Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹9.8 LAccepted-AOC 1ST FLOOR FLAT NO A 104 ANANT EMEGINE PURANA BUS STAND KORBA CHHATTISGARH | KORBA | KORBA | CHHATTISGARH | 495678 | 1 | Accepted-AOC Resultant single bidder and has submitted all confirmatory documents as per NIT. | |
| 2 | Rejected-Technical ETTA BHATTA MAINROAD SURAJPUR BHATGAON SURAJPUR CHHATTISGARH | DURG | CHHATTISGARH | 490001 | - | Rejected-Technical Rejected in technical evaluation as per NIT | |
| 3 | Rejected-Technical 97 INDIRA COMPLEX T P NAGAR KORBA CHHATTISGARH 495677 | KORBA | KORBA | CHHATTISGARH | 495677 | - | Rejected-Technical Rejected in technical evaluation |
| Sl No | Description | Qty | Unit | AARNA Constructions L1 |
|---|---|---|---|---|
| 1.00 | Providing, installation, commissioning, testing of 3 nos. Neutral Grounding Resistor (NGR) with fail safe monitoring relay system (setting of relay in multiple of 1) and other accessories of 6600 Voltage grade suitable for fault current of 10A, 381.1 Ohm rating for use in secondary side:-
1.Non ageing corrosion resistant AISI 304 grade or better stainless steel grid resistance of 381.1 Ohms for 6.6 KV NGR.
2.Solid State earth fault relay.
3.Resin cast HV & LV instrument & Current transformer.
4.Buzzer with all necessary accessories.
5.Floor mounted panel fitted with canopy complete with control wiring circuit.
6.Terminals, insulators wires ferrules tapes.
7.Fail safe monitoring relay and other required relays – NGR will be monitored through fail safe relay i.e. in case of NGR failure or open circuit from transformer neutral end to ground and or earth fault in the system relay will provide trip signal to HT breaker.
8.NGR shall be IP 65 or better for outdoor location | 3 | nos. | 2,50,000 ₹7,50,000 Lowest |
| 2.00 | A)Conducting following routine test for checking healthiness of each transformer though instrument calibrated from NABL accredited Laboratory : -
1.Insulation Test
2.Polarization index Test
3.Winding Resistance Test
4.Turn Ratio Test
5.Magnetic Balance test
6.Voltage Ratio Test
B) Conduct following Oil testing of each transformer from NABL/Govt Lab accredited Laboratory :-
1.Dissolve Gas Analysis (DGA) Test as per Standard IEC 60567 for Transformer oil
2.Break Down Voltage Test as per standard as IS 60156 for Transformer oil
3.Dielectric Dissipation factor ( Tan Delta) as per standard IS 60247 for Transformer oil
4.Specific Resistance as per standard IS 60247 for Transformer oil
5.Neutralization value as per standard IS 62021-1 for Transformer oil
6.Inter facial Tension Test as per standard ASTM D 971/IS 6104 for Transformer oil
7.Flash point test as per standard ASTM D – 6450 for Transformer oil
8.Furan Compounds as per standard IEC 61198 for Transformer oil
9.Sediments and Sludge Test as Per relevant Standard for Transformer oil | 3 | nos. | 27,000 ₹81,000 Lowest |
| 4.00 | Total impact of GST for the purpose of CTC | 1 | Nos | - |
Tender Value
₹9.8 L
EMD Value
₹12,300
Closing Date
19 Sept 2026, 5:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Staff Officer, EnM
Office of the Area General Manager, SECL Gevra Area - 495452
Supply, Installation, and commissioning of 03 Nos 6.6 kV Neutral Grounding Resistor along with routine test of Transformer at 33/6.6/3.3kV Main Substation and Dipka unit Substation under Power Supply of Gevra Project.
2026_SECL_364827_1
SECL/GA/SO ENM/26-27/E-TENDER/59 dt. 03/09/2026
Open Tender
Electrical and Maintenance Works
Item Rate
60 days
Gevra Project
Please refer Tender documents.
5 documents required · 5 mandatory
₹12,300
14 Nov 2026
5 Sept 2026
21 Sept 2026
5 Sept 2026
19 Sept 2026
7 Sept 2026
5 Sept 2026 - 12 Sept 2026
120 days
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Providing, installation, commissioning, testing of 3 nos. Neutral Grounding Resistor (NGR) with fail safe monitoring relay system (setting of relay in multiple of 1) and other accessories of 6600 Voltage grade suitable for fault current of 10A, 381.1 Ohm rating for use in secondary side:-
1.Non ageing corrosion resistant AISI 304 grade or better stainless steel grid resistance of 381.1 Ohms for 6.6 KV NGR.
2.Solid State earth fault relay.
3.Resin cast HV & LV instrument & Current transformer.
4.Buzzer with all necessary accessories.
5.Floor mounted panel fitted with canopy complete with control wiring circuit.
6.Terminals, insulators wires ferrules tapes.
7.Fail safe monitoring relay and other required relays – NGR will be monitored through fail safe relay i.e. in case of NGR failure or open circuit from transformer neutral end to ground and or earth fault in the system relay will provide trip signal to HT breaker.
8.NGR shall be IP 65 or better for outdoor location | 3 | nos. | 2,50,000 | ₹7,50,000 |
| 2 | A)Conducting following routine test for checking healthiness of each transformer though instrument calibrated from NABL accredited Laboratory : -
1.Insulation Test
2.Polarization index Test
3.Winding Resistance Test
4.Turn Ratio Test
5.Magnetic Balance test
6.Voltage Ratio Test
B) Conduct following Oil testing of each transformer from NABL/Govt Lab accredited Laboratory :-
1.Dissolve Gas Analysis (DGA) Test as per Standard IEC 60567 for Transformer oil
2.Break Down Voltage Test as per standard as IS 60156 for Transformer oil
3.Dielectric Dissipation factor ( Tan Delta) as per standard IS 60247 for Transformer oil
4.Specific Resistance as per standard IS 60247 for Transformer oil
5.Neutralization value as per standard IS 62021-1 for Transformer oil
6.Inter facial Tension Test as per standard ASTM D 971/IS 6104 for Transformer oil
7.Flash point test as per standard ASTM D – 6450 for Transformer oil
8.Furan Compounds as per standard IEC 61198 for Transformer oil
9.Sediments and Sludge Test as Per relevant Standard for Transformer oil | 3 | nos. | 27,150 | ₹81,450 |
| 4 | Total impact of GST for the purpose of CTC | 1 | Nos | - | - |
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.05 MB
Tendernotice_1.pdf
PDF • 1.43 MB
Tendernotice_2.pdf
PDF • 0.82 MB
BOQ_377811.xls
BOQ • 0.25 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart shows the information on this page on a best-effort basis and does not guarantee that it is accurate, complete or current. Check it against the buyer's official notice and documents before you act on it; the official record prevails. TenderKart is not liable for any loss or claim arising from the use of this information. If you notice any error or omission, please let us know at .