Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹24.7 LAccepted-AOC | L1 | Accepted-AOC LOWEST BIDDER | |
| 2 | L2₹2.6 L−₹23.3 L (90.0%)Rejected-Finance | L2 | Rejected-Finance OTHER THAN LOWEST BIDDER | |
| 3 | L3₹28.8 L+₹3.0 L (11.5%)Rejected-Finance | L3 | Rejected-Finance OTHER THAN LOWEST BIDDER |
Tender Value
₹48 L
EMD Value
₹96,000
Closing Date
3 Sept 2024, 6:00 pmClosed
GE NAGROTA
GE NAGROTA
REPAIR AND MAINT OF SECURITY LIGHT STREET LIGHT LT PANELS CABLES EARTHING POLES OVERHEAD CONDUCTOR FEEDER PANEL BOXES JUNCTION BOXES EXTERNAL ELECTRIFICATION CEILING FAN EXHAUST FAN GEYSER DESERT COOLER ETC IN SILA GRN AT AGE REASI OF GE NAGROTA
2024_MES_664213_1
CA NO GEN-42/2024-2025
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
NAGROTA
Class D Category b i
8 documents required · 8 mandatory
₹500
GE NAGROTA
₹96,000
Yes
29 Oct 2024
5 Jul 2024
5 Sept 2024
5 Jul 2024
3 Sept 2024
22 Jul 2024
Amount
SCHEDULE ‘A’ PART-I Supply and fix 1100 Volts heavy duty round sheathed multistranded three core copper conductor cable of size 2.5 Sqmm for electrical connections to the street lights fittings complete all as specified and directed.
M & L Dismantling and taking down carefully flood light, street light /perimeter lighting luminaries from its position of any size /wattage from over head line poles or from elevated sentry post for carrying out repair/replacement of burt/worn out accessories and removing unserviceable items frim site and depositing to MES store yard at Reasi, including material and insulated copper conductor single core cable 1.5 sqmm size, connector block, screws etc. Refixing the fitting after repair to its position complete all as directed by Engr-in-Charge. (Note : Contractor responsibility is to liase with the department concerned for LT supply shut down required to carry out the work & aslo ensure the safety of labour emploued by giving them safety wquipments like helmet, gloves safety blt, discharge rod etc and nothing extra shall be permissible in this account. complete all as specified and directed.
Supply and fix Service cable/wire 1100 V flat twin core aluminium stranded conductor of size 6 Sqmm complete all as specifeid and directed.
Supply and fix Service cable/wire 1100 V flat twin core aluminium stranded conductor of size 10 Sqmm complete all as specifeid and directed.
Supply and fix Service cable/wire 1100 V flat twin core aluminium stranded conductor of size 16 Sqmm complete all as specifeid and directed.
Supply and fix Timer switch with sheet metal enclosure pole mounted type fabricated out of 16 gauge steel sheet consisting of following : - (i) Digital type time swith 24 hours with Power contactor single phase of 65 /TP Amp and MCB of 63 Amp SPN complete all as specified and directed. Make CAT Part No. IHXSS03120 of Havells " or equivalent make as specified in PS
M & L for cleaning, preparing and painting with one coat of aluminium paint to steel tubular pole 9 mtr long complete with cross arms, MS channels, angle, iron, frame work, etc incl numbering of pole with black enameled paint from stencil, complete all as specified and directed.
Supply and fix non-metallic PVC conduit 20 mm exclusive of boxes(junction boxes/terminal boxes) but inclusive of all tees, bends, elbows, reducers bell mouth tube ends and fixing accessories such as couplers, lock, nuts, saddle, pipe hooks etc.
Supply and Fixing in replacement of unsv burnt surge protection device of capacity 10 kv complete suitable for security light fitting of any capacity complete all as specified and directed.
Excavation in trenches not exc 1.5 mtr wide and not exc 1.5 m in depth in a soft/Hard soil for laying underground cables/ errection of steel tubular poles / stay pit etc all as directed by Engr-in-charge.
Returning, filling in incl spreading,levelling watering and well ramming in layer n exc .25 cm in soil each layer complete specified and directed by Engr-in-Charge.
Removing excavated surplus material to a distance n.exc 50 m and depostimg where directed at alevel n exc. 1.5 m above the starting point in any type of soil complete all as specified and directed by Engr-in-Charge.
M & L for sand cushioning with a layer of sand 80 mm thick before laying of cable and 150 mm thick after laying of cable in trenches complete all as specified and directed.
M & L for Brick covering with width equal to length of brick as mechanical protection to cables with well burnt sub class 'B' (old size) bricks laid dry flat, complete all as specified and directed.
Material and labour for PCC 1:4:8 type D-2 using 40mm graded stone aggregate as in base of pole, coping of above Ground level etc complete all as specified and directed.
Material and labour for PCC 1:3:6 type C-2 using 40mm graded stone aggregate as in foundation of pole complete all as specified and directed.
Supply and laying GI Tubing Light grade 40 mm Bore dia as Cable Protection fixied on walls/ poles by using the suitable size clamps, nuts, bolts etc or laid in trenches complete all as specfied and directed.
Supply and laying GI Tubing Light grade 50 mm Bore dia as Cable Protection fixied on walls/ poles by using the suitable size clamps, nuts, bolts etc or laid in trenches complete all as specfied and directed.
Supply and laying GI Tubing Light grade 80 mm Bore dia as Cable Protection fixied on walls/ poles by using the suitable size clamps, nuts, bolts etc or laid in trenches complete all as specfied and directed.
S & F inreplacement of GI tubing 50 mm dia light grade 1.2 mtr long pipe bent to shape 120 degree for mounting of security light and fixed to wall/pole, with suitable MS clamps 4 Nos with nut and bolt and washers including connecting complete including of suitable length as per direction and approved by Engr-in-charge,
Supply and fix 1100 Volts heavy duty round sheathed multistranded three core copper conductor cable of size 2.5 Sqmm for electrical connections to the street lights fittings complete all as specified and directed.
M & L Dismantling and taking down carefully flood light, street light /perimeter lighting luminaries from its position of any size /wattage from over head line poles or from elevated sentry post for carrying out repair/replacement of burt/worn out accessories and removing unserviceable items frim site and depositing to MES store yard at Reasi, including material and insulated copper conductor single core cable 1.5 sqmm size, connector block, screws etc. Refixing the fitting after repair to its position complete all as directed by Engr-in-Charge. (Note : Contractor responsibility is to liase with the department concerned for LT supply shut down required to carry out the work & aslo ensure the safety of labour emploued by giving them safety wquipments like helmet, gloves safety blt, discharge rod etc and nothing extra shall be permissible in this account.
Supply and fix Service cable/wire 1100 V flat twin core aluminium stranded conductor of size 10 Sqmm complete all as specifeid and directed.
M & L for cleaning, preparing and painting with one coat of aluminium paint to steel tubular pole 9 mtr long complete with cross arms, MS channels, angle, iron, frame work, etc incl numbering of pole with black enameled paint from stencil, complete all as specified and directed.
S&F DB for street light made out of PVC sheet 3.0mm thick, dust and vermin proof out door type of size 350mmx300mmx150mm (HxWxD) with arrangement of incoming and outgoing feeder with 04 Nos copper bus bar of 32 Amp, for termination of line with and including single MCB SP 230V. 5A 10 KA (in accordance with IS/IEC 60898-1) and making arrangement for fixing aluminium conductor of size 16 sqmm 4 core and copper wire of size 2 x1.5 sqmm with 1 x 1.5 sqmm earth wire in green wire of FR PVC insulated copper conductor from DB to light fitting, complete all as specified and directed.
S&F of 35 W LED Street Light luminaire confirmining incliding all necessary arrangemet for fixing on Pole made up SITC of high quality integrated LED street light with a minimum system lumen of 4500 Lm and system wattage not exceeding 35 W with nominal effiiciency 110 lumen/Watt. CCT of 5700K with SDCM of <5 and CRI>70. The housing should be of non- Corrosive high - pressure die cast aluminum with heat resistant toughened clear glass to with stand extreme environments with PF>0.95. Life time of 50K Hrs @L70. The ingress protection should be minimum IP 66 with IK ratingof 0.7. The luniunaire should have 5 KV internal 10 KV external surge protection in the luminaire. incl takin down old unsv light fittings complete all as specified and directed.
S&F of 60 W LED Street Light luminaire confirmining incliding all necessary arrangemet for fixing on Pole made up SITC of high quality integrated LED street light with a minimum system lumen of 6600 Lm and system wattage not exceeding 60 W with nominal effiiciency 110 lumen/Watt. CCT of 5700K with SDCM of <5 and CRI>70. The housing should be of non- Corrosive high - pressure die cast aluminum with heat resistant toughened clear glass to with stand extreme environments with PF>0.95. Life time of 50K Hrs @L70. The ingress protection should be minimum IP 66 with IK ratingof 0.7. The luniunaire should have 5 KV internal 10 KV external surge protection in the luminaire. incl takin down old unsv light fittings complete all as specified and directed.
S&F of 90 W LED Street Light luminaire confirmining incliding all necessary arrangemet for fixing on Pole made up SITC of high quality integrated LED street light with a minimum system lumen of 9900 Lm and system wattage not exceeding 90 W with nominal effiiciency 110 lumen/Watt. CCT of 5700K with SDCM of <5 and CRI>70. The housing should be of non- Corrosive high - pressure die cast aluminum with heat resistant toughened clear glass to with stand extreme environments with PF>0.95. Life time of 50K Hrs @L70. The ingress protection should be minimum IP 66 with IK ratingof 0.7. The luniunaire should have 5 KV internal 10 KV external surge protection in the luminaire. incl takin down old unsv light fittings complete all as specified and directed.
S&F of 70W LED Flood Light luminaire made up of Matt black ptextured powder coated pressure Die Cast aluminum housing and frame with heat resistant toughened clear glass fixed with SS screw/ Ant dust exposed lens, sturdiness and embossed brand name/ logo name of manufacturer on fixture. The luminaire should have a minimum system lumen output of 10800 lumens and 70 Watts. The fixture shall have a CRI of minimym 70. The fixture shall be designed for a system life of 50000 hours @ 70 % lumen maintenence , Ingress protection of IP 66 (lamp and gear compartement) and Mechanical impact resistance rating of IK>=07. The fixture driver should have an operaing voltage rang of 20-277V, surge protection of 10 KV, PF. 0.95, THD<10% inc taking down old unsv light fittings complete all as specified and directed
S&F of 120W LED Flood Light luminaire made up of Matt black ptextured powder coated pressure Die Cast aluminum housing and frame with heat resistant toughened clear glass fixed with SS screw/ Ant dust exposed lens, sturdiness and embossed brand name/ logo name of manufacturer on fixture. The luminaire should have a minimum system lumen output of 14400 lumens and 120 Watts. The fixture shall have a CRI of minimym 70. The fixture shall be designed for a system life of 50000 hours @ 70 % lumen maintenence , Ingress protection of IP 66 (lamp and gear compartement) and Mechanical impact resistance rating of IK>=07. The fixture driver should have an operaing voltage rang of 20-277V, surge protection of 10 KV, PF. 0.95, THD<10% inc taking down old unsv light fittings complete all as specified and directed
Supply and Fixing in replacement of old burnt constant current driver suitable for following LED security kight/Flood light fitting of 35 to 60 W capaity complete all as specified and directed.
Supply and Fixing in replacement of old burnt constant current driver suitable for following LED security kight/Flood light fitting of 72 to 100 W capaity complete all as specified and directed.
Supply and Fixing in replacement of old burnt constant current driver suitable for following LED security kight/Flood light fitting of 120 to 180 W capaity complete all as specified and directed.
S & F in repair MCB TPN 63 Amp 415 Volts 50 Hz AC 10 KA with necessary lugs incliding lugs, including taking down existing MCB complete all as specified and directed.
Supply and fix aluminium lugs of any type / shape of capacity from 10 Sqmm to 25 Sqmm complete all as specified and directed.
Supply and fix aluminium lugs of any type / shape of capacity from 35 Sqmm to 95 Sqmm complete all as specified and directed.
Supply and fix aluminium lugs of any type / shape of capacity from 120 Sqmm to 240 Sqmm complete all as specified and directed.
M & L for Earthing complete with galvanised steel earth plate electrode 60cmx60cmx6mm thick burried directly in ground vertically to a depth not less than 2.25 metre below ground level with top edge of the earth plate at a depth not less than 1.5 M below ground level, earth plate surrounded by 15cm thick and packed with layers of charcoal dust and common salt , earth lead of galvanised iron strip of size 25x4 mm connectd to GI earth plate elcectrode by means of bolts, nuts, check nuts and washers of galvanised iron and thimbles and other end of earth wire connected to main switch board and protected by galvanised iron pipe medium grade 15mm bore and 20mm bore light gradeGI pipe with funnel and wire mesh for watering including necessary excavation and earth works. PCC Chamber in cement concrete 1:3:6 type C-2 & RCC cover in M-20 (Design mix ) and all as shown in Electrical Plate No. 3 of SSR ( Part-I) of 2009 and testing on completion. complete all as specified and directed.
Supplying and making in renewal straight through joint heat shrinkable type for 1.1 KV grade XLPE cable of sizes 35 to 50 sqmm 3.5 core complete all as specified and directed.
Supplying and making in renewal straight through joint heat shrinkable type for 1.1 KV grade XLPE cable of sizes 70 to 120 sqmm 3.5 core complete all as specified and directed.
M&L for painting to Old LT Panel of different size with Silver Gray synthetic enamelled paint of 2 Coats complete all as specified and directed.
M&L for Repair to Old LT Panel of different size with Welding work and Painting after Repair with Silver Gray synthetic enamelled paint of 2 Coats complete all as specified and directed.
Supply, laying and testing of cable XLPE insulated screened PVC bedded galvanized steel striper wire armoured electric power cable heavy duty with standard aluminium conductor, 1100 volts grade, cross sectional area 3.5 core 95 Sqmm complete all as specified and directed by Engr-in-Charge.
All as per ser No. 43 above but 70 Sqmm 3.5 core
All as per ser No. 43 above but 50 Sqmm 3.5 core
All as per ser No. 43 above but 35 Sqmm 3.5 core
All as per ser No. 43 above but 25 Sqmm 4 core
All as per ser No. 43 above but 16 Sqmm 4 core
All as per ser No. 43 above but 16 Sqmm 2 core
All as per ser No. 43 above but 10 Sqmm 4 core
All as per ser No. 43 above but 10 Sqmm 2 core
All as per ser No. 43 above but 6 Sqmm 2 core
S&F in replacement of MCCB 25 to 100 amp, 4 pole 16KA (Ics=100% Icu) thermally adjustable between 70% to 100% with spreader links on both sides all as specified and directed.
S&F in replacement of MCCB 125 amp, 4 pole, 16KA (Ics=100% Icu) thermally adjustable between 70% to 100% with spreader links on both sides all as specified and directed.
S&F in replacement of MCCB 160 amp, 4 pole, 36 KA (Ics=100% Icu) thermally adjustable between 70% to 100% with spreader links on both sides all as specified and directed.
Supply & fixing of Aluminium conductor, steel reinforced of any size on LT Poles including straining, binding with insulators with Al/copper binding wire with insulators as in OH conductors, providing PVC sleeves for jumper fixed as in repairs complete all as specified and directed.
Labour only for Re-stringing/restretching ACSR aluminium conductor laid over, over head LT line on steel/PCC poles after removing binding from insulator and rewinding the conductor with insulator including providing spacer and neew binding wire jumpering provide with after restranining and removing unavoidable sags in the line and trimming of tree and branches on LT line for main clearance complete all as specified and directed.
Labour and tools for trimming tree branches up to 100 mm grith of any location around existing HT/LT OH lines giving clearance of 1.5 m on all sides after arranging shut down and taking all precaution while working on lines incl all T&P required for the purpose complete all as directed as specified by Engr-in-Charge. The contractor shall arrange the tree cutting machine and vehicle mounted telescopic ladder for the same.
M&L steel tubular swaged pole 09 metre long complete with cast iron base plate finial taper plug, bolts, nuts and secrew all as specified type 410 SP-31 (9.0 metres long) including painting upto 1.5M above PCC coping in black and white strips 5 Nos each 30 CM high starting from botting of pole. The pole shall be coated with two coats of black bituminous paint throughout internally and externally up to the planting depth. The remaining portion of the exterior shall be painted with on coat of red oxidor primer including dismantling of old damaged LT poles of any type and size for taking credit complete all as specified and as directed by Engr-in-Charge
Material and labour for Outdoor type factory made feeder pillar box canopy type of size 0.45 x 0.75 x 0.40 M depth made out of CRCA sheet 3.15 mm thick, suitable 04 Nos busbar size 20 x 5 mm having locking arrangement, provn of suitable hole at bottom for incoming and outgoing UG cables incl painting with 2 coat of powder coated paint over a coat of red oxide promer on exterior and interior faces of Bus bar chamber, errection of Bus bar chamber with PCC 1:2:4 type B2 and fixing and connection including earth work, taking down and provn of suitable frame at bottom made out of angle iron of size 40 x40 x6mm thick complete all as specified and directed by Engineer-in-Charge
Supply & fix 25 x4 Galvanised earth continuity conductor of main earthing lead fixed to wall on batten or recess or cheses or buried in ground of drawn in conduit /pipe or fixed to poles or any outher indicated situation for loop earting etc. as required and directed.
S & F in replacement old broken post top lantern of capacity 20 W energy saving , environmental friendly, long life aestetically designed with symmetrical light distribution spun aluminium land scape luminaire with high power LEDs as light source. The luminare shall be complete IP65 for optical compartement suitable gor working for input voltage range of 140V to 270 V light shall have power factor more than 0.9 with THD less than 10% having lm of 900W incluging complete GI pipe bracket complete all as specified and directed. Make Orient cat part No LLAS-20C or equivalent make as specified in PS
S & F and fix 9 W LED Bollard light fitting with opal arylic diffuser and IP 65 protection power coated squre extruded aluminium housing. Mushroom shape Opal acrylic diffuser is fixed in die cast aluminium frames on four sides for pleasant light output with inbuilt driver with 4.5 kV surge protection. Luminaire is provided with a base plate and fixing holes for directly mounting on the concrete pedestal. LEDs mounted on top die cast aluminium housing and can be separated from base plate for easy maintenance incl taking down old unsv light fittings complete all as specified and directed. Make Orient cat part No LLOBL-10-W or equivalent make as specified in PS
Supplying, installation, testing & commissioning in CPRI approved outdoor cubical type LT of size 1.5Mx1.2Mx0.60M depth,(HxBxD) panel suitable for 415V, 3 phase, 4 wire 50 Hz, AC supply system with short circuit withstand capacity 35 MVA for 1 second, IP 54 protection, fabricated in compartmentalized design with CRCA sheet 3.15 mm thick, factory made, totally enclosed having front and rear openable, powder coated, dust, weather & vermin proof, having TPN aluminium bus bars of rating 1.5 times that of controlling MCCB supported on 'F' class SMC insulators, bottom base channel of MS section not less than 75 mm x 40 mm x 5 mm thick, entire panel shall have a common aluminium earth bar of size 25 mm x 5 mm at the rear with 2 Nos earth stud, solid connections from main bus bar to switchgears with required size bus bars and control wiring with minimum 1.5 sqmm PVC insulated copper conductor cable, cable alleys, cable gland plates including digital multi functional meter to measure voltage, current, PF & frequency and mounted on by making suitable PCC foundation, necessary inter connection including following controls :-
Incoming:- One number MCCB 250 amp, 4 pole, Ics 36 KA, 415 volts, 50 Hz withThermal & Adjustable Magnetic type between 40% to 100% against overload setting. 01 Nos
Outgoing:- (i) One numbers MCCB 160amp, 4 pole, Ics 25 KA, 415 volts, 50 Hz, Thermal & Adjustable Magnetic type between 70% to 100% against overload setting. - 01 Nos
(ii) One numbers MCCB 100amp, 4 pole, Ics 25 KA, 415 volts, 50 Hz, Thermal & Adjustable Magnetic type between 70% to 100% against overload setting. - 01 Nos
(iii) One numbers MCCB 63 amp, 4 pole, Ics 25 KA, 415 volts, 50 Hz, Thermal & Adjustable Magnetic type between 70% to 100% against overload setting. - 01 Nos
M & L for breaking of PCC (for taking out PCC poles) and removing broken PCC outside cantonment area to a distance beyond 5 km but not exceeding 15 km and depositing at a level not exceeding 1.5 m above the starting point complete.
M & L Cutting of road not exceeding 100 CM depth for laying of UG Cable incl make good the surface of road with cement plaster mix 1:2 of suitable quantity, complete all as specified and directed.
M & L Restringing/restretching aluminium conductor on existing over head lines( dismantled including necessary binding with binding wire with insulator , connections of incoming and out going cables complete all as specified and directed.
M & L for cleaning, preparing and painting with one coat of aluminium paint to steel tubular pole 9 mtr long complete with cross arms, MS channels, angle, iron, frame work, etc incl numbering of pole with black enameled paint from stencil, complete all as specified and directed.
S&F in replacement of MCCB 250 amp, 4 pole, 36 KA (Ics=100% Icu) thermally adjustable between 70% to 100% with spreader links on both sides all as specified and directed.
M&L for ACSR conductor of any size for OH lines on poles including stringing & binding complete all as specified and directed.
Material and labour for Outdoor type factory made Bus bar chamber of size 0.45 x 75 x 0.40 M depth made out of CRCA sheet 3.15 mm thick, suitable for 63 AMP Changeover switch 4 pole, 415 volt, 25 KA having locking arrangement, provn of suitable hole at bottom for incoming and outgoing UG cables incl painting with 2 coat of powder coated paint over a coat of red oxide promer on exterior and interior faces of Bus bar chamber, errection of Bus bar chamber with PCC 1:2:4 type B2 and fixing and connection of changeover switch including earth work and provn of suitable frame at bottom made out of angle iron of size 40 x40 x6mm thick complete all as specified and directed by Engineer-in-Charge
Supplying, installation, testing & commissioning in CPRI approved outdoor cubical type LT of size 1.5Mx1.2Mx0.60M depth,(HxBxD) panel suitable for 415V, 3 phase, 4 wire 50 Hz, AC supply system with short circuit withstand capacity 35 MVA for 1 second, IP 54 protection, fabricated in compartmentalized design with CRCA sheet 3.15 mm thick, factory made, totally enclosed having front and rear openable, powder coated, dust, weather & vermin proof, having TPN aluminium bus bars of rating 1.5 times that of controlling MCCB supported on 'F' class SMC insulators, bottom base channel of MS section not less than 75 mm x 40 mm x 5 mm thick, entire panel shall have a common aluminium earth bar of size 25 mm x 5 mm at the rear with 2 Nos earth stud, solid connections from main bus bar to switchgears with required size bus bars and control wiring with minimum 1.5 sqmm PVC insulated copper conductor cable, cable alleys, cable gland plates including digital multi functional meter to measure voltage, current, PF & frequency and mounted on by making suitable PCC foundation, necessary inter connection including following controls :-
Incoming:- One number MCCB 250 amp, 4 pole, Ics 36 KA, 415 volts, 50 Hz withThermal & Adjustable Magnetic type between 40% to 100% against overload setting. 01 Nos
Outgoing:- (i) One numbers MCCB 160amp, 4 pole, Ics 25 KA, 415 volts, 50 Hz, Thermal & Adjustable Magnetic type between 70% to 100% against overload setting. - 01 Nos
(ii) One numbers MCCB 100amp, 4 pole, Ics 25 KA, 415 volts, 50 Hz, Thermal & Adjustable Magnetic type between 70% to 100% against overload setting. - 01 Nos
(iii) One numbers MCCB 63 amp, 4 pole, Ics 25 KA, 415 volts, 50 Hz, Thermal & Adjustable Magnetic type between 70% to 100% against overload setting. - 01 Nos
M&L for Servicing of ceiling fans of capacity 1200/1400mm including taking down from site, dismantling, cleaning, greasing/oiling of bush and bearings, replacement of set of split pins, cotter pins, blade screws and refixing to the existing site after servicing complete all as directed. (Unserviceable parts other than specified in this item if any will be measured seperately).
M&L for Servicing of Exhaust fans of capacity 300mm to 450mm including taking down from site, dismantling, cleaning, greasing/oiling of bush and bearings, replacement of set of split pins, cotter pins, blade screws and refixing to the existing site after servicing complete all as directed . (Unserviceable parts other than specified in this item if any will be measured seperately).
M&L for Rewinding of ceiling fan motor of size 1200mm/1400mm with super enamelled copper winding wire of appropriate gauge and weight affter cutting and removing the burnt existing winding including varnishing heating by providing fresh insulating materials complete.
M&L for Rewinding of exhaust fan/wall monting fan motor of size 300mm with super enamelled copper winding wire of appropriate gauge and weight affter cutting and removing the burnt existing winding including varnishing heating by providing fresh insulating materials .complete all as specified and directed.
All as per Srl Item No-76 above but for exhaust fan of size 400/450 mm of any make complete all as specified.
S&f in replacement ball bearing of ceiling / exhaust fan of any size and make as required with alignment of shaft and testing complete all as specified and directed.
S& F in replacement of AC film capacitor 4.0 mfd, 440 volts suitable for any type ceiling fan/exhaust fan in FR plastic casing including connection complete all as specified and directed.
S& F in replacemen of AC film capacitor 2.5 mfd, 440 volts suitable for any type ceiling fan in FR plastic casing including connection complete all as specified and directed.
Replacement of old unserviceable fan blades made of MS sheet duly powder coated ,of type make and colour as of ceiling fan suitable for 1200mm sweep ceiling fan of any make incl all accessories complete all as specified.
Replacement of Blade assembly of Exhaust fan with fixing hexagonal nut of size 300 to 450mm of any make complete all as specified and directed..
Replacement of iron Frame of exhaust fan 4 way with welded and painted as directed.
M/L Gun metal bush of exhaust fan complete all as specified and directed.
S&f in replacement of rubber reel with a pair of clamp, nuts, bolts, split pins etc suitable for ceiling fan down rods of any size and make as required.complete all as specified and directed.
S&F in replacementl of PVC canopy suitable for ceiling fan of any size and make as required.complete all as specified and directed.
S&F in replacement of PVC insulated and sheathed flexible 3 core cable with copper conductor of size 0.5 sqmmcomplete all as specified and directed.
S&F in replacement of down rod of ceiling fan made of GI pipe medium grade 15 mm bore of length upto 600 mm including cutting, threading, painting complete all as specified and directed.
Taking down of desert cooler fixed at any position, cleaning internally and externally by scraping all scales dirt etc and repairs to desert cooler to check leakage, tightening ( By replacing screws, nuts and bolts etc ) including painting of desert cooler with spray machine with two coats of synthetic enamel hammer tone paint over one coat of red oxide primer, letters, Refixing of the desert cooler after necessary oilling and greasing of fan and water lifting pump complete all specified and directed
Supplying in replacement Fan motor 1/6 HP, 230 volt, single phase for the existing desert cooler complete all specified and directed
Supplying in replacement Water lifting pump, Vertical type,18 watts, 230 volt, 50 C/S, single phase suitable for desert coolers complete all specified and directed
Supplying in replacement Side panel made out of 1.0 mm thick GI sheet, fixed with iron handle suitable for desert coolers of capacity 3000 cfm including two coats of synthetic enamel hammer tone paint over a one coat of red oxide primer on both side of panel complete all specified and directed
Supplying in replacement High density polythene pipe 15 mm dia complete all specified and directed
Supplying in replacement Complete steel body of desert cooler of capacity 3000 cfm duly painted with two coats of synthetic enamel hammer tone paint over one coat of red oxide primer . The body of desert cooler shall be fabricated as under :- ( a ) The top and bottom made out of 1.25 mm thick GI sheet. ( b ) side panels (set of three) made out 1.00 mm thick GI sheet. ( c ) Front grill of suitable size and of approved quality.
Supplying and Replacement Three way water distributor, heavy duty, PVC, including necessary nuts and bolts complete and taking out old distributor complete all specified and directed
Supplying in replacement of capacitor 4 mfd suitable for Desert cooler complete all as specified and directed
Re-wiring of desert cooler with suitable size of copper conductor PVC insulated cable and providing main lead three metre long of 3 core PVC insulated copper conductor of size 23/ .0076 complete all specified and directed
Dismanting and taking out Old, Unservicable fan motor from the desert cooler and Rewinding with supper enamel copper winding wire of suitable size, varnishing etc including replacement of bushes, assembling testing and refixing at the existing site complete all as specified and directed
M& L for fabrication of desert cooler stand made out of MS angle iron 40x40x6mm thick all as per existing size suitable at site incl painting ith two coats of synthetic enameld paint over a coat of red oxide primer coat replacement
Repairs to voltage stabilizer of any make, single phase with input voltage 135 - 190 V and out put voltage 200-240 volt, capacity 5 KVA by dismantling and taking out burnt main transformer and rewinding with super enamelled copper wire of suitable size including varnishing and insulation material etc.complete all as specified and directed
All as per item No 101 above but for capacity 03 KVA
All as per item 101 above but for capacity 01 to 02 KVA
Disconnecting the inlet and outlet connections of the existing Geyser 25/50 Ltr, taking down carefully, cleaning/descaling the blocks both in GI pipes and water heater refixing the bolts by proper grouting in the wall and refixing the water heater in the same or in other places as directed by Engr in charge
S&F in place of unsv PVC connection of any make with (ISI Mark) having10mm dia, 45 cm long with steel reinforcement suitable for hot & cold water geyser outlet supply with 02 Nos of Unions/ cup shaped cover with washers all as directed by Engr-in-charge.
Replacement of unserviceable heating element of geyser 2KW/1.5 KW of any pattern all as specified
Replacement of unserviceable thermostat of geyser 2KW/1.5 KW of any pattern all as specified
S & F in replacement of pressure release valve suitrable for 25/50 ltr electric water heater complete all as specified.
S&F in replacement of U/S apparatus plate of geysers 25/50 litre capacity by brazing not exceeding 5 mm thick complete all as specified and directed.
Replacement of unserviceable Inner Tank of geyser steel body of capaciy 25/50 Ltrs as existing pattern complete all as specified and directed.
Replacement of unserviceable PVC flexible pipe inlet 16mm outer dia and 450 mm long for hot/cold water heavy duty with brass nuts & bolts. complete all as specified and directed.
Disconnecting the inlet and outlet connections of the existing solar water heater 300 Ltr, taking down carefully, cleaning/descaling the blocks both in GI pipes and water heater refixing the bolts by proper grouting in the wall and refixing the water heater in the same or in other places as directed by Engr in charge
Replacement of unserviceable heating element of solar water heater 300 Ltr 2KW/1.5 KW of any pattern all as specified
Replacement of unserviceable thermostat of solar water heater 300 Ltr 2KW/1.5 KW of any pattern complete all as specified and directed.
S&F in replacement of apparatus plate of solar water heater 300 Ltr 25/50 litre capacity by brazing not exceeding 5 mm thickcomplete all as specified and directed.
Replacement of unserviceable float valve with new brass Float valve of desert coolers complete any make 15 mm bore complete all as specified and directed.
M/S KALSI ENGINEERS AND CONTRACTORS (BID ID -3072727)
M/S PRAJAPATI ENGINEERS (BID ID -3080003)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .