| 1 | L1₹48.0 LAccepted-AOC 43 VIMAL ENCLAVE CHAMRAULI MODE SHAMSHABAD ROAD AGRA UP 282001 | AGRA | AGRA | UTTAR PRADESH | 282001 | L1 | Accepted-AOC BEING LOWEST REASONABLE BIDDER | |
| 2 | L2₹59.9 L+₹11.0 L (22.4%)Rejected-Finance PLOT NO 37 BADANPUR OLD SER NO 34658 NEAR SAI BARAT PALACE PAWAN BHUMI SHAKTI NAGAR JABALPUR MADHYA PRADESH 482001 | JABALPUR | MADHYA PRADESH | 482001 | L2 | Rejected-Finance OTHER THAN LOWEST BIDDER |
| Sl No | Description | Qty | Unit | S S TRADERS L1 | Zamzam Refrigeration and airconditioning L2 |
|---|---|---|---|---|---|
| 1.00 | Comprehensive periodic maintenance, repair & servicing of central Air Conditioning Plant of Make : Carrier of capacity (3 x 175) TR model:30 HXC 190 A and ventilation system existing at Military Hospital Jabalpur as per manufacturers instructions and as directed by Engr-in-Charge :-
Main equipments to be maintained/ serviced are listed below :-
(a) Preventive and comprehensive repair, maintenance, servicing through authorised dealer of company for 3 Nos of chilling machine of screw type compressor 350 TR, (3x175)TR each single stage, 3000 RPM, 415 Volts, 3 Phase, 50 Hz, semihermatic electric motor of capacity 80 KW, shell and tube type condensor with carbon steel plate, copper tube, externally and internally to pass water flow 1400 USG/ PM, including carbon plate shell and tube flooded type chiller unit working with microprocessor based controls in sheet metal control panel etc
Make : M/s Carrier Co.
Note:- Refrigerant and compressor oil as and when in the opinion of Engr-in-Charge is required to be replaced, same shall be replaced immediately and cost of the same shall be deemed to be included in the unit rates quoted by the contractor.
(b) Other associates parts/accessories :-
(i) Condensing pump set with motor of capacity 30 KW/40 HP, 1450 RPM, 50Hz, pump head 26.5 Mtr - 02 Sets (Motor of make ALSTOM and Pump of make Kirloskar). Descalling by Descalling pump and using Carrier approved chemical for mechanical descalling. | 4 | Each Job | 1,20,000 ₹4,80,000 Lowest | 2,25,000 ₹9,00,000 |
| 1.10(ii) Chiller motor pump set complete of capacity 30 KW/ 40 HP, 1450 RPM, 50Hz, total head of pump 26.5 Mtr- 02 Sets (Motor of make : ALSTOM and Pump of make : Kirloskar) (iii) FRP cooling tower including lubrication and servicing of mechanical transmission and repair and pluging of leakages with FRP patches to bottom tank of cooling tower complete with electric motor of capacity 7.5 KW, 1460 RPM, 415Volt -02 Sets (Tower model: 9081 of make- Mihir, Electric motor of make- Navyug) (iv) Condensor water pipe line of size 300mm dia to 450mm dia complete with butterfly valve 50mm to 200mm dia of make: Kirloskar, strainer including cost of repair/ replacement of chiller/ hot water pipe less than 100mm dia and accessories complete all as per requirement. (v) AHU complete with accessories i.e. blower with casing, chilled water coil, hotwater coil, filter, filter frame drive motor, humidification kit, mortise motor control panel including lubrication and servicing of mechanical transmission etc as required. Note:- Spares shall be measured and paid for separately under relevant item of Sch'A'/ BOQ. (vi) Fan ventilation system with fan motor of capacity 2.2 KW, drive package and vibration pad installed at basement of AHU of MH, Jabalpur. (vii) Makeup/ expansion tank of capacity 5000 Ltrs of PVC of make- Sintex complete with inlet/ outlet GI pipes, PTMT float valves, installed on the roof of the plant room and Hospital bulding - 02 Sets | |||||
| 1.20(viii) Control desk remote to control the AHU panel of 6 Nos AHUs located in different ward/ department in MH Jabalpur complete including replacement of control wiring with and including copper wire of existing type and size of make as approved by GE and replacement of indicating lamp of existing make complete installed at main AC plant room etc Note:- Control wiring, switches and lamps as and when in the opinion of Engr-in-Charge is required to be replaced, same shall be replaced immediately and cost of the same shall be deemed to be included in the unit rates quoted by the contractor. (ix) Mono block pump set of capacity 1.0 HP, 2700 RPM, head 17 to 23 Mtr including suction/ discharge pipe line and electric connection of type KDC 128 pump of make Kirloskar for taking out the inside flow water of the plant room. | |||||
| 1.30(x) LT panel including all accessories and wiring of LT cable for exhaust/ blower control of industrial type installed at main AC plant room including blower fan heavy duty , MS impeller , blower fan and blower shaft with electric motor 10 HP. (xi) Hot water generator of capacity 800 KW with monoblock pump set, AC 415 volts, 50 Hz, 2900 RPM, 10 HP of total head 30 Mtr, 23 LPS with all accessories - 02 Sets (xii) Butterfly motorised valve with actuator gate valves etc. (xiii) Descaling of condenser units (minimum twice during Contract Period). c) Make & model of the any part of the plant which are required to be replaced, shall be the same as per existing one at site or as per OEM . (d) Comprehensive/ periodic maintenance means to ensure the optimum functioning of AC plant by synchronising the entire assembly to produce desired temperature, humidity and duct filteration levels without any extra cost. (e) Periodic maintenance shall take place at every 03 months or as directed by GE. | |||||
| 1.40(f) During entire contract period any defective components and/or any other materials which is not specified/ given in Sch'A'/ BOQ but same is necessary to repair/ replace to make the plant/ machines fully functional, the cost of the same shall be deemed to be included in the unit rates quoted by the contractor and no extra payment shall be made to the contractor on this account. (g) The cost of transportation and other necessary equipment shall be arranged/ brought by the contractor to complete the job and no extra payment shall be made to the contractor on this account. Hence, bidders are advised to visit the site to assess the quantum of work to be carried out in this contract before quoting their rates. (h) Contractor shall responsible for maintaining the temperature & humidity to the required level inside the bldg/ shed, failing which a recovery of Rs. 1000.00 per day per plant on account of penalty shall be made from the contractor's dues/ payment . | |||||
| 2.00 | Comprehensive periodic maintenance, repair & servicing of central Air Conditioning Plant of Make : Blue Star of capacity 3 x 300 TR model: LCW2-320X07X056969 and ventilation system existing at Military Hospital Jabalpur as per manufacturers instructions and as directed by Engr-in-Charge :-
Main equipments to be maintained/ serviced are listed below :-
(a) Preventive and comprehensive repair, maintenance, servicing through authorised dealer of company for 3 Nos of chilling machine of screw type compressor , 3x 300 TR each single stage, 3000 RPM, 415 Volts, 3 Phase, 50 Hz, shell and tube type condensor with carbon steel plate, copper tube, externally and internally to pass water flow 1400/2000 USG/ PM, including carbon plate shell and tube flooded type chiller unit working with microprocessor based controls in sheet metal control panel etc
Make : M/s BLUESTAR.
Note:- Refrigerant and compressor oil shall be replaced immediately and cost of the same shall be deemed to be included in the unit rates quoted by the contractor complete all as specified and directed by Engineer-in-Charge. | 4 | Each Job | 1,40,000 ₹5,60,000 Lowest | 2,25,000 ₹9,00,000 |
| 2.10(b) Other connected parts/accessories :- (i) Condensing pump set with motor of capacity 30 KW/40 HP, 1450 RPM, 50Hz, 03 Sets make : BHARAT BIJALI. (ii) Chiller motor pump set complete of capacity 30 KW/ 25 HP, 1450 RPM, 50Hz, 03 Sets make : BHARAT BIJALI. (iii) FRP cooling tower including lubrication and servicing of mechanical transmission and repair and pluging of leakages with FRP patches to bottom tank of cooling tower complete with electric motor of capacity upto 5.0 HP, 1400/1500 RPM, 415Volt -01 Sets (of suitable tower model required at site). (iv) Condensor water pipe line of size 100mm dia to 400mm dia complete with butterfly valve 50mm to 200mm dia of make: Kirloskar, strainer including cost of repair/ replacement of chiller/ hot water pipe less than 100mm dia and accessories complete all as per requirement at site. (v) AHU complete with accessories i.e. blower with casing, chilled water coil, hotwater coil, filter, filter frame drive motor, humidification kit, mortise motor control panel including lubrication and servicing of mechanical transmission etc as required. Note:- Spares shall be measured and paid for separately under relevant item of Sch'A'/ BOQ. | |||||
| 2.20(vi) Fan ventilation system with of fan motor of capacity upto 5 HP, drive package and vibration pad installed at basement of AHU of MH, Jabalpur. (vii) Makeup/ expansion tank of capacity 5000 Ltrs of PVC of make- Sintex complete with inlet/ outlet GI pipes, PTMT float valves, installed on the roof of the plant room and Hospital bulding - 02 Sets (viii) Control desk remote to control the AHU panel of 6 Nos AHU`s located in different ward/ department in MH Jabalpur complete including replacement of control wiring with and including copper wire of existing type and size of make as approved by GE and replacement of indicating lamp of existing make complete installed at main AC plant room etc Note:- Control wiring, switches and lamps as and when, in the opinion of Engr-in-Charge, is required to be replaced, same shall be replaced immediately and cost of the same shall be deemed to be included in the unit rate quoted by the contractor. (ix) Mono block pump set of capacity 1.0 HP, 2700 RPM, head 17 to 23 Mtr including suction/ discharge pipe line and electric connection of type KDC 128 pump of make Kirloskar for taking out the inside flow water of the plant room. | |||||
| 2.30(x) LT panel including all accessories and wiring of LT cable for exhaust/ blower control of industrial type installed at main AC plant room including blower fan heavy duty , MS impellar , blower fan and blower shaft with electric motor 10 HP. (xi) Hot water generator of capacity 320 KW with monoblock pump set, AC 415 volts, 50 Hz, 2900 RPM, 10 HP of total head 30 Mtr, 23 LPS with all accessories - 02 Sets (xii) Butterfly motorised valve with actuator gate valves etc. (xiii) Descaling of condenser units (minimum twice during Contract Period). (c) Make & model of the any part of the plant which are required to be replaced, shall be the same as per existing one at site or as per OEM. (d) Comprehensive/ periodic maintenance means to ensure the optimum functioning of AC plant by synchronising the entire assembly to produce desired temperature, humidity and duct filteration levels without any extra cost. | |||||
| 2.40(e) Periodic maintenance shall take place at every 03 months or as directed by GE. (f) During entire contract period any defective components and/or any other materials which is not specified/ given in Sch'A'/ BOQ but same is necessary to repair/ replace to make the plant/ machines fully functional, the cost of the same shall be deemed to be included in the unit rates quoted by the contractor and no extra payment shall be made to the contractor on this account. (g) The cost of transportation and other necessary equipment shall be arranged/ brought by the contractor to complete the job and no extra payment shall be made to the contractor on this account. Hence, bidders are advised to visit the site to assees the quantum of work to be carried out in this contract before quoting their rates. (h) Contractor shall responsible for maintaining the temperature & humidity to the required level inside the bldg/ shed, failing which a recovery of Rs. 1000.00 per day per plant on account of penalty shall be made from the contractor's dues/ payment . | |||||
Tender Value
₹60 L
EMD Value
₹1.2 L
Closing Date
20 Dec 2025, 6:00 pmClosed
CWE JABALPUR
HQ COMMANDER WORKS ENGINEER, SUPPLY MARG, P B NO. 54, JABALPUR - 482001
COMPREHENSIVE MAINTENACE OF CENTRAL AC PLANT OF MILITARY HOSPITAL OF PH-II AND PH-III AND STATION MDC UNDER GE (WEST) JABALPUR
2025_MES_740900_1
81153/E8
Open Tender
Miscellaneous Works
Item Rate
180 days
JABALPUR
As per NIT
7 documents required · 7 mandatory
₹1,000
GE (WEST) JABALPUR
₹1.2 L
Yes
18 Mar 2026
21 Nov 2025
27 Dec 2025
21 Nov 2025
20 Dec 2025
13 Dec 2025
21 Nov 2025 - 12 Dec 2025
(ii) Chiller motor pump set complete of capacity 30 KW/ 40 HP, 1450 RPM, 50Hz, total head of pump 26.5 Mtr- 02 Sets (Motor of make : ALSTOM and Pump of make : Kirloskar) (iii) FRP cooling tower including lubrication and servicing of mechanical transmission and repair and pluging of leakages with FRP patches to bottom tank of cooling tower complete with electric motor of capacity 7.5 KW, 1460 RPM, 415Volt -02 Sets (Tower model: 9081 of make- Mihir, Electric motor of make- Navyug) (iv) Condensor water pipe line of size 300mm dia to 450mm dia complete with butterfly valve 50mm to 200mm dia of make: Kirloskar, strainer including cost of repair/ replacement of chiller/ hot water pipe less than 100mm dia and accessories complete all as per requirement. (v) AHU complete with accessories i.e. blower with casing, chilled water coil, hotwater coil, filter, filter frame drive motor, humidification kit, mortise motor control panel including lubrication and servicing of mechanical transmission etc as required. Note:- Spares shall be measured and paid for separately under relevant item of Sch'A'/ BOQ. (vi) Fan ventilation system with fan motor of capacity 2.2 KW, drive package and vibration pad installed at basement of AHU of MH, Jabalpur. (vii) Makeup/ expansion tank of capacity 5000 Ltrs of PVC of make- Sintex complete with inlet/ outlet GI pipes, PTMT float valves, installed on the roof of the plant room and Hospital bulding - 02 Sets
(viii) Control desk remote to control the AHU panel of 6 Nos AHUs located in different ward/ department in MH Jabalpur complete including replacement of control wiring with and including copper wire of existing type and size of make as approved by GE and replacement of indicating lamp of existing make complete installed at main AC plant room etc Note:- Control wiring, switches and lamps as and when in the opinion of Engr-in-Charge is required to be replaced, same shall be replaced immediately and cost of the same shall be deemed to be included in the unit rates quoted by the contractor. (ix) Mono block pump set of capacity 1.0 HP, 2700 RPM, head 17 to 23 Mtr including suction/ discharge pipe line and electric connection of type KDC 128 pump of make Kirloskar for taking out the inside flow water of the plant room.
(x) LT panel including all accessories and wiring of LT cable for exhaust/ blower control of industrial type installed at main AC plant room including blower fan heavy duty , MS impeller , blower fan and blower shaft with electric motor 10 HP. (xi) Hot water generator of capacity 800 KW with monoblock pump set, AC 415 volts, 50 Hz, 2900 RPM, 10 HP of total head 30 Mtr, 23 LPS with all accessories - 02 Sets (xii) Butterfly motorised valve with actuator gate valves etc. (xiii) Descaling of condenser units (minimum twice during Contract Period). c) Make & model of the any part of the plant which are required to be replaced, shall be the same as per existing one at site or as per OEM . (d) Comprehensive/ periodic maintenance means to ensure the optimum functioning of AC plant by synchronising the entire assembly to produce desired temperature, humidity and duct filteration levels without any extra cost. (e) Periodic maintenance shall take place at every 03 months or as directed by GE.
(f) During entire contract period any defective components and/or any other materials which is not specified/ given in Sch'A'/ BOQ but same is necessary to repair/ replace to make the plant/ machines fully functional, the cost of the same shall be deemed to be included in the unit rates quoted by the contractor and no extra payment shall be made to the contractor on this account. (g) The cost of transportation and other necessary equipment shall be arranged/ brought by the contractor to complete the job and no extra payment shall be made to the contractor on this account. Hence, bidders are advised to visit the site to assess the quantum of work to be carried out in this contract before quoting their rates. (h) Contractor shall responsible for maintaining the temperature & humidity to the required level inside the bldg/ shed, failing which a recovery of Rs. 1000.00 per day per plant on account of penalty shall be made from the contractor's dues/ payment .
(b) Other connected parts/accessories :- (i) Condensing pump set with motor of capacity 30 KW/40 HP, 1450 RPM, 50Hz, 03 Sets make : BHARAT BIJALI. (ii) Chiller motor pump set complete of capacity 30 KW/ 25 HP, 1450 RPM, 50Hz, 03 Sets make : BHARAT BIJALI. (iii) FRP cooling tower including lubrication and servicing of mechanical transmission and repair and pluging of leakages with FRP patches to bottom tank of cooling tower complete with electric motor of capacity upto 5.0 HP, 1400/1500 RPM, 415Volt -01 Sets (of suitable tower model required at site). (iv) Condensor water pipe line of size 100mm dia to 400mm dia complete with butterfly valve 50mm to 200mm dia of make: Kirloskar, strainer including cost of repair/ replacement of chiller/ hot water pipe less than 100mm dia and accessories complete all as per requirement at site. (v) AHU complete with accessories i.e. blower with casing, chilled water coil, hotwater coil, filter, filter frame drive motor, humidification kit, mortise motor control panel including lubrication and servicing of mechanical transmission etc as required. Note:- Spares shall be measured and paid for separately under relevant item of Sch'A'/ BOQ.
(vi) Fan ventilation system with of fan motor of capacity upto 5 HP, drive package and vibration pad installed at basement of AHU of MH, Jabalpur. (vii) Makeup/ expansion tank of capacity 5000 Ltrs of PVC of make- Sintex complete with inlet/ outlet GI pipes, PTMT float valves, installed on the roof of the plant room and Hospital bulding - 02 Sets (viii) Control desk remote to control the AHU panel of 6 Nos AHU`s located in different ward/ department in MH Jabalpur complete including replacement of control wiring with and including copper wire of existing type and size of make as approved by GE and replacement of indicating lamp of existing make complete installed at main AC plant room etc Note:- Control wiring, switches and lamps as and when, in the opinion of Engr-in-Charge, is required to be replaced, same shall be replaced immediately and cost of the same shall be deemed to be included in the unit rate quoted by the contractor. (ix) Mono block pump set of capacity 1.0 HP, 2700 RPM, head 17 to 23 Mtr including suction/ discharge pipe line and electric connection of type KDC 128 pump of make Kirloskar for taking out the inside flow water of the plant room.
(x) LT panel including all accessories and wiring of LT cable for exhaust/ blower control of industrial type installed at main AC plant room including blower fan heavy duty , MS impellar , blower fan and blower shaft with electric motor 10 HP. (xi) Hot water generator of capacity 320 KW with monoblock pump set, AC 415 volts, 50 Hz, 2900 RPM, 10 HP of total head 30 Mtr, 23 LPS with all accessories - 02 Sets (xii) Butterfly motorised valve with actuator gate valves etc. (xiii) Descaling of condenser units (minimum twice during Contract Period). (c) Make & model of the any part of the plant which are required to be replaced, shall be the same as per existing one at site or as per OEM. (d) Comprehensive/ periodic maintenance means to ensure the optimum functioning of AC plant by synchronising the entire assembly to produce desired temperature, humidity and duct filteration levels without any extra cost.
(e) Periodic maintenance shall take place at every 03 months or as directed by GE. (f) During entire contract period any defective components and/or any other materials which is not specified/ given in Sch'A'/ BOQ but same is necessary to repair/ replace to make the plant/ machines fully functional, the cost of the same shall be deemed to be included in the unit rates quoted by the contractor and no extra payment shall be made to the contractor on this account. (g) The cost of transportation and other necessary equipment shall be arranged/ brought by the contractor to complete the job and no extra payment shall be made to the contractor on this account. Hence, bidders are advised to visit the site to assees the quantum of work to be carried out in this contract before quoting their rates. (h) Contractor shall responsible for maintaining the temperature & humidity to the required level inside the bldg/ shed, failing which a recovery of Rs. 1000.00 per day per plant on account of penalty shall be made from the contractor's dues/ payment .
water flow 17.4 m3/Hr, and heat source side water flow 21.7 m3/ Hr including carbon plate shell and tube flooded type chiller unit complete all as specified and directed by engineer in charge. Make : M/s DAIKIN. Note:- Refrigerant and compressor oil shall be replaced immediately and cost of the same shall be deemed to be included in the unit rates quoted by the contractor complete all as specified and directed by Engineer in Charge.
(b) Other connected parts/accessories :- (i) Condensing pump set with motor of capacity 30 KW/40 HP, 1450 RPM, 50Hz, pump head 26.5 Mtr - 02 Sets (Motor of make ALSTOM and Pump of make Kirloskar/as required at site). (ii) Chiller motor pump set complete of capacity 30 KW/ 40 HP, 1450 RPM, 50Hz, total head of pump 26.5 Mtr- 02 Sets (Motor of make : ALSTOM and Pump of make : Kirloskar/as required at site) (iii) FRP cooling tower including lubrication and servicing of mechanical transmission and repair and pluging of leakages with FRP patches to bottom tank of cooling tower complete with electric motor of capacity upto 5.0 HP, 1400/1500 RPM, 415Volt -01 Sets (of suitable tower model required at site). (iv) Condensor water pipe line of size 100mm dia to 400mm dia complete with butterfly valve 50mm to 200mm dia of make: Kirloskar, strainer including cost of repair/ replacement of chillar/ hot water pipe less than 100mm dia and accessories complete all as per required at site. (v) AHU complete with accessories i.e. blower with casing, chilled water coil, hotwater coil, filter, filter frame drive motor, humidification kit, mortise motor control panel including lubrication and servicing of mechanical transmission etc as required. Note:- Spares shall be measured and paid for separately under relevant item of Sch'A'/ BOQ.
(vi) Fan ventilation system with fan motor of capacity upto 5 HP, drive package and vibration pad installed at basement of AHU of MH, Jabalpur. (vii) Makeup/ expansion tank of capacity 5000 Ltrs of PVC of make- Sintex complete with inlet/ outlet GI pipes, PTMT float valves, installed on the roof of the plant room and Hospital bulding - 02 Sets (viii) Control desk remote to control the AHU panel of 6 Nos AHU`s located in different ward/ department in MH Jabalpur complete including replacement of control wiring with and including copper wire of existing type and size of make as approved by GE and replacement of indicating lamp of existing make complete installed at main AC plant room etc Note:- Control wiring, switches and lamps as and when, in the opinion of Engr-in-Charge, is required to be replaced, same shall be replaced immediately and cost of the same shall be deemed to be included in the unit rate quoted by the contractor. (ix) Mono block pump set of capacity 1.5 HP, 200/2700 RPM, head 15 to 23 Mtr including suction/ discharge pipe line of make Kirloskar for taking out the inside flow water of the plant room.
(x) LT panel including all accessories and wiring of LT cable for exhaust/ blower control of industrial type installed at main AC plant room including blower fan heavy duty , MS impeller , blower fan and blower shaft with electric motor upto 10 HP. (xi) Hot water generator of capacity upto 200 KW with monoblock pump set, AC 415 volts, 50 Hz, 2900 RPM, 5 HP of total head upto 30 Mtr, 23 LPS with all accessories - 02 Sets (xii) Butterfly motorised valve with actuator gate valves etc. (xiii) Descaling of condenser units (minimum twice during Contract Period). (c) Make & model of the any part of the plant which are required to be replaced, shall be the same as per existing one at site or as per OEM . (d) Comprehensive/ periodic maintenance means to ensure the optimum functioning of AC plant by synchronising the entire assembly to produce desired temperature, humidity and duct filteration levels without any extra cost.
Supply only Cloth Micro Filter Size : 587.50 x 487.50 as per existing one to be fixed under item No. 01 /02/03 here-in-before complete all as specified and directed..
S&F in replacement Star delta Electronic Timer suitable for existing make or model all as specified and directed.
S&F in replacement of power contactor 3TS3700-0B.4-8K 32-50 Amp all as specified and directed Make siemens/L&T/TC /KCI
S&F in replacement Contactor 3TS3400-0A-8K 32-42 Amp all as specified and directed Make siemens/L&T/TC
S&F in replacement Contactor 3TS32 10-OA..8K 25-32 Amp all as specified and directed Make siemens/L&T/TC
S&F Sprinkler set complete As per specification Main Pipe OD 140 mm Branch Pipe OD 75 x 1500 mm Complete with reducer and steel leg all as specified and directed (i) Round Distributor 01 nos. (ii) Tie Rod 04 Nos. (iii) Turn Buckle 04 Nos. (iv) GI Clamp 08 Nos. (v) Distributor Cap 01 Nos
Supply only V belt 'B' section of size A-47 as per existing one to be fixed under item No. 01 /02/03 here-in-before complete all as specified and directed..
S&F Compressor motor protector relay for bluestar compressor 3 x 300 TR, Model: LCW2-320X07X056969 ( Make :Blue Star ) complete all as specified and directed. Make hony well
S&F oil Heater suitable for compressor 3 x 300 TR, Model: LCW2-320X07X056969 ( Make :Blue Star ) complete all as specified and directed.
S&F oill level Switch suitable for compressor 3 x 300 TR, Model: LCW2-320X07X056969 ( Make :Blue Star ) complete all as specified and directed.
Supply and fixing, in replacement, Water temperature sensor with sensor cable of central Air Conditioning Plant of Make : Carrier /Blue Star at Military Hospital Jabalpur as per existing make/ as per manufacturer's recommendations duly approved by GE after taking out the old unserviceable temperature sensor with sensor cable complete all as specified & directed.
S&F in Framed brackets of angles or tees with web and flanges cut to shape, drilled and countersunk for screw, including bending and welding angles, as necessary,gusset plates, riveting, etc. all as specified and directed.
Supply and fixing of painting of MS pipe up to 150mm dia with one coat of existing colour paint after preparation of surfaces all as specified and directed.
M&L for painting for outer and inner steel/iron surface with applying two coats of synthetic enamel paint after preparation of new surface complete all as specified and directed.
Each Set
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.92 MB
TENDER1.pdf
Tender Documents • 2.22 MB
BOQ_829632.xls
BOQ • 0.42 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .