Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹9.5 LAccepted-AOC 25 A RR SAMY LANE KATTOOR COIMBATORE 641009 | COIMBATORE | COIMBATORE | TAMIL NADU | 641009 | L1 | Accepted-AOC Quoted amount is over all reasonable | |
| 2 | L2₹9.6 L+₹17,943 (1.90%)Rejected-AOC NO 1A 1 SHALOM VALLUVAR STREET SIVANANDHA COLONY COIMBATORE TAMIL NADU 641 012 | COIMBATORE | TAMIL NADU | 641012 | L2 | Rejected-AOC Quoted amount is higher than 1st lowest | |
| 3 | L3₹9.8 L+₹37,080 (3.92%)Rejected-AOC NO 12 25 26 KATHIRAVAN NAGAR MAHALINGAPURAM PO POLLACHI COIMBATORE 642 002 | COIMBATORE | TAMIL NADU | 642002 | L3 | Rejected-AOC Quoted amount is higher than 1st lowest |
Tender Value
₹9.7 L
EMD Value
₹19,400
Closing Date
17 Oct 2019, 6:00 pmClosed
Yogesh S Meshram
AGE (I) Agrani Redfields Coimbatore
SPECIAL REPAIR TO EXTERNAL ELECTRIC SUPPLY TO OFFICERS MESS AND SPECIAL REPAIR TO LT PANEL NEAR ADMIN BLOCK AT INS AGRANI COIMBATORE
2019_MES_283059_1
8722/E8
Open Tender
Civil Works
Item Rate
182 days
Coimbatore
Class- E Category - b (I) / as per NIT documents
6 documents required · 6 mandatory
₹500
AGE I Agrani
₹19,400
Yes
18 Jan 2020
18 Sept 2019
19 Oct 2019
18 Sept 2019
17 Oct 2019
2 Oct 2019
18 Sept 2019 - 2 Oct 2019
Amount
Taking out of old unsv LT cable of any sizes from ground or wall.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 120 sqmm 3 1/2 core. Make : Glostar/Havell's/Finolex
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 70 sqmm 3 1/2 core. Make : Glostar/Havell's/Finolex
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 35 sqmm 3 1/2 core. Make : Glostar/Havell's/Finolex
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 25 sqmm 4 core. Make : Glostar/Havell's/Finolex
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 16 sqmm 4 core. Make : Glostar/Havell's/Finolex
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 10 sqmm 2 core. Make : Glostar/Havell's/Finolex
S&F submain wiring with multistranded colour code copper conductor in PVC conduit with FRLS cable 2 x 6.0 Sqmm size 1100 volts grade conforming to IS:694 single core stranded FRLS copper conductor 6.0 Sqmm PVC insulated cable as earth wire to common earth and connected to earth dolly and earth terminal box drawn in concealed PVC conduit. Make of Cable : Finolex,Havell's, Polycab Make of Conduit : Precision/Polycab or equivalent make approved by E-in-C's branch
S&F submain wiring with multistranded colour code copper conductor in PVC conduit with FRLS cable 2 x 10.0 Sqmm size 1100 volts grade conforming to IS:694 single core stranded FRLS copper conductor 10.0 Sqmm PVC insulated cable as earth wire to common earth and connected to earth dolly and earth terminal box drawn in concealed PVC conduit. Make of Cable : Finolex,Havell's, Polycab Make of Conduit : Precision/Polycab or equivalent make approved by E-in-C's branch
S&F submain wiring with multistranded colour code copper conductor in PVC conduit with FRLS cable 2 x 4.0 Sqmm size 1100 volts grade conforming to IS:694 single core stranded FRLS copper conductor 4.0 Sqmm PVC insulated cable as earth wire to common earth and connected to earth dolly and earth terminal box drawn in concealed PVC conduit. Make of Cable : Finolex,Havell's, Polycab Make of Conduit : Precision/Polycab or equivalent make approved by E-in-C's branch
S&F submain wiring with multistranded colour code copper conductor in PVC conduit with FRLS cable 2 x 2.5 Sqmm size 1100 volts grade conforming to IS:694 single core stranded FRLS copper conductor 2.5 Sqmm PVC insulated cable as earth wire to common earth and connected to earth dolly and earth terminal box drawn in concealed PVC conduit. Make of Cable : Finolex,Havell's, Polycab Make of Conduit : Precision/Polycab or equivalent make approved by E-in-C's branch
S&F Sheet metal enclosure for DB's double glazed door IP-43 Single pole & neutral 12 way with cable end box conforming to IS-8623-1 & 3 , IEC 61439-1 &3 made in CRCA sheet steel, RAL 9003 powder coated ready to use DB's provided with 100 A insulated phase bus bar, neutral bar with shrouds, earth bar, sticking saddles, cement spill protector, colour coded interconnection wire set, cable ties, blanking plates and circuit identification label with provision for DP MCB as incomer and SP MCBs as outgoing complete all as specified and directed by Engr-in-Charge. NOTE :- (a) MCBs shall be measured and paid separately. (b) All cables terminating into MCBs shall be connected by using suitable copper lugs/thimbles/sleeves and its cost shall be deemed to be included under respective item of Sch 'A'. Make/Model : Cat Part No. DBSPN012GD of make L&T or Cat Part No. CSDBSPNSDCA12 of C&S or equivalent in Schneider.
S&F Sheet metal enclosure for DB's double glazed door IP-43 Single pole & neutral 8 way with cable end box conforming to IS-8623-1 & 3, IEC 61439-1 &3 made in CRCA sheet steel, RAL 9003 powder coated ready to use DB's provided with 100 A insulated phase bus bar, neutral bar with shrouds, earth bar, sticking saddles, cement spill protector, colour coded interconnection wire set, cable ties, blanking plates and circuit identification label with provision for DP MCB as incomer and SP MCBs as outgoing complete all as specified and directed by Engr-in-Charge. NOTE:- (a) MCBs shall be measured and paid separately. (b) All cables terminating into MCBs shall be connected by using suitable copper lugs/thimbles/sleeves and its cost shall be deemed to be included under respective item of Sch 'A'. Make/Model : Cat Part No. DBSPN008GD of make L&T or Cat Part No. CSDBSPNSDCA08 of C&S or equivalent in Schneider.
S&F Sheet metal enclosure for DB's double glazed door IP-43 Vertical Triple pole & neutral 4 way with cable end box conforming to IS-8623-1 & 3, IEC 61439-1 &3 made in CRCA sheet steel, RAL 9003 powder coated ready to use DB's provided with insulated vertical phase bus bar, neutral bar with shrouds, earth bar, sticking saddles, cement spill protector, colour coded interconnection wire set, cable ties, blanking plates and circuit identification label with provision for 3/4 pole MCCB as incomer and SP/TP MCBas outgoings complete all as specified and directed by Engr-in-Charge. NOTE (a) MCCB/MCBs shall be measured and paid separately. (b) All cables terminating into MCCB/MCBs shall be connected by using suitable copper lugs/thimbles/sleeves and its cost shall be deemed to be included under respective item of Sch 'A'. Make/Model : Cat Part No. DBVTL004GD of make L&T or Cat Part No. CSDBMCCB100DD04IP43S of C&S or equivalent in Schneider.
S&F on distribution board MCCB four pole, 125 Amps, ultimate breaking cap 36 KA complete conforming to IEC 60947-2 Suitable for isoltaion Ics= 100% of Icu which having adjustable overload setting, adjustable short circuit setting, transparent release cover including suitable spreader terminals complete all as specified. Make/Model : Cat part No. DZ1F0125DXD1A of make L&T or equivalent in CSE1M125ATM4P of C&S or equivalent in Schneider.
S&F on distribution boards, MCCB four pole, 25 Amps, ultimate breaking cap 10 KA complete conforming to IEC 60947-2, Ics= 100% of Icu which having Thermal magnetic realese including suitable spreader terminals complete all as specified. Make/Model : Cat part No. EM90984OODO of make L&T or equivalent in CSE1N125FMU4P of C&S or equivalent in Schneider.
M&L for earthing complete with galvanized steel earth plate 600 x 600 x 6 mm thick burried directly in ground (earth pit not less than 2.25 mtr deep below ground level) with top edge of the plate not less than 1.5 mtr below normal ground level, connected to galvanised iron earthing lead 4 mm by means of bolts, nuts, check-nuts, and washers of galvanised iron or steel besides welding at all joints as shown in drawings and including excavation and earth work, GI pipe light grade 25 mm bore for protection of GI strip from earth electrode to and including the earth test point of galvanised iron / steel of size 75 x75 x 25 mm, supplying and laying charcoal dust, common salt, PCC 1:2:4 type B1 chamber and MS angle iron frame 40 x 40 x 3 mm and RCC cover 40 mm thick (1:2:4) type B1 using 20 mm graded stone aggregate reinforced with 6 mm dia round bars @ 75 mm C/C both ways with MS handle 12 mm dia, PGI funnel and wire mesh, 20 mm dia GI Pipe light grade for watering all as shown in drawing and connected to earth test point including testing complete all as specified and directed. As per SSR plate No.5 Note :- Testing should be carried out in front of Engr-in-Charge and report to be submit to this office in duplicate.
S&F single pole MCB 6 to 16 Amps 240 v, 50 Hz AC Made from moulded self-extinguishing thermostat plastic and suitable for ‘C’ curve, 15 KA breaking capacity conforms to IS/IEC 60947-2 and terminal box suitable upto 35 sqmm cable complete all as specifed and directed. Make/Model : Cat part No. BB10060C of make L&T or Cat part No. CSMBS1C6 of make C&S or equivalent in Schnider.
S&F DP MCB 32 Amps 240 v, 50 Hz AC Made from moulded self-extinguishing thermostat plastic and suitable for ‘C’ curve, 15 KA breaking capacity conforms to IS/IEC 60947-2 and terminal box suitable upto 35 sqmm cable complete all as specifed and directed. Make/Model : Cat part No. BB20320C of make L&T or Cat part No. CSMBS2C32 of make C&S or equivalent in Schnider.
Providing, cement concrete type B 1 (1:2:4) 20 mm grade aggregate in roof kerbs of mud stops, rounded or chamfered on edges in lintels upto 1.5 m clear span, cills, steps; seismic and other similar bands, plinth courses, string courses, lacing courses, parapets and railings upto 60 cm in height, copings, kneelers, apex stones, bed plates, kerbs not provided for in Item 04028, water troughs and the like including weathering, slightly rounded for chamfered angles and throating, as directing
Supply and fix ON LOAD change over switch 415V in sheet metal enclosures 4 pole of capacity 63 Amps. Make/Model : Cat part No. CO10630OSOO of make L&T or Cat part No. E-CSCS63NM4CO of make C&S or equivalent in Schneider.
Supply and fix ON LOAD change over switch 415V in sheet metal enclosures 4 pole of capacity 125 Amps. Make/Model : Cat part No. CO11250OOSO of make L&T or Cat part No. E-CSCS125NM4CO of make C&S or equivalent in Schneider.
Supply and fix ON LOAD change over switch 240V in sheet metal enclosures 2 pole of capacity 40 Amps. Make:- L&T/C&S/Havell's
Taking out old LT panel including all connection mechanically and electrically and deposited to MES Store yard or refixing the same as desired location electrically/mechanically complete all as specified and directed.
Supply installation, testing and commissioning of outdoor type IP - 66 protection factory fabricated cubical type LT panel board made out of 2.00mm thick CRCA sheet compartamentalised to accommodate the following , TPN aluminium bus bar rating of 800 Amp, bus bar shall be insulated with colour coated heat shrinkable sleeves and shall be mounted on DMC/epoxy insulator of size not less than 50 x 50mm conical type at a maximum interval of 500 mm through out the length of TPN bus bar, panel shall be front and back open above system, operated from both sides shall have louvers and air vent gasket for natural flow of air 'U' type gasket used to make panel board completely vermin proof (back side door shutter shall be double leaf) including taking out of old LT panel board complete.
The extension link shall not less than 300 mm long supported on DMC/epoxy insulator having provision for termination of incomer and outgoing cables. All interconnections between the main bus bar as well as outgoing feeders shall be carried out with TPN aluminium bus bar of rating not less than 1.5 time rated capacity of individual outgoing feeders. All control wire shall be 2.5 sqmm multi stranded copper conductor and shall be properly bunched, tied ferried for proper identification and crimped with adequate size of lugs. The cubical panel shall have a bottom MS channel of size 75x 40mm duly coated with zinc metal coating having thickness not less than 100 microns. A detachable predrilled suitable size gland plate zinc matel coated should be used at the bottom for entry of cable with lead, complete all as specified and directed for housing and incl of the following items :-
(A) INCOMING (i) MCCB : 250A, 4 Pole, 36 KA, 415 V, 50 Hz,conforming to IS/IEC 60947-2, Ics = 100% Icu, suitable for isolation, adjustable overload from 0.4 to 1.0 x In and adjustable short circuit from 1.5 - 8 Ir, inbuilt Instantaneous protection, provn of thermal memory : ON/OFF, variable trip class at 7.2Ir to 6 Ir, Front LED indication of Over load including suitable spreader terminal complete all as specifed and directed. Make / model : Cat part No. CM93003OOOOX1 of make L&T or Cat part No.. CSE3N400ETM4P-400A of Make C&S or quivalent in Seimens. - 01 Nos.
(iii) RYB LED indicating lamp - 01 Each
(B) OUTGOING (i) MCCB four pole, 160 Amps, ultimate breaking cap 36 KA complete conforming to IEC 60947-2 Suitable for isoltaion Ics= 100% of Icu which having adjustable overload setting, adjustable short circuit setting, transparent release cover including suitable spreader terminals complete all as specified. Make/Model : Cat part No. DZ1F0160DXD1AOOOO of make L&T or equivalent in CSE2M250ATM4P of C&S or equivalent in Schneider. - 01 Nos.
(ii) MCCB four pole, 125 Amps, ultimate breaking cap 36 KA complete conforming to IEC 60947-2 Suitable for isoltaion Ics= 100% of Icu which having adjustable overload setting, adjustable short circuit setting, transparent release cover including suitable spreader terminals complete all as specified. Make/Model : Cat part No. DZ1F0125DXD1A of make L&T or equivalent in CSE1M125ATM4P of C&S or equivalent in Schneider - 03 Nos.
(iii) MCCB four pole, 40 Amps, ultimate breaking cap 36 KA complete conforming to IEC 60947-2 Suitable for isoltaion Ics= 100% of Icu which having adjustable overload setting, adjustable short circuit setting, transparent release cover including suitable spreader terminals complete all as specified. Make/Model : Cat part No. DZ1F0040DXC1A of make L&T or equivalent in CSE1N125FMU4P of C&S or equivalent in Schneider - 02 Nos.
(iv) DP MCB 32/40 Amps 240 v, 50 Hz AC Made from moulded self-extinguishing thermostat plastic and suitable for ‘C’ curve, 15 KA breaking capacity conforms to IS/IEC 60947-2 and terminal box suitable upto 35 sqmm cable complete all as specifed and directed. Make/Model : Cat part No. BB20320C of make L&T or Cat part No. CSMBS2C32 of make C&S or equivalent in Schnider. - 04 Nos.
M&L for earthing complete with galvanized steel earth plate 600 x 600 x 6 mm thick burried directly in ground (earth pit not less than 2.25 mtr deep below ground level) with top edge of the plate not less than 1.5 mtr below normal ground leve, connected to galvanised iron earthing strip 25 x 4mm by means of bolts, nuts, check-nuts, and washers of galvanised iron or steel besides welding at all joints as shown in drawings and including excavation and earth work, GI pipe light grade 25 mm bore for protection of GI strip from earth electrode to and including the earth test point of galvanised iron / steel of size 75 x75 x 25 mm, supplying and laying charcoal dust, common salt, PCC 1:2:4 type B1 chamber and MS angle iron frame 40 x 40 x 3 mm and RCC cover 40 mm thick (1:2:4) type B1 using 20 mm graded stone aggregate reinforced with 6 mm dia round bars @ 75 mm C/C both ways with MS handle 12 mm dia, PGI funnel and wire mesh, 20 mm dia GI Pipe light grade for watering all as shown in drawing and connected to earth test point including testing complete all as specified and directed. As per SSR plate No.5. Note : Testing should be carried out in front of Engr-in-Charge and report to be submit to this office in duplicate.
Excavation in trenches, n. exc 1.5 m wide and n. exc 1.5 m in depth for foundation etc.and getting out for hard/dense soil complete all as specified and directed.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc 25cm for soft/loose soil complete all as directed.
Removing excavated material n.exc 50m and depositing where directed at a level n.exc 1.5 m above the starting point complete all as directed.
Supply and spread dry river sand unwashed free from sharp particles for cable cushioning including punning on both top and bottom of the cable complete all as specified and as directed.
Supply and lay one layer of new bricks laid in flat butting to each other in such a way that the length of the brick is at right angle to the central axis of the cable using old size sub class B bricks all as specified and as directed.
M & L for PCC (1:3:6) type C-1 using 20mm graded stone aggregate as in coping of poles above ground leve including finishing to exposed concrete surfaces even and fair and provision of form work for rough finished surfaces complete all as specified
Supply and lay GI tubes light grade with connected fittings laid in trenches/wall/ pole for protection to UG cables of size 25 mm dia. Make: Surya/Jindal/TATA
Supply and lay GI tubes light grade with connected fittings laid in trenches/wall/ pole for protection to UG cables of size 50 mm dia. Make: Surya/Jindal/TATA
Supply and lay GI tubes light grade with connected fittings laid in trenches/wall/ pole for protection to UG cables of size 80 mm dia. Make: Surya/Jindal/TATA
Supply, installation, testing and commissioning of outdoor type IP -66 protection factory fabricated cubical type LT panel board made out of 3.00mm thick CRCA sheet compartamentalised to accommodate the following , TPN aluminium bus bar rating of 400 Amp, bus bar shall be insulated with colour coated heat shrinkable sleeves and shall be mounted on DMC/epoxy insulator of size not less than 50 x 50mm conical type at a maximum interval of 500 mm through out the length of TPN bus bar, panel shall be front and back open above system, operated from both sides shall have louvers and air vent gasket for natural flow of air 'U' type gasket used to make panel board completely vermin proof (back side door shutter shall be double leaf) including taking out of old LT panel board complete.
The extension link shall not less than 300mm long supported on DMC/epoxy insulator having provision for termination of incomer and outgoing cables. All interconnections between the main bus bar as well as outgoing feeders shall be carried out with TPN aluminium bus bar of rating not less than 1.5 time rated capacity of individual outgoing feeders. All control wire shall be 2.5 sqmm multi stranded copper conductor and shall be properly bunched, tied ferried for proper identification and crimped with adequate size of lugs. The cubical panel shall have a bottom MS channel of size 75x 40mm duly coated with zinc metal coating having thickness not less than 100 microns. A detachable predrilled suitable size gland plate zinc matel coated should be used at the bottom for entry of cable with lead, complete all as specified and directed for housing and incl of the following items :-
(A) INCOMING (i) MCCB : 200A, 4 Pole, 36 KA, 415 V, 50 Hz,conforming to IS/IEC 60947-2, Ics = 100% Icu, suitable for isolation, adjustable overload from 0.4 to 1.0 x In and adjustable short circuit from 1.5 - 8 Ir, inbuilt Instantaneous protection, provn of thermal memory : ON/OFF, variable trip class at 7.2Ir to 6 Ir, Front LED indication of Over load including suitable spreader terminal complete all as specifed and directed. Make / model : Cat part No. CM92151OOOOX1 of make L&T or Cat part No.. CSE3N400ETM4P-400A of Make C&S or quivalent in Seimens. - 01 Nos.
(iii) RYB LED indicating lamp - 01 Each
(B) OUTGOING (i) MCCB four pole, 100 Amps, ultimate breaking cap 36 KA complete conforming to IEC 60947-2 Suitable for isoltaion Ics= 100% of Icu which having adjustable overload setting, adjustable short circuit setting, transparent release cover including suitable spreader terminals complete all as specified. Make/Model : Cat part No. DZ1F0100DXD1AOOOO of make L&T or equivalent in CSE1N125ATM4P of C&S or equivalent in Schneider. - 02 Nos.
(ii) MCCB four pole, 63 Amps, ultimate breaking cap 36 KA complete conforming to IEC 60947-2 Suitable for isoltaion Ics= 100% of Icu which having adjustable overload setting, adjustable short circuit setting, transparent release cover including suitable spreader terminals complete all as specified. Make/Model : Cat part No. DZ1F0063DXD1AOOOO of make L&T or equivalent in CSE1N125ATM4P of C&S or equivalent in Schneider - 03 Nos.
(iii) MCCB four pole, 40 Amps, ultimate breaking cap 36 KA complete conforming to IEC 60947-2 Suitable for isoltaion Ics= 100% of Icu which having adjustable overload setting, adjustable short circuit setting, transparent release cover including suitable spreader terminals complete all as specified. Make/Model : Cat part No. DZ1F0040DXD1AOOOO of make L&T or equivalent in CSE1M125FMU4P of C&S or equivalent in Schneider - 06 Nos.
shalom constructions
Rajapriyaconstruction
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .