| 1 | L1₹73.0 LAccepted-AOC HOUSE NO 251 E BLOCK ADARSH NAGAR BALLABHGARH FARIDABAD PIN 121004 HARYANA | FARIDABAD | FARIDABAD | HARYANA | 121004 | L1 | Accepted-AOC Being L1 | |
| 2 | L2₹78.6 L+₹5.6 L (7.63%)Rejected-Finance | L2 | Rejected-Finance Not Being L1 | |
| 3 | L3₹80.8 L+₹7.8 L (10.6%)Rejected-Finance | L3 | Rejected-Finance Not Being L1 | |
| 4 | L4₹84.5 L+₹11.4 L (15.6%)Rejected-Finance BANPUR BATWARA SRINAGAR 190004 J K | SRINAGAR | SRINAGAR | JAMMU AND KASHMIR | 190004 | L4 | Rejected-Finance Not Being L1 | |
| 5 | L5₹87.0 L+₹13.9 L (19.1%)Rejected-Finance | L5 | Rejected-Finance Not Being L1 |
Tender Value
₹94.7 L
EMD Value
₹1.7 L
Closing Date
13 Mar 2021, 6:00 pmClosed
CWE, HQ 133 Wks Engrs
HQ 133 Wks Engrs PIN-914133 c/o 56 APO
SPECIAL REPAIR FOR REPLACEMENT OF BER DG SETS UNDER GE 864 EWS AT BB CANTT SRINAGAR
2020_MES_394907_2
CWEK-50/2020-21
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE 864 EWS
Class C Category b i
7 documents required · 7 mandatory
₹1,000
GE 864 EWS
₹1.7 L
Yes
HQ 133 Wks Engrs
12 Nov 2021
17 Feb 2021
15 Mar 2021
17 Feb 2021
13 Mar 2021
6 Mar 2021
17 Feb 2021 - 3 Mar 2021
27 Feb 2021
Amount
Excavating in trenches, not exceeding 1.50 metre wide and not exceeding 1.50m in depth for foundation etc. or for shafts, wells, cesspits, manholes, pier holes etc. not exceeding 10 sq.m on plan and not exceeding 1.50m in depth and getting out in soft/loose soil, complete all as specified and as directed .
Returning filling in including spreding leveling watering and well ramming in layers not exc 25 cm each in soft/loose soil, complete all as specified and as directed .
Removing excavated soil to a distance not exc 50 m and depositing where directed at level n exc 1.5 above the starting points, complete all as specified and as directed .
Material and Labour for Fine and dry sand cushioning for underground cable by providing a layers of sand 8cm deep before laying and 15cm deep after laying the cable including tretching the cable, complete all as specified and as directed . Note - Punned thickness of sand layer shall be measured and paid to contractor.
Material and labour for sub class brick laid dry width wise across the cable in trenches for protection of cable complete all as specified.
Supply, Installation, testing and commissioning of silent type Diesel engine driven generating set with Governing class (as per ISO 8528 Part V) -G2 incl sound reducing canopy (sound level not more than 75 db) 14 guage as per guideline issued by Ministry of Environment & forest notification, & Central pollution control board or GSR 54(E) dt 23 Jan 2015, 415 volts, 3 phase, 50 Hz supply complete with panel for automatic starting or main failure control panel suitable for giving an output of 200 KVA after considering derating factor confirming to IS-1601 at 1800 metre altitude above mean sea level and capable of operating between temperature range (-20) degree C to 40 degree C (at Srinagar area of J & K) and alternator of suitable capacity and RPM coupled with each other & capable of taking 10% over load for one hours on every 12 hours (As per BS-5514/649) with flexible coupling mounted on common base plate on Antivibration pads on foundationas recommended by manufacture. The DG set shall comprise of Electric starter motor with batteries, Turbocharger, water cooled & comprising all standard fittings, fixtures & all piping etc as below :- (a) Alternator : Directly coupled with Engine and suitable to produce 415 volts, 3 phase 4 wire system, 50 Hz 0.8 PF @1500 RPM of capacity 200 KVA all as per as per IS: 13364 and up to date amendments with H class insulation having efficiency 91% on 100% load at 0.8 PF, self excited, self regulated, screen protected drip proof type with two end shield ball/Roller bearing with damper winding in each pole faces as per IS-4722 or BS 2613-1970 all as specified and directed (b) Engine : Water cooled Deisel Engine (CPCB Norms Compliance) developing Min 217 BHP or as recommended by the manufacturer for 1800 mtr altitude having Self start engine (including batteries with provn of charging the batteries and leads) suitable to drive above specified alternator complete with foundation (foundation design as per OEM), as per IS:10001/ 10002, coupled directly through flexible coupling, multi cylinder four stroke, cold starting, 1500 RPM industrial type as per BS-649 or IS-1601 with AI electronic governer suitable to regulate speed of DG set from No load to full load completed with fuel tank of cap as per manufacturer recommendations, fuel lines, exhaust pipe duly insulated painted and fitted with inlet and outlet connections
with asbestos rope and with support and silencer mufflers etc for continuous operation and standard accessories, sump pre heaters, cold start kit etc all as specified and directed. (c)Canopy : Acoustic enclosure shall be powder coated and fabricated out of 16 SWG CRCA MS sheet. The silent canopy shall be of nut bolt type construction. Critical processes of punching is done on CNC machines to maintain dimensional accuracy of holes within 0.1 mm. Powder coating is done after seven‐tank surface preparation process of sheet metal. Canopy panel and doors shall have inside lining of FIRE‐RETARDANT foam as acoustic material . Four hinged doors shall be provided to canopy, one door shall have glass window for control panel. (d) Base Frame : Base frame is fabricated in sheet metal. The base frame will be primer coated and painted. The base frame is rugged n construction and designed for mounting engine and alternator close coupled, with cross members mounted on AVM. The base frame shall have provision for mounting of acoustic enclosure & control panel on in it. The base frame is having provision of lifting hook for convenient lifting of complete set, i.e. along with canopy, engine and alternator. (e) Generating Panel :- DG set should consist of standard Generating Panel. (f) Exhaust System: The exhaust system and noise suppressor shall be provided with thermal insulation by using fire retardant / non igniting foam conforming to BIS 7888/BS 4375 to prevent excess heat radiation on the engine and safe for operator. (g) Fuel Tank: Fuel tank shall be fabricated out of 16 SWG CRCA MS Sheet . It is duly . Float gauge and fuel float switch is provided. Fuel tank shall have guage duly calibrated at every 5 litre. daily service fuel tank of suitable capacity as per manufacturer's instruction of having min fuel storing cap of 12 hours for running DG set including fuel oil indicating gauge drain and vent plug etc complete on a common base within the acoustic enclosure.
(h) Control Panel :- Alternator inbuilt control panel 415 Volt ,3 phase, 4 wire, 50 cycle fabricated out of 1.6mm thick MS sheet painted with internally/externally with two coats of synthic enamelled paing over one coat of primer complete with internal copper wiring sutiable for 200 KVA DG Set comprising of MCCB 4P,300 Amp 36 KA 01 No with spreader link,Multifunctional meter suitable to indicate Volt,power factor,bty voltage,RPM frequency,temp, oil pressure,hours run,Current AMP,KW, KWH etc. Note:- 1. Capacity of alternator at 1800 meters altitute -200 KVA, AC 3 Phase, 415 volts, 50 Hz. and as recommended by the manufacturer for above sized motor. 2. Place of installation- Near GT Sump BB Cantt Srinagar. 3. PCC platform 1:2:4 600 mm thick using 40mm graded stone aggregate to suit base frame size 45 cms below & 15 cms above ground level. Grouting 08 bolts of 600mm x 30mm and fixing the engine and alternator with base frame on the platform. PCC shall be measured & paid separately. 4. Engine and alternator shall be assembled on common steel frame by the manufacturer itself and not by rep / authorised agent / sister concern etc. 5. Engine shall be designed keeping in consideration of de-rating factor for 1800 meters altitute. 6. Canopy and engine shall be of same make. 7. Installation, testing and commissioning of Gen Set shall be done in presence of maufacturer's Engineer and not by any authorised person / rep/sister concern etc 8. DG Set to be tested for 12 Hrs contineously on full load (Rated load) including 1 Hr at 110% load. All testing materials and fuel to be provided by the contractor. 9. complete unit/set shall be equipped with all standard fitting as per manufacture recommendations and mounted on common base frame with following fitting and rates shall be deemed to be inclusive of the same:-
(j) Batteries : Maintenenace free batteries of 12 Volt /24 volt as per manufacturer direction complete with copper conductor multistranded lead of suitable length from self starter to the battery terminals complete with initial charge and initial fill of electronic all as specified. Starter gear ring, start and stop push button , ignition key/switch,(k) Handing and operation : Sailent features of accessories shall be as under :-Radiator with blower fan , Corrosion inhibitor coolent, paper element filter for fuel, lub oil and by pass, Elecronic governer controlled direct fuel injection system, Fly wheel housing and fly wheel (k) Generator Monitoring Panel : Comprising of following:- (i) Microprocessor based genset controller for metering, monitoring,governing and protection (ii) Engine protection for low oil pressure, high coolent temperature (alarm & shutdown) (iii) Alternator protection parameter like under voltage, over current, under frequency, over frequency, (alarm & shutdown) (iv) Relay drivers for remote annuciations (v) Cyclic cranking (vi) Auto/manual strat/stop (vii) Operator within a temperatur ( range (-20 to 60 degree C) and humidity upto 95% (viii) Remote monitoring capacity throught separate interface moudules (m) Genset metering parameters like lube oil pressure, coolent temperature, engine speed (RPM), run hours, DC voltage, intake manifold temperature, 3 phase volts and 3 phase amperes,frequency, KW,KVA, power factor. (n) Safety Controls :- Engine low lube oil pressure, high water temparature and over speeding of engine (o) Coupling arrangement : Flexible coupling, fly wheel to suit flexible coupling fly wheel housing (p) Accessories :- AVM pads builts or separately mounted to manufacture base frames.(q) Base frame : Stardy design made of MS channel with necessary reniforcement and predetermined holes. (r) daily service fuel tank of suitable capacity as per manufacturer's instruction of having min fuel storing cap of 12 hours for running DG set including fuel oil indicating gauge drain and vent plug etc complete on a common base within the acoustic enclosure.
Supply, Installation, testing and commissioning of silent type Diesel engine driven generating set with Governing class (as per ISO 8528 Part V) -G2 incl sound reducing canopy (sound level not more than 75 db) 14 guage as per guideline issued by Ministry of Environment & forest notification, & Central pollution control board or GSR 54(E) dt 23 Jan 2015, 415 volts, 3 phase, 50 Hz supply complete with panel for automatic starting or main failure control panel suitable for giving an output of 62.5 KVA ( 61 KW) after considering derating factor confirming to IS-1601 at 1800 metre altitude above mean sea level and capable of operating between temperature range (-20) degree C to 40 degree C (at Srinagar area of J & K) and alternator of suitable capacity and RPM coupled with each other & capable of taking 10% over load for one hours on every 12 hours (As per BS-5514/649) with flexible coupling mounted on common base plate on Antivibration pads on foundationas recommended by manufacture. The DG set shall comprise of Electric starter motor with batteries, Turbocharger, water cooled & comprising all standard fittings, fixtures & all piping etc as below :- (a) Alternator : Directly coupled with Engine and suitable to produce 415 volts, 3 phase 4 wire system, 50 Hz 0.8 PF @1500 RPM of capacity 62.5 KVA all as per as per IS: 13364 and up to date amendments with H class insulation having efficiency 91% on 100% load at 0.8 PF, self excited, self regulated, screen protected drip proof type with two end shield ball/Roller bearing with damper winding in each pole faces as per IS-4722 or BS 2613-1970 all as specified and directed (b) Engine : Water cooled Deisel Engine (CPCB Norms Compliance) developing Min 61 KW/ 83 BHP or as recommended by the manufacturer for 1800 mtr altitude having Self start engine (including batteries with provn of charging the batteries and leads) suitable to drive above specified alternator complete with foundation (foundation design as per OEM), as per IS:10001/ 10002, coupled directly through flexible coupling, multi cylinder four stroke, cold starting, 1500 RPM industrial type as per BS-649 or IS-1601 with AI electronic governer suitable to regulate speed of DG set from No load to full load completed with fuel tank of cap as per manufacturer recommendations, fuel lines, exhaust pipe duly insulated , painted and fitted with inlet and outlet connections
with asbestos rope and with support and silencer mufflers etc for continuous operation and standard accessories, sump pre heaters, cold start kit etc all as specified and directed. (c)Canopy : Acoustic enclosure shall be powder coated and fabricated out of 16 SWG CRCA MS sheet. The silent canopy shall be of nut bolt type construction. Critical processes of punching is done on CNC machines to maintain dimensional accuracy of holes within 0.1 mm. Powder coating is done after seven‐tank surface preparation process of sheet metal. Canopy panel and doors shall have inside lining of FIRE‐RETARDANT foam as acoustic material . Four hinged doors shall be provided to canopy, one door shall have glass window for control panel. (d) Base Frame : Base frame is fabricated in sheet metal. The base frame will be primer coated and painted. The base frame is rugged n construction and designed for mounting engine and alternator close coupled, with cross members mounted on AVM. The base frame shall have provision for mounting of acoustic enclosure & control panel on in it. The base frame is having provision of lifting hook for convenient lifting of complete set, i.e. along with canopy, engine and alternator. (e) Generating Panel :- DG set should consist of standard Generating Panel. (f) Exhaust System: The exhaust system and noise suppressor shall be provided with thermal insulation by using fire retardant / non igniting foam conforming to BIS 7888/BS 4375 to prevent excess heat radiation on the engine and safe for operator. (g) Fuel Tank: Fuel tank shall be fabricated out of 16 SWG CRCA MS Sheet . It is duly . Float gauge and fuel float switch is provided. Fuel tank shall have guage duly calibrated at every 5 Litres. daily service fuel tank of suitable capacity as per manufacturer's instruction of having min fuel storing cap of 12 hours for running DG set including fuel oil indicating gauge drain and vent plug etc complete on a common base within the acoustic enclosure.
(h) Control Panel :- Alternator inbuilt control panel 415 Volt ,3 phase, 4 wire, 50 cycle fabricated out of 1.6mm thick MS sheet painted with internally/externally with two coats of synthic enamelled paing over one coat of primer complete with internal copper wiring sutiable for62.5 KVA DG Set comprising of MCCB 4P,100 Amp, 25 KA- 01 No with spreader link,Multifunctional meter suitable to indicate Volt,power factor,bty voltage,RPM frequency,temp, oil pressure,hours run,Current AMP,KW, KWH etc. Note:- 1. Capacity of alternator at 1800 meters altitute -62.5 kVA, AC 3 Phase, 415 volts, 50 Hz. and as recommended by the manufacturer for above sized motor. 2. Place of installation- Near BB Cantt Srinagar. 3. PCC platform 1:2:4 600 mm thick using 40mm graded stone aggregate to suit base frame size 45 cms below & 15 cms above ground level. Grouting 08 bolts of 600mm x 30mm and fixing the engine and alternator with base frame on the platform. PCC shall be measured & paid separately. 4. Engine and alternator shall be assembled on common steel frame by the manufacturer itself and not by rep / authorised agent / sister concern etc. 5. Engine shall be designed keeping in consideration of de-rating factor for 1800 meters altitute. 6. Canopy and engine shall be of same make. 7. Installation, testing and commissioning of Gen Set shall be done in presence of maufacturer's Engineer and not by any authorised person / rep/sister concern etc 8. DG Set to be tested for 12 Hrs contineously on full load (Rated load) including 1 Hr at 110% load. All testing materials and fuel to be provided by the contractor. 9. complete unit/set shall be equipped with all standard fitting as per manufacture recommendations and mounted on common base frame with following fitting and rates shall be deemed to be inclusive of the same:-
(j) Batteries : maintenenace free batteries of 12 Volt /24 volt as per manufacturer direction complete with copper conductor multistranded lead of suitable length from self starter to the battery terminals complete with initial charge and initial fill of electronic all as specified. Starter gear ring, start and stop push button , ignition key/switch,(k) Handing and operation : Sailent features of accessories shall be as under :-Radiator with blower fan , Corrosion inhibitor coolent, paper element filter for fuel, lub oil and by pass, Elecronic governer controlled direct fuel injection system, Fly wheel housing and fly wheel (k) Generator Monitoring Panel : Comprising of following:- (i) Microprocessor based genset controller for metering, monitoring,governing and protection (ii) Engine protection for low oil pressure, high coolent temperature (alarm & shutdown) (iii) Alternator protection parameter like under voltage, over current, under frequency, over frequency, (alarm & shutdown) (iv) Relay drivers for remote annuciations (v) Cyclic cranking (vi) Auto/manual strat/stop (vii) Operator within a temperatur ( range (-20 to 60 degree C) and humidity upto 95% (viii) Remote monitoring capacity throught separate interface moudules (m) Genset metering parameters like lube oil pressure, coolent temperature, engine speed (RPM), run hours, DC voltage, intake manifold temperature, 3 phase volts and 3 phase amperes,frequency, KW,KVA, power factor. (n) Safety Controls :- Engine low lube oil pressure, high water temparature and over speeding of engine (o) Coupling arrangement : Flexible coupling, fly wheel to suit flexible coupling fly wheel housing (p) Accessories :- AVM pads builts or separately mounted to manufacture base frames.(q) Base frame : Stardy design made of MS channel with necessary reniforcement and predetermined holes. (r) daily service fuel tank of suitable capacity as per manufacturer's instruction of having min fuel storing cap of 12 hours for running DG set including fuel oil indicating gauge drain and vent plug etc complete on a common base within the acoustic enclosure.
Supply, Installation, testing and commissioning of silent type Diesel engine driven generating set with Governing class (as per ISO 8528 Part V) -G2 incl sound reducing canopy (sound level not more than 75 db) 14 guage as per guideline issued by Ministry of Environment & forest notification, & Central pollution control board or GSR 54(E) dt 23 Jan 2015, 415 volts, 3 phase, 50 Hz supply complete with panel for automatic starting or main failure control panel suitable for giving an output of 180 KVA after considering derating factor confirming to IS-1601 at 1800 metre altitude above mean sea level and capable of operating between temperature range (-20) degree C to 40 degree C (at Srinagar area of J & K) and alternator of suitable capacity and RPM coupled with each other & capable of taking 10% over load for one hours on every 12 hours (As per BS-5514/649) with flexible coupling mounted on common base plate on Antivibration pads on foundationas recommended by manufacture. The DG set shall comprise of Electric starter motor with batteries, Turbocharger, water cooled & comprising all standard fittings, fixtures & all piping etc as below :- (a) Alternator : Directly coupled with Engine and suitable to produce 415 volts, 3 phase 4 wire system, 50 Hz 0.8 PF @1500 RPM of capacity 180 kVA all as per as per IS: 13364 and up to date amendments with H class insulation having efficiency 91% on 100% load at 0.8 PF, self excited, self regulated, screen protected drip proof type with two end shield ball/Roller bearing with damper winding in each pole faces as per IS-4722 or BS 2613-1970 all as specified and directed (b) Engine : Water cooled Deisel Engine (CPCB Norms Compliance) developing Min 234 BHP or as recommended by the manufacturer for 1800 mtr altitude having Self start engine (including batteries with provn of charging the batteries and leads) suitable to drive above specified alternator complete with foundation (foundation design as per OEM), as per IS:10001/ 10002, coupled directly through flexible coupling, multi cylinder four stroke, cold starting, 1500 RPM industrial type as per BS-649 or IS-1601 with AI electronic governer suitable to regulate speed of DG set from No load to full load completed with fuel tank of cap as per manufacturer recommendations, fuel lines, exhaust pipe duly insulated painted and fitted with inlet and outlet connections
with asbestos rope and with support and silencer mufflers etc for continuous operation and standard accessories, sump pre heaters, cold start kit etc all as specified and directed. (c)Canopy : Acoustic enclosure shall be powder coated and fabricated out of 16 SWG CRCA MS sheet. The silent canopy shall be of nut bolt type construction. Critical processes of punching is done on CNC machines to maintain dimensional accuracy of holes within 0.1 mm. Powder coating is done after seven‐tank surface preparation process of sheet metal. Canopy panel and doors shall have inside lining of FIRE‐RETARDANT foam as acoustic material . Four hinged doors shall be provided to canopy, one door shall have glass window for control panel. (d) Base Frame : Base frame is fabricated in sheet metal. The base frame will be primer coated and painted. The base frame is rugged n construction and designed for mounting engine and alternator close coupled, with cross members mounted on AVM. The base frame shall have provision for mounting of acoustic enclosure & control panel on in it. The base frame is having provision of lifting hook for convenient lifting of complete set, i.e. along with canopy, engine and alternator. (e) Generating Panel :- DG set should consist of standard Generating Panel. (f) Exhaust System: The exhaust system and noise suppressor shall be provided with thermal insulation by using fire retardant / non igniting foam conforming to BIS 7888/BS 4375 to prevent excess heat radiation on the engine and safe for operator. (g) Fuel Tank: Fuel tank shall be fabricated out of 16 SWG CRCA MS Sheet . It is duly . Float gauge and fuel float switch is provided. Fuel tank shall have guage duly calibrated at every 5 Litres. daily service fuel tank of suitable capacity as per manufacturer's instruction of having min fuel storing cap of 12 hours for running DG set including fuel oil indicating gauge drain and vent plug etc complete on a common base within the acoustic enclosure.
(h) Control Panel :- Alternator inbuilt control panel 415 Volt ,3 phase, 4 wire, 50 cycle fabricated out of 1.6mm thick MS sheet painted with internally/externally with two coats of synthic enamelled paing over one coat of primer complete with internal copper wiring sutiable for 180 KVA DG Set comprising of MCCB 4P,250 Amp 36 KA 01 No with spreader link,Multifunctional meter suitable to indicate Volt,power factor,bty voltage,RPM frequency,temp, oil pressure,hours run,Current AMP,KW, KWH etc. Note:- 1. Capacity of alternator at 1800 meters altitute -180 kVA, AC 3 Phase, 415 volts, 50 Hz. and as recommended by the manufacturer for above sized motor. 2. Place of installation- Near Batwara Sump BB Cantt Srinagar. 3. PCC platform 1:2:4 600 mm thick using 40mm graded stone aggregate to suit base frame size 45 cms below & 15 cms above ground level. Grouting 08 bolts of 600mm x 30mm and fixing the engine and alternator with base frame on the platform. PCC shall be measured & paid separately. 4. Engine and alternator shall be assembled on common steel frame by the manufacturer itself and not by rep / authorised agent / sister concern etc. 5. Engine shall be designed keeping in consideration of de-rating factor for 1800 meters altitute. 6. Canopy and engine shall be of same make. 7. Installation, testing and commissioning of Gen Set shall be done in presence of maufacturer's Engineer and not by any authorised person / rep/sister concern etc 8. DG Set to be tested for 12 Hrs contineously on full load (Rated load) including 1 Hr at 110% load. All testing materials and fuel to be provided by the contractor. 9. complete unit/set shall be equipped with all standard fitting as per manufacture recommendations and mounted on common base frame with following fitting and rates shall be deemed to be inclusive of the same:-
(j) Batteries : Maintenenace free batteries of 12 Volt /24 Volt as per manufacturer direction complete with copper conductor multistranded lead of suitable length from self starter to the battery terminals complete with initial charge and initial fill of electronic all as specified. Starter gear ring, start and stop push button , ignition key/switch,(k) Handing and operation : Sailent features of accessories shall be as under :-Radiator with blower fan , Corrosion inhibitor coolent, paper element filter for fuel, lub oil and by pass, Elecronic governer controlled direct fuel injection system, Fly wheel housing and fly wheel (k) Generator Monitoring Panel : Comprising of following:- (i) Microprocessor based genset controller for metering, monitoring,governing and protection (ii) Engine protection for low oil pressure, high coolent temperature (alarm & shutdown) (iii) Alternator protection parameter like under voltage, over current, under frequency, over frequency, (alarm & shutdown) (iv) Relay drivers for remote annuciations (v) Cyclic cranking (vi) Auto/manual strat/stop (vii) Operator within a temperatur ( range (-20 to 60 degree C) and humidity upto 95% (viii) Remote monitoring capacity throught separate interface moudules (m) Genset metering parameters like lube oil pressure, coolent temperature, engine speed (RPM), run hours, DC voltage, intake manifold temperature, 3 phase volts and 3 phase amperes,frequency, KW,KVA, power factor. (n) Safety Controls :- Engine low lube oil pressure, high water temparature and over speeding of engine (o) Coupling arrangement : Flexible coupling, fly wheel to suit flexible coupling fly wheel housing (p) Accessories :- AVM pads builts or separately mounted to manufacture base frames.(q) Base frame : Stardy design made of MS channel with necessary reniforcement and predetermined holes. (r) daily service fuel tank of suitable capacity as per manufacturer's instruction of having min fuel storing cap of 12 hours for running DG set including fuel oil indicating gauge drain and vent plug etc complete on a common base within the acoustic enclosure.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 300 sq mm 3.5 core complete all as specified and directed.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 185 sq mm 3.5 core complete all as specified and directed.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 240 sq mm 3.5 core complete all as specified and directed.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 120 sq mm 3.5 core complete all as specified and directed.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 50 sq mm 3.5 core complete all as specified and directed.
Supply, install, test & commission LT panel outdoor type, dust & Vermin proof self supporting fabricated out of CRCA steel sheet 3 mm thick at outer cover and 1.6 at inner compartment of size 1200 X 2000 X 450 ( l x b x h) mm with base ISMB 100 mm and Angle Iron frame (50x50x5mm) support to mount panel and tightened with 06 Nos 30 mm x 15 mm bolts & nuts with 4 Legs 30 cms below & 30 cms above GL grouted in PCC 1:3:6 Type C2 , cubicle type floor mounting, suitable for 3 phase 4 wire, 415 V, 50 Hz, AC supply, having cable ally on both sides of panel independant bays for incomming & outgoings with openable from front, rear, left & right side . Duly painted with powder coating (10 tank process) and PU gasket . Cable lugs are to be used to terminate cables/wires. Existing incomming connections are to be re-arranged as directed by Engineer-in-Charge. Single core copper cables shall be used for connections from bus bar to MCCBs/MCBs/instuments etc.
Supply, install, test & commission LT panel outdoor type, dust & Vermin proof self supporting fabricated out of CRCA steel sheet 3 mm thick at outer cover and 1.6 at inner compartment of size 1200 X 2000 X 450 ( l x b x h) mm with base ISMB 100 mm and Angle Iron frame (50x50x5mm) support to mount panel and tightened with 06 Nos 30 mm x 15 mm bolts & nuts with 4 Legs 30 cms below & 30 cms above GL grouted in PCC 1:3:6 Type C2 , cubicle type floor mounting, suitable for 3 phase 4 wire, 415 V, 50 Hz, AC supply, having cable ally on both sides of panel independant bays for incomming & outgoings with openable from front, rear, left & right side . Duly painted with powder coating (10 tank process) and PU gasket . Cable lugs are to be used to terminate cables/wires. Existing incomming connections are to be re-arranged as directed by Engineer-in-Charge. Single core copper cables shall be used for connections from bus bar to MCCBs/MCBs/instuments etc.
Material and labour for construction of open shed of size 6.0m X 4.0 m ( height 1.00 metre more than the height of DG Set ) having platform 5.00 m X 3.00 m X 0.30 for packaged type DG Set comprising of the following activities complete all as specified. Surface excavation in any type of soil, levelling and excavation in trenches in soft/loose soil, PCC 1:4:8 in foundation, 23cm thick Brick wall of platform in cement mortar 1:6 (30cm below and 30cm above ground level). 100mm thick PCC 1:2:4 in flooring of platform over PCC sub base 1:5:10 type E2 over 75mm thick hard core. Medium channel MC 150 in column post -06 Nos embedded in PCC platform, Truss, purlins, rafter, etc of mild steel angle iron 65x65x6mm fixed in position,conforming to Fe-410(Gde 250). pre-painted galvalume aluminium zinc coating GI based profiled steel sheet 0.50mm thick as in roof covering, painting two coat to all steel surface over a coat of primer, etc, complete all as specified and directed by Engr-in-charge. Note- (i) . The quoted rate include all the missing item required for the completion of shed. For quoting rate any other details required for completion of shed, contractor can checked with AGE E/M GE 864 EWS during office hour.
Supply, install, test & commission LT panel outdoor type, dust & Vermin proof self supporting fabricated out of CRCA steel sheet 3 mm thick at outer cover and 1.6 at inner compartment of size 1200 X 2000 X 450 ( l x b x h) mm with base ISMB 100 mm and Angle Iron frame (50x50x5mm) support to mount panel and tightened with 06 Nos 30 mm x 15 mm bolts & nuts with 4 Legs (30 cms below and 30 cms above GL) grouted in PCC 1:3:6 Type C2 , cubicle type floor mounting, suitable for 3 phase 4 wire, 415 V, 50 Hz, AC supply, having cable ally on both sides of panel independant bays for incomming and outgoings with openable from front, rear, left & right side . Duly painted with powder coating (7 tank process) and PU gasket . Cable lugs are to be used to terminate cables/wires. Existing incomming connections are to be re-arranged as directed by Engineer-in-Charge. Single core copper cables shall be used for connections from bus bar to MCCBs/MCBs/instuments etc.
Earthing complete with galvanised earth plate electrode 600mm x 600mmx 6mm thick buried directly in ground vertically ( earth pit of depth not less than 2.25m below ground level ) with top edge of the earth plate not less than 1.5m below normal ground level, connecting with GI strips of size 32x6mm earthing lead by means of bolts, nuts, checks nut and washers made out of galvanized iron and earth strip protected by galvanized steel pipe 40mm dia (light grade) including provn of concrete pit in PCC 1:2:4 type B-1 (using 20 mm graded mechanically crushed stone aggregate), 40mm thick RCC cover slab 1:2:4 tpye B1 reinforced with XPM ( weight not less than 4kg/sqm ) and frame made of angle iron of section 40x40x6mm with lugs, 02 Nos handle of 6mm dia mild steel bar made to shape, 20mm dia GI pipe (light grade) for watering perforated at bottom 1.75m long placed on top edge of earth plate, charcoal and salt filling in alternate layer, test point made out of phopsphorus/ Bronze with fixing arrangement , funnel wire mesh and earth work in soft/loose soil, returning filling, removal of surplus soil all as shown in electrical plate No.5 of SSR Part-I and connection to earth test point complete, all as specified including testing on completion. Note : Item of earthing include cost of 7.5m long GI earth strips of size 32x6mm, ,earth work in soft/ loose soil, returning filling and removal, GI protection pipe, GI watering pipe, funnel, wire wesh, RCC cover, etc .
Supply and fixing of Galvanised iron strip 32 x 6mm buried in ground complete all as specified and directed.
Supply and fixing of GI pipe, light grade, 100 mm bore, ISI Marked for protection to cable along the pole/across road crossing/passing through culvert, complete all as specified.
Supply and fixing of GI pipe, light grade, 80 mm bore, ISI Marked for protection to cable along the pole/across road crossing/passing through culvert complete all as specified.
PCC (1:4:8) type D-2 (using 40 mm graded stone aggregate) in foundation of electric poles, struts PCC blocks and fair finish to exposed surfaces without using extra cement etc complete all as specified.
Supply and fixing of OFF load Change over Switch in and including sheet metal enclosure cubical type 4 pole of rating 400 Amps, confirming to IS-13947 (Part 3) with rotary handles. Make: Havells Model No.IHCFFE0400 or equivalent model in makes mentioned in Appendix 'B' of tender document )
Supply and fixing of OFF load Change over Switch in and including sheet metal enclosure cubical type 4 pole of rating 100 Amps, confirming to IS-13947 (Part 3) with rotary handles. Make: Havells Model No.IHCFFE0400 or equivalent model in makes mentioned in Appendix 'B' of tender document )
Supply and fixing of OFF load Change over Switch in and including sheet metal enclosure cubical type 4 pole of rating 320 Amps, confirming to IS-13947 (Part 3) with rotary handles. Make: Havells Model No.IHCFFE0320 or equivalent model in makes mentioned in Appendix 'B' of tender document )
Shifting of existing DG Set of capacity 250 KVA from HQ 15 Corps to STP at transit camp at BB cantt including disconnecting and shifiting LT panels change over switch etc. complete all as directed. Note : DG set shall be shifted with proper safety using crane hydra/T&P/man power as required and same is deemed to be including in quoted rates.
Shifting of existing BER DG Set of capacity 110 to 125 KVA from GT Sump to MES store yard at BB cantt including disconnecting and shifiting LT panels change over switch etc. complete all as directed. Note : DG set shall be shifted with proper safety using crane hydra/T&P/man power as required and same is deemed to be including in quoted rates.
Shifting of existing BER DG Set of capacity 160 KVA from Batwara Sump to MES store yard at BB cantt including disconnecting and shifiting LT panels change over switch etc. complete all as directed. Note : DG set shall be shifted with proper safety using crane hydra/T&P/man power as required and same is deemed to be including in quoted rates.
Dismanting all electrical connection and shifting of existing DG Set of capacity 125 KVA at GT Sump installation from foundation to trolley and shifting the trolley to MES Store yard including making all electrical connection etc. and also taking down of existing DG set of any capacity to tubewell No. 1 complete all as directed. Note : DG set shall be shifted with proper safety using crane hydra/T&P/man power as required and same is deemed to be including in quoted rates.
M/S Noor Mohammad Shalla
ALCO ENGINEERSPVT LTD
M/S SUHEEL CONSTRUCTIONS
M/S Sky Engineers
RAMESH AND CO
M/S SURINDER KUMAR MAHAJAN
ABDUL MAJID BHAT
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .