction of RCC retaining wall to retain backfill as per yard level and outside level i.e. bed level (existing/after re-routing of barsati nala) is in the scope of successful bidder. The provision for stability of retaining wall in view of barsati nala is to be considered by the successful bidder at the time of designing of retaining wall without any extra cost to HVPNL. i) Retaining wall for NGL & FGL difference from 2.0Mtr. to 3.0Mtr.
ii) Retaining wall for NGL & FGL difference from 3.0Mtr. to 4.0Mtr.
iii) Retaining wall for NGL & FGL difference above 4.0Mtr.
12 U/C FENCING & GATES: Providing & fixing chain link fencing including foundations, GI angle iron posts and gate(s) complete as per electrical layout & tech. spec. & as per drawing attached.
13. MULTI-STORY CONTROL ROOM BUILDING: Design engineering, supply of labour, material, T&P and construction of multi-story control room building complete in all respect as per tech. specs. including exterior weather proof paint, interior emulsion, all internal services like water supply including supply & providing of 5000ltr. capacity double layer Sintex/Diplast PVC tank, Sewerage system, electrification including wiring, modular switches, maximum 20W 4ft. long LED tubes with fittings minimum 1960 lumens, ceiling/exhaust fans, Finishing, Plinth protection, Indoor trenches/cut-outs, Soakage pit near the switch house building, connection of sewerage system to Soakage pit/Sewerage system of local authorities (as applicable), connection to main water supply system of local authority, bore (Tubewell) (as applicable) etc. & any other item not mentioned herein but required for completion of works.
14 DRAINAGE-CUM- RAIN HARVESTING SYSTEM: 14.1) Supply of labour, material for construction of 1 nos. recharge structures with bore well(s) as per HVPN drawings & specs. complete in all respect. The location of recharge structures shall preferably be located on corner(s) of the substation and shall be got decided from the concerned XEN/Civil Works Division on the basis of surroundings of the substation(s). In case ground water table is less than 8m from FGL, rain harvesting well shall not be constructed (the drainage system with sump pit is to be constructed as per item mentioned below).
14.2)The successful bidder shall evolve design & drawing for drains, manholes with RCC covers and settlement tank including preparation of drainage layout drawing for disposal of rain water from building’s roof top & switch yard (s/stn.) area into respective bore well(s) in such a way that there shall be no ponding of water on the roof and switch yard (s/stn.). The layout so developed shall be got approved from the employer. The location of sump-pit-cum-pump chamber shall preferably be located on corner(s) of the s/stn. and shall be got decided from the concerned XEN/Civil Works Division on the basis of surroundings of the substation(s). The successful bidder will also supply labour and material for construction of 1 no. sump-pit-cum-pump chamber as per HVPNL drgs. & provide one no. non clog pump(s) of 5HP of reputed make capacity with main switch, starter, volt meter, Amp. Mtr. etc. (for each sump pit) for disposal of excess water to outfall point. Any other item(s) not mentioned herein but is/are required for completion of works shall be done by the successful bidder without any extra cost to the employer.
220kv s/Stn Pinjore 1) 12.5/16MVA, 66/11kV T/Fs To be provided by HVPNL
2) 132 kV Bus post Insulators
3) a) 66 kV Surge Arrestor
b) 66 kV Surge Arrestor 6No. existing dismantled form the system to be used
4) 66 kV T/F CT (300-200-150/0.577-1-1A)
5) 66 kV CVT for line
6) 66kV Post insulator
7) 66 kV NCT (300-200-150/1A)
8) 11 kV NCT for 66/11kV (1200-900/5A)
10) 66kV Wave trap
11) 11 kV CT/PT combined unit (1No. - to be provided by HVPNL)
12 (a) 1.1 kV Copper Control Cable unarmoured for 66kV & 132kV bays of size 7Cx4mm2, 4Cx4mm2, 2Cx4mm2,2Cx6mm2, 3Cx2.5mm2, 16Cx2.5mm2, 10Cx2.5mm2 & 7Cx2.5mm2 including junction box etc. refer Section-6 of copper & control cable & Section-7 for switchyard erection.
12 (b) Stainless steel MK (200 TB)
13) 11 kV Power Cable XLPE 1C x1000mm2 for T/F to 11kV incomer with termination kit for both ends.
14) Connecting equipmnents to existing earthmat as per Section-7
15)Supply and installation of 2 fittings of 240W LED lamps with all accessories for Complete lighting of outdoor Switch yard area as per clause 16.0 of section 7 of the specifications.
16) 66 kV bolted type single suspension/tension string assembly with silicon polymer composite insulator string (E&M strength 9000 kg) per string with all hardware accessories suitable for TWIN zebra/single zebra conductor. Spared from the dismantlement to be used
17) Boltless C-Type Wedge connectors matching with conductor size.
18) Copper lugs glands, PVC ferrules for control cabling.
19) Fibre cleats, Aluminium clamps, bolts, nuts, washers etc., for fixing control cables in trenches.
20) Galvanized iron perforated tray with side coupler plate bolts, nuts, washers and clamps etc. of size 75x25x2 mm, 150x25x2mm, 100x25x2mm etc. & G.I. Conduits of 50mm/100mm dia from equipment to main trench as per Section-7, Switchyard erection.
21) ACSR Zebra Conductor
22) 7/3.15 GS Earthwire ( to be supplied by HVPNL , item lying in DD store , panipat)
23) Spacers for Twin zebra Conductor
24) U-bolt 20mm dia
25) Tower type BT-1
26) Tower type BT-3
27) Beam type BB-1
28) Tower type CT-4
29) Tower type CT-5
30) Beam type CB-6
31) Structure - 66kV Post insulator . HTD/ST-145
32) Structure - 132kV Bus Post Insulator drg.No.HTD/ST-144
33) Structure - 11 kV NCT Drg. HTD/ST-149( if combined structure used )
34) Structure - 11 kV NCT Drg. HTD/ST-88R( if required )
1. Dismantlement of usable 132kV equipments from 220/132/66kV S/Stn. Pinjore. and transportation & erection at 132 kV cum 66kV S/Stn Nanakpur for items i to iii i) 10/16MVA 132/11kV T/F along with its all accessories & transformer oil
ii) 132kV SF-6 Breaker
iii) 132kV lightning arrestor
2. The Dismantlement of old 132/66kV transformers (to be placed in the yard of 220kV S/Stn Pinjore after removing from plinth as spare ) i) 132 kV T/F CT
ii) 132 kV Isolator
iii) 132 kV NCT
iv) 132/66kV 40 MVA T/F
v) 66 kV T/F CT
vi) 66 kV LA
vii) 66 kV NCT
viii 66 kV Circuit Breaker
ix) 66 kV Isolator
X) All the above equipments alongwith asoociated jumpers, hardwarefittings and allied structures
3. Dismantlement of material of 132/11kV 10/16MVA T/F bay material (to be placed at any suitable place at 220kV S/Stn Pinjore) 1) 132kV NCT
2) 11kV NCT
3) 132kV T/F CT
5) 11kV CT and PT combined unit
6) 11kV XLPE power cable 630sqmm. Single core 300 meter approx
7) T/F MK with all control cable
8) C&R panel of T/F 132/11kV 10/16 MVA
9) All the above equipments alongwith associated jumpers, hardware fittings and allied equipment structures
CIVIL WORKS for Bays work at 220KV S/Stn Pinjore FOUNDATIONS Supply of labour, T&P, material and construction of RCC footings & pedestals etc. for steel gantry and equipment structures complete in all respects as per technical specifications & drawings attached with the tender document including cost of excavation, concreting, cement, reinforcement steel, form work, grouting, holding down bolts, backfilling etc. and other items not mentioned herein but required for the completion of work. Including disposal of surplus earth. A GANTRY TOWERS i) BT-1
iii) CT-4
B EQUIPMENT 132KV side i) 132kV POST INSULATOR
66kV side i) 66kV POST INSULATOR
2. OUTDOOR CABLE TRENCHES Design, Engineering, supply of labour, material, T&P and construction of Outdoor Cable Trenches including pre-cast RCC covers, RCC culverts for road crossings wherever required as per approved layout plan for trenches, drainage etc. including cement, reinforcement steel, GI angles, flats etc. complete in all respects as per technical specifications. Including disposal of surplus earth.
5 SITE SURFACING: Providing, supplying and laying 100mm thick PCC (1:4:8) using 20mm nominal coarse aggregates and spreading 100mm thick layer of 40mm nominal size uncrushed/crushed/ broken stone pebbles over the PCC including construction of toe wall (exposed wall plastered with cement mortar 1:5) to hold 40mm single size uncrushed/ crushed/broken stone pebbles wherever required in the bays covered under the present scope as detailed in the GELO & instructions of concerned Executive Engineer/Civil Works Division. Including disposal of surplus earth.
SMS India Private Limited
SRIHARI CONSTRUCTIONS
Hartek Power Private
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.05 MB
Download all tender documents and submit your bid