Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹3.4 LAccepted-Finance SHANKAR HOUSE TOTU SHIMLA HP 171011 | SHIMLA | SHIMLA | HIMACHAL PRADESH | 171011 | L1 | Accepted-Finance L1 | |
| 2 | L2₹4.0 L+₹59,979.45 (17.4%)Rejected-Finance 00 KIWADI SAFEDABAD BARABANKI BARABANKI UTTAR PRADESH 225001 | BARABANKI | UTTAR PRADESH | 225001 | L2 | Rejected-Finance L2 |
Tender Value
₹3.5 L
EMD Value
₹7,100
Closing Date
20 Mar 2026, 5:00 pmClosed
EE
Electrical Division No.II, HPPWD, U.S. Club, Shimla-01.
Providing installation testing and commissioning of 10 KVA UPS in HPPWD B and R Sub Division Jalog District Shimla.
2026_PWD_131160_2
ED.II.TA.TENDER.25.26.3841 dated 09.03.26
Open Tender
Electrical Works
Percentage
30 days
Jalog
Please refer to tender documents. Eligibility criteria is mentioned at page No. 6-7, 9-10 of GCC. Documents mentioned in eligibility criteria must be uploaded to qualify the bid.
7 documents required · 7 mandatory
₹350
₹7,100
6 Apr 2026
13 Mar 2026
23 Mar 2026
13 Mar 2026
20 Mar 2026
13 Mar 2026
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.:
Group C:
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.:
2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire:
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.:
:5/6 amps switch
:15/16 A switch
:3 pin 5/6 A socket outlet
:6 pin 15/16 A socket outlet
Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.:
:4 Module
:12 Module
Prov.installation.Testing & commissioning of 10KVA Online UPS: Capacity: 10 kVA Nominal Power (kVA): 10000VA Nominal Power (kW): 10000W Technology: On-line double conversion VFI-SS-111 Input Voltage: 230 V (Line-Neutral) 400 V (Line-Line) Input Voltage Range: 176 V - 280 V (Line- Neutral), 305 V - 485 V (Line- Line) THDi: < 5% Input Power Factor: > 0.99 Input Frequency: 40-70 Hz Compatibility with Diesel Generators: Yes Output Voltage: 230 V (adjustable to 220/230/240±1%(L-N) Efficiency Online: > 94.0% Efficiency in GREEN mode: > 98.0%Output frequency (nominal): 50 /60 Hz (Adjustable from front panel) Output frequency tolerance: ±0,1%Synch with Mains; ±0,01% Free RunCrest Factor: up to 3:1 THD of output voltage: < 1% at full linear load < 3% at full non-linear load Output power factor: Unity Output voltage Regulation: ± 1%; Dynamic Class1 IEC/EN62040-3 Overload Capability: Inverter: Upto 105% continuous, 106 -110% for 60min 111-130% for 10 min, 131-155% for 1min , >155% 200 msec Bypass Parameters Type: Static Automatic Input Voltage: 176 V - 280 V (Line- Neutral), 305 V - 485 V (Line-Line) Input Frequency: 50-60Hz ± 10% Battery/Storage Compatibility: VRLA, Tubular Battery Connection: Series Number of 12V Batteries: 16-40 No's Control Panel Display: LCD Communication ports: RS485 / USB /(SNMP & ModBus-TCP/IP) (Optional) Operating Temperature (°C): 0 - 40 °C (Recommended temperature for longer Battery Life: 20-25°C)Relative Humidity Range: 20-95% (Non-Condensing) Protection degree: IP20, Acoustic Noise at 1m (dBA): < 55 as required complete in all respect.:
Prov.installation. Testing & commissioning of 65AH 12V SMF Battery Make: Exide /Quanta. Warranty-02 yrs. as required complete in all respect.:
Providing and fixing Battey stand ( Rack ) of suitable size for housing of Batteries Rack & Connectors for Batteries as required complete in all respect.:
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.:
2 x 1.5 sq. mm:
3 x 4 sq. mm:
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.:
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.:
Single pole :
Supplying and fixing following rating, followings poles 10ka 240/415v 'C' curves miniature circuit braker suitable for inductive load of following poles in the exsisting MCB DB complete with connections, testing and commissioning etc. as required.:
Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator):
8 way , Double door:
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.81 MB
GCC.pdf
Tender Documents • 4.59 MB
BOQ_193921.xls
BOQ • 0.36 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .