Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹2.1 CrAccepted-AOC 128 BOMMASANDRA INDUTSRIAL AREA JIGANI LINK ROAD NEAR TIMES OF INDIA BANGALORE KARNATAKA 560099 UDYAM KR 03 0377101 | BENGALURU URBAN | KARNATAKA | 560099 | ₹2.1 Cr | L1 | Accepted-AOC Technically qualified and financially lowest Bid |
| 2 | L2₹2.1 CrRejected-Finance | ₹2.1 Cr | L2 | Rejected-Finance Quoted rate higher than L1 |
| 3 | L3₹2.1 CrRejected-Finance | ₹2.1 Cr | L3 | Rejected-Finance Quoted rate higher than L1 |
| Sl No | Description | Qty | Unit | ANU ELECTRICALS L1 | Maruthi Electricals L2 | Swastik Eelectricals L3 |
|---|---|---|---|---|---|---|
| 1.00External Electrification Works of Railway Staff Quarters and Other Service Buildings at Hassan, in connection with Railway Electrification works of Mysuru-Hassan-Mangalore section of South Western Railway. | ||||||
| 2.00 | Amount after unconditional rebate | 1 | Nos | 0 ₹2.1 Cr | 0 ₹2.1 Cr | 0 ₹2.1 Cr |
Tender Value
Refer Docs
EMD Value
₹3.8 L
Closing Date
9 Mar 2026, 11:00 amClosed
General Manager
General Manager/Civil RITES Ltd 5th Floor Industry House 45 Fairfield Layout Race course road Bengaluru 560001
Please refer tender document
2026_RITES_268763_1
RITES/BLR/HASMAQ/EXTELE/LT
Limited
Electrical Works
270 days
Hassan
Please refer tender document
4 documents required · 4 mandatory
₹8,260
Payable To RITES Ltd
₹3.8 L
21 Apr 2026
25 Feb 2026
10 Mar 2026
25 Feb 2026
9 Mar 2026
2 Mar 2026
25 Feb 2026 - 2 Mar 2026
External Electrification Works of Railway Staff Quarters and Other Service Buildings at Hassan, in connection with Railway Electrification works of Mysuru-Hassan-Mangalore section of South Western Railway.
Amount after unconditional rebate
Item Rate BoQ
BoQ_Ver4.0
NIT No. RITES/BLR/HAS-MAQ/EXT-ELE/LT/2026
Name of the Bidder/ Bidding Firm / Company :
PRICE SCHEDULE (This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only)
NUMBER #
Total Of BOQ 3, BOQ 4, BOQ 5 and BOQ 6
SCHEDULE -"A" DSR 2025 Electrical Items
SCHEDULE -"B" KPWD SR 2023-24 - Electrical Items
SCHEDULE - "C" Market Rate - Electrical Items
SCHEDULE - "D" DSR 2023 Civil Items
Percentage BoQ At Par
BoQ_Ver4.0
NIT No. RITES/BLR/HAS-MAQ/EXT-ELE/LT/2026
Name of the Bidder/ Bidding Firm / Company :
PRICE SCHEDULE -"A" DSR 2025 Electrical Items (This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only )
NUMBER #
Part A - DSR 2025 - Electrical Items
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required.
Group C
Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.
2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire
2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
4 X 6 sq. mm + 2 X 6 sq. mm earth wire
Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)
12 way , Double door
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Single pole
Double pole
Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc. as required.
6 Module (200mmX75mm)
8 Module (125mmX125mm)
Supplying and fixing following modular switch / socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.
5/6 A switch
15/16 A switch
3 pin 5/6 A socket outlet
6 pin 15/16 A socket outlet
Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required.
Supplying and fixing brass batten/ angle holder including connection etc. as required.
Installation, Testing and Commissioning of ceiling fan, including wiring the down rods of standard length (upto 30 cm) with 1.5 sq. mm FRLS/HFFR PVC insulated, copper conductor, single core cable etc. as required.
LED Batten light (System lumen efficacy >135 lm/Watt) Supplying, installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85% ,Operating voltage AC 140- 270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, Flicker free (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy >135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminium Body (Thickness > 1.20 mm)
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.
Above 120 sq. mm and upto 400 sq. mm
Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench etc as required.
Above 120 sq. mm and upto 400 sq. mm
Supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required:
Supplying and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.
Upto 35 sq. mm
Above 35 sq. mm and upto 95 sq. mm
Above 95 sq. mm and upto 185 sq. mm
Above 185 sq. mm and upto 400 sq. mm
Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench etc as required.
Upto 35 sq. mm
Above 95 sq. mm and upto 185 sq. mm
Above 185 sq. mm and upto 400 sq. mm
Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.I. plate with inscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixing the same in ground as required.
Supplying and making straight through joint with heat shrinkable kit including ferrules and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
4 X 16 sq. mm
3½ X 50 sq. mm
3½ X 95 sq. mm
3½ X 120 sq. mm
3½ X 185 sq. mm
3½ X 300 sq. mm
Providing, laying and fixing following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep)and re-filling etc a required
100 mm dia
Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. in the existing trench, complete as required.
63 mm dia (OD-63 mm & ID-51 mm nominal)
120 mm dia (OD-120 mm & ID-103 mm nominal)
160 mm dia (OD-160 mm & ID-135 mm nominal)
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 Meter long etc. with charcoal/ coke and salt as required.
Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 Meter long etc. with charcoal/ coke and salt as required.
Percentage BoQ At Par
BoQ_Ver4.0
NIT No. RITES/BLR/HAS-MAQ/EXT-ELE/LT/2026
Name of the Bidder/ Bidding Firm / Company :
PRICE SCHEDULE -"B" KPWD SR 2023-24 -Electrical Items (This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only )
NUMBER #
Part B - KPWD SR 2023-24 -Electrical Items
Supply of LED Streetlight luminaire with pressure die cast aluminium housing body for optimal thermal dissipation. Lamp compartment comprising of anti glare clear diffuser with Injection moulded polycarbonate material, delivering superior light output Rated life Burning Hrs 50000 hr @ Lumen Maintenance of 70%, maximum light intensity should be between 60 degrees to 70 degrees. CCT > 5500K, IP66 optical and electrical compartment & impact resistance of complete luminaire > IK08. Power Factor >0.9 with mains, Surge Protection- Min 5KV along with Over voltage/ Overload, short circuit/ miss-wiring protection. Compatible for pole mounting with outer dia of 40mm to 50mm. Universal Voltage driver to operate wide voltage range from 100V to 270V 50/60Hz application. Compliance to IS 10322/IEC 60598, LM 79 & LM 80 Adherence with RoHS. UL approved MCPCB. Top access street light with single screw to ensure ease of maintenance at the sight site location with minimized minimal tools. LED Light fixture with ........W System Power consumption. LED Efficiency>1301m/w, nominal CRI >75. Luminaire manufacturer should have in-house facility accredited by NABL/CPRI & any Government certified agency & Design & Development facility certified by ISO 9001:2008. Housing with supplier word mark /name shall be Engraved / Embossing on the die cast housing/ Body part. Warranty of 2 Years against any manufacturing defect working under standard electrical conditions as mentioned above should be given by LED manufacturer & Cree/Nichia/ Lumileds/Osram make LED Source.
LED Streetlight 70W
Supply of LED floodlight luminaire with pressure die cast aluminium housing body for optimal thermal dissipation. Lamp compartment comprising of anti glare clear diffuser with Injection moulded polycarbonate/clear glass material, delivering superior light output. Rated life Burning Hrs 50000 hr @ Lumen Maintenance of 70%, CCT > 5500K, IP 66 optical and electrical compartment & impact resistance of complete luminaire > IK08. Power Factor >0.9 with mains, Surge Protection- Min 5KV along with Over voltage/ Overload, short circuit/ miss-wiring protection. Compatible for pole mouting with outer dia of 40mm to 50mm. Universal Voltage driver to operate wide voltage range from 100V to 270V 50/60Hz application. Compliance to IS 10322/ IEC 60598, LM 79 & LM 80 Adherence with RoHS. UL approved MCPCB. Top access street light with single screw to ensure ease of maintenance at the sight site location with minimized minimal tools. LED Light fixture with W System Power consumption. LED Efficiency>130lm/w, nominal CRI >75. Luminaire manufacturer should have in- house facility accredited by NABL/CPRI & any Government certified agency & Design & Development facility certified by ISO 9001:2008 . Housing with supplier word mark /name shall be Engraved / Embossing on the die cast housing/ Body part. Warranty of 2 Years against any manufacturing defect working under standard electrical conditions as mentioned above should be given by LED manufacturer & Cree/Nichia/ Lumileds/Osram make LED Source.
LED Floodlight 100W
Fixing halogen/metal halide /SVL/IL/LED floodlight fitting over existing pole / wall ceiling including clamps, bolts, nuts and wiring using suitable capacity wires.
Supplying and Fixing of........mm dia class A GI pipe bracket upto 2 ms long bent at suitable angle and fixing to this bracket street light fitting of all capacities to GIor GIorrailor RCC pole/wall using suitable clamps, bolts, and nuts and wiring using suitable capacity wires.
Using 32mm dia G.I.Pipe
GI/ Copper strips for grounding connections, using necessary fixing materials as required.
50 x 6 mm GI strip
50 x 6 mm Copper strip
Supplying & Fixing Chemical earthing for grounding. Conduits, IC cut -outs & other equipments back fill compound which is non -corrosive, thermally conductive, potential to permissible limits, superior Fault conduction capacity, non toxic, weather resistance & capable of achieving ohmic value less than one ohm
Using 4ft. Copper bonded rod with backfill compound
Providing 6kg Fire Extinguisher Mono Ammonium Phosphate Powder 90, Stored Pressure Type, Pressure Gauge, Gross Weight 9.40 Kg, empty weight 3.4 Kg, Can Height 480MM, Diameter 160MM, Discharge Time less than 13 Sees, Controllable discharge mechanism (Squeeze grip with easy snap safety seal), Range minimum 4 meters, applicable on Class A,B, C and electrically started Fire, A Rating 3A, B Rating 21B, Can construction : Deep drawn & Co., Mig welded, valve Construciton : Forging and Mechining, Internal Coating of Can: Epoxy powder coating, External Coating of Can: Epoxy Polyster power coating, Sheet metal thickness: 1.60MM, 5 years Warranty with instalert system with Superior quality EPDM Rubber Hosepipe etc., including cost of materials, labour, usage charges of machinery complete as per specifications. complete IS 15683 and CE Approved
Providing 4.5Kg C02 gas valve type Fire Extinugisher, Tro lley Mounted, Easy Weight Management used Unused Mechanism, Gross Weight 19.1 Kg. empty Weight 14.6 Kg. Can Height 860MM Diameter 140MM, Discharge Time less than13 Sees,Controllable discharge mechanism, Applicable on Class 8&C Fire, 8 Rating 138, Can Constuction : Hot spinning/Forging, Valve Construction : Forging & Machining, Internal Coating of Can : Not Applicable, External coating of Can : Spray Painting, Sheet metal thickness : 4.5M M lSI Approved, 1YearWarranty.with instalert system with Superior quality EPDM Rubber Hosepipe etc., including cost of materials, labour, usage charges of machinery complete as per specifications. complete
Supplying of four bucket stand along with buckets, complete.
Supplying of Hand gloves, complete.
Supplying of first aid box, complete.
Supplying of Saftey Mask, complete.
Supplying of First Aid Chart with lamination, complete.
Supplying and installation of Rubber Mat 1 mtr x 1 mtr - 10 mm thick, complete including cost of materials, labour, usage charges of machinery complete as per specifications.
Supply & Fixing Heavy Duty Copper Terminal Long Barrel lugs of the following sizes
300 Sqmm Copper Terminal
Supply & Fixing of Caution / Danger Boards
Supply
Fixing
11KV CT (Secondary - 1A) for 3 Phase 4 Wire Metering, Burden: 2.5 VA, 0.2 Accuracy Class
Ratio: 1.25/1A to 2.5/1A
11kV/√3/110V/√3, 1 Phase metering PT class - 1, 100 VA per Phase for measurement of voltage
GSM modem with connecting cable for remote communicating capabilities
Fixing of Thread Through Meter along with wiring
Fixing of GPRS Modems with Accessories
CT PT Operated ETV Meter 0.2s Accuracy Class with ABT feature and DLMS protocal with ToD with RS 232 Port UNIDIRACTIONAL (Used for HT Installation, LT Metering Cubicle {50-150 KW})
LT Line Tester
Screw Ddriver 8"
Adjustabale Screw Spanner 12"
Hi Visibility Reflective Jacket
Hi Visibility Reflective Rain Wear
Percentage BoQ At Par
BoQ_Ver4.0
NIT No. RITES/BLR/HAS-MAQ/EXT-ELE/LT/2026
Name of the Bidder/ Bidding Firm / Company :
PRICE SCHEDULE - "C" -MARKET RATE - Electrical Items (This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only )
NUMBER #
Part - C -MARKET RATE - Electrical Items
11KV, HT 3 Way Non DAS VCB Panel
Supply, erection, testing and commissioning of 11KV, 3PH, 50 HZ, 350 MVA, 630 AMPS, OUTDOOR TYPE 3 VCB Panel H.T. Control panel,Comprising of 1 VCB incomer & 2 outgoing VCB's fabricated out of 2 mm Cold Rolled mild steel, metal clad , free standing totally enclosed cubicle type, fully compartmentalised & suitable for operation on 11 KV, 3 phase, 50 Hz AC Earthed system and comprising of the following as per the detail specifications below.
Incoming
VCB Panel consisting of :
a. 3P VACCUM CIRCUIT BREAKER, horizontal drawout, horizondally isolated type, 630 amps 350MVA, 11 kV, 26.3kA with all standard accessories fitted with, shunt trip/closing coil, Motor: 220V / 110V AC motor / hand operated mechanism and operaration counter -1 no
b.Non lockable breaker control (TNC) switch with twistle grip handle and spring return to neutral - 1 set
c.3P, Non directional IDMT 30/c , 1 E/F relay with instantaneuous elements MC 31 A - 1 set
d.Resin cast CT's 15/7.5 vA class 5P 10/1 - 3 nos
e.Resin cast PT's, 3P,100vA class 1 - 1 no
f.Breaker on/off indication lamps - 1 set
i.Aluminium busbar, suitable rating 3 Phase,Air insulated with heat shrinkable sleevs - 1set
j.Earth 25X3 mm Tin coated copper busbar - 1set
k.Busbar supports resin cast with 33kV die electric and mechanical strength - 1 set
Outgoing
VCB Panel 2 & 3 - - 2Nos , Each Consisting of the following:
a. 3P VACCUM CIRCUIT BREAKER, horizontal drawout, horizondally isolated type, 630 amps 350MVA, 11 kV, 26.3kA with all standard accessories fitted with, shunt trip/closing coil, Motor: 220V / 110V AC motor / hand operated mechanism and operaration counter -1 no
b.Non lockable breaker control (TNC)switch with twistle grip handle and spring return to neutral - 1 set
c.3P, Non directional IDMT 30/c , 1 E/F relay with instantaneuous elements MC 31 A - 1 set
d.Resin cast CT's 15/7.5 vA class 5P 10/1 - 3 nos
e.Breaker on/off indication lamps - 1 set
g.Aluminium busbar, suitable rating 3 Phase,Air insulated with heat shrinkable sleevs - 1set
h.Earth 25X3 mm Tin coated copper busbar - 1set
i.Busbar supports resin cast with 33kV die electric and mechanical strength - 1 set
Compact Sub-station 11kV/433 V, 500KVA
Design, fabrication, Supply, erection, testing and commissioning of Outdoor type package substation (Compact Substation) comprising of 1 No of 11 KV VCB of rating 630 A, MDO type, directly connected with 1 No 11 KV/433 V, 500 KVA copper wound Dry type power distribution transformer and 2 No's of 800A 4P MCCB's microprocessor type or based LT outgoing (operating voltage 433 V), 50 KA, Shunt release, Under voltage release and E/F relay complete with all standard accessories as required and subject to ESCOM requirment / Norms. CSS panel enclouser frabicated out of 2 mm thick CRCA sheet steel and also as per detail specification enclouser
11 KV/433 V, 500 KVA 'Compact Substation
Main LT Power Panel
Supply, erection, testing and commisioning of Indoor type Main LT Power Panel fabricated out of 16 SWG CRCA sheet steel metal with all aluminium TPN busbars, doors interlock with switches, dead front type design, metal pretreatment of such as derusting, degreasing, phosphating, Powder coated, prime coats and finish paints of approved color with all leads and lift and as directed by the Engineer incharge. The Panel shall be erected with suitable" C " Channels over the existing Duct and shall comprise of the following.
EB Incomer 1
i) '800 A 4 pole 50KA EDO ACB with O/C, S/C, LSI Releases - 1 No
EB Incomer 2
i) '800 A 4 pole 50KA EDO ACB with O/C, S/C, LSI Releases - 1 No
Buscoupler
i) '800 A 4 pole 50KA EDO ACB with O/C, S/C, LSI Releases - 1 No
Under Voltage Release - 3 No's
EB 1 & EB 2 Metering Consisting of
RYB phase indication lamps - 2 sets
ACB Indication Lamps ON / OFF / TRIP / CHARGE - 3 Set
MFM Meter - 2 Nos
CT Ratio 800 / 5 A, Class 1.0, Burden 15 VA - 3 no's
Earth Leakage Relay with CBCT - 2 No's
6 Amps SP MCB for Control Circuits
Phase Failure Relay with Under & Over Voltage Relay setting with Neutral fail Protection. - 3 Sets
ON / OFF ILPB with NO- NC Contactors - 3 Sets
Trip Indication Lamps - 3 Sets
On Delay Timer - 3 Nos
Auxilory Contractors - 3 Sets
INTERLOCK
Electrical Interlock of EB Incomer 1& 2 and Bus Coupler with Auxilary Contractors, Relays, Connectors, Timers, MCB's and other accessories.
Out-going
400 A 3P+NL MCCB with 36 KA Breaking capacity. O/C & S/C releases - 1 No
250 A 3P+NL MCCB with 25 KA Breaking capacity. O/C & S/C releases - 3 No
200 A 3P+NL MCCB with 25 KA Breaking capacity. O/C & S/C releases - 4 No
125 A 3P+NL MCCB with 25 KA Breaking capacity. O/C & S/C releases - 2 No
100 A 3P+NL MCCB with 25 KA Breaking capacity. O/C & S/C releases - 1 No
Suitable Spreder Terminals and Extended Rotary Handles for all MCCB's as required.
( Note : The Logic Sequence of the Main Panel shall be Designed in such a way that, at any point of time only One Incoming source will be functional)
New 100 KVAR Capacitor Control Panel
Supply, installation, testing and commissioning of Indoor type 100 KVAR Automatic Power factor correction relay ( APFCR ) of 6 stages, fabricated out of 16 SWG CRCA sheet steel metal with all aluminium TPN busbars, doors interlock with switches, dead front type design, metal pretreatment of such as derusting, degreasing, phosphating, Powder Coated, prime coats and finish paints of approved color with all leads and lift and as directed by the Engineer incharge. The Panel shall be erected with suitable" C " Channels over the existing Duct and shall comprise of the following.
Incoming
200 A 3P+NL MCCB with 25 KA Breaking capacity. O/C & S/C releases - 1 No
250 A Aluminium Busbar - 1set (Colour code shall be followed strictly for all phases) with heat shrinkable sleeves and SMC busbar supports)
RYB phase indication lamps - 3 set
VAF Meter - 1 Nos
CT Ratio 400 / 5 A, Class 5, Burden 15 VA - 36 No's
6 Amps SP MCB for Control Circuit
6 Stage APFCR Relay
Suitable Spreder Terminals and Extended Rotary Handles for all MCCB's as required.
Outgoing:
25 KVAR Capacitor Bank with 63 Amps TP MCB Switching duty TP contactors , with ON/OFF Push buttons & ON indication lamps complete - 2 Nos
20 KVAR Capacitor Bank with 40 Amps TP MCB Switching duty TP contactors , with ON/OFF Push buttons & ON indication lamps complete- 1 No
10 KVAR Capacitor Bank with 32 Amps TP MCB Switching duty TP contactors , with ON/OFF Push buttons & ON indication lamps complete - 3 Nos
LT Metering Cubicle
Supply, installation, testing and commissioning outdoor type LT Metering Cubicle frabcatied of 2 mm CRCA sheet metal with all aluminium TPN busbars, doors interlock with switches, dead front type design, metal pretreatment of such as derusting, degreasing, phosphating, Powder coated, prime coats and finish paints of approved color with all leads for loads sutiable on LT supply from 50 KW to 150 KW having specification & design as per the prototype approval as per CESCOM requirment and approval (Excluding Meter Cost & Modem Cost)
AMF Panel for 250 KVA DG Set:
Supply, installation, testing and commissioning of Indoor type AMF Panel fabricated out of 16 SWG CRCA sheet steel metal with all aluminium TPN busbars, doors interlock with switches, dead front type design, metal pretreatment of such as derusting, degreasing, phosphating, Powder coated, prime coats and finish paints of approved color with all leads and lift and as directed by the Engineer incharge. The Panel shall be erected with necessary angle frame/ C Channel supports. The AMF Panel shall comprise of the following.
Incoming
400 A ATS - 1 No
400 A Aluminium Busbar - 1set (Colour code shall be followed strictly for all phases) with heat shrinkable sleeves and SMC busbar supports)
RYB phase indication lamps - 2 set, EB ON, DG ON indication
Microprocessor based AMF module with supply failure timer, Restoration timer, 3 impulse automatic engine start/stop logic, Mains/generator voltage.
Wiring of 1/1.5 Sqmm Insulated Single Core Multistrand Copper Conductor for Control & Voltage Circuits
Outgoing:
400 A 3P+NL MCCB with 36KA Breaking capacity. O/C & S/C releases - 2 No's
New Essential LT Power Panel:
Supply, erection, testing and commisioning of Indoor type LT Essential Power Panel fabricated out of 16 SWG CRCA sheet steel metal with all aluminium TPN busbars, doors interlock with switches, dead front type design, metal pretreatment of such as derusting, degreasing, phosphating, Powder coated, prime coats and finish paints of approved color with all leads and lift and as directed by the Engineer incharge. The Panel shall be erected with suitable" C " Channels over the existing Duct and shall comprise of the following.
Incoming
400 A TP +NL MCCB 36 KA breaking capacity with O/C, S/C release - 1 No,
400 A Aluminium Busbar - 1 set (Colour code shall be followed strictly for all phases) with heat shrinkable sleeves and SMC busbar supports)
RYB phase indication lamps - 1 set
Earth Leakage Relay with CBCT - 1 No
6 Amps SP MCB for Control Circuits
CTS 125/5A Class 1.0 Burden 5VA.
Out-going
200 A 3P+NL MCCB with 36 KA Breaking capacity. O/C & S/C releases - 1 No
125 A 3P+NL MCCB with 25 KA Breaking capacity. O/C & S/C releases - 3 No's
63 A 3P+NL MCCB with 16 KA Breaking capacity. O/C & S/C releases - 5 No's
32 A 3P+NL MCCB with 16 KA Breaking capacity. O/C & S/C releases - 1 No's
Suitable Spreader Terminals and Extended Rotary Handles for all MCCB's as required.
New Commercial LT Power Panel:
Supply, erection, testing and commisioning of Indoor type LT Commercial Power Panel fabricated out of 16 SWG CRCA sheet steel metal with all aluminium TPN busbars, doors interlock with switches, dead front type design, metal pretreatment of such as derusting, degreasing, phosphating, Powder coated, prime coats and finish paints of approved color with all leads and lift and as directed by the Engineer incharge. The Panel shall be erected with suitable" C " Channels over the existing Duct and shall comprise of the following.
Incoming
250 A TP +NL MCCB 36 KA breaking capacity with O/C, S/C release - 1 No,
250 A Aluminium Busbar - 1 set (Colour code shall be followed strictly for all phases) with heat shrinkable sleeves and SMC busbar supports)
RYB phase indication lamps - 1 set
Earth Leakage Relay with CBCT - 1 No
6 Amps SP MCB for Control Circuits
CTS 125/5A Class 1.0 Burden 5VA.
Out-going
200 A 3P+NL MCCB with 25 KA Breaking capacity. O/C & S/C releases - 1 No
125 A 3P+NL MCCB with 25 KA Breaking capacity. O/C & S/C releases - 2 No's
100 A 3P+NL MCCB with 25 KA Breaking capacity. O/C & S/C releases - 2 No's
63 A 3P+NL MCCB with 16 KA Breaking capacity. O/C & S/C releases - 1 No's
32 A 3P+NL MCCB with 16 KA Breaking capacity. O/C & S/C releases - 2 No's
Suitable Spreader Terminals and Extended Rotary Handles for all MCCB's as required.
New Domestic LT Power Panel:
Supply, erection, testing and commisioning of Indoor type LT Domestic Power Panel fabricated out of 16 SWG CRCA sheet steel metal with all aluminium TPN busbars, doors interlock with switches, dead front type design, metal pretreatment of such as derusting, degreasing, phosphating, Powder coated, prime coats and finish paints of approved color with all leads and lift and as directed by the Engineer incharge. The Panel shall be erected with suitable" C " Channels over the existing Duct and shall comprise of the following.
Incoming
250 A TP +NL MCCB 36 KA breaking capacity with O/C, S/C release - 1 No,
250 A Aluminium Busbar - 1 set (Colour code shall be followed strictly for all phases) with heat shrinkable sleeves and SMC busbar supports)
RYB phase indication lamps - 1 set
Earth Leakage Relay with CBCT - 1 No
6 Amps SP MCB for Control Circuits
CTS 125/5A Class 1.0 Burden 5VA.
Out-going
200 A 3P+NL MCCB with 25 KA Breaking capacity. O/C & S/C releases - 1 No
125 A 3P+NL MCCB with 25 KA Breaking capacity. O/C & S/C releases - 2 No's
63 A 3P+NL MCCB with 16 KA Breaking capacity. O/C & S/C releases - 3 No's
Suitable Spreder Terminals and Extended Rotary Handles for all MCCB's as required.
LT Feeder Pillar Panel:
Supply, erection, testing and commisioning of Outdoor type LT Feeder Pillar Panel fabricated out of 14 SWG CRCA sheet steel metal with all aluminium TPN busbars, doors interlock with switches, dead front type design, metal pretreatment of such as derusting, degreasing, phosphating, Powder coated, prime coats and finish paints of approved color with all leads and lift and as directed by the Engineer incharge. The Panel shall be erected with suitable" C " Channels over the existing Duct and shall comprise of the following.
Incoming
125 A TP +NL MCCB 25 KA breaking capacity with O/C, S/C release - 1 No,
150 A Aluminium Busbar - 1 set (Colour code shall be followed strictly for all phases) with heat shrinkable sleeves and SMC busbar supports)
RYB phase indication lamps - 1 set
6 Amps SP MCB for Control Circuits
CTS 125/5A Class 1.0 Burden 5VA.
Out-going
100 A 3P+NL MCCB with 25 KA Breaking capacity. O/C & S/C releases - 3 No's
63 A 3P+NL MCCB with 16 KA Breaking capacity. O/C & S/C releases - 2 No's
32 A 3P+NL MCCB with 165 KA Breaking capacity. O/C & S/C releases - 4 No's
Suitable Spreder Terminals and Extended Rotary Handles for all MCCB's as required.
LT Cable
Supply of 1.1 KV, XLPE or Heat resistant PVC insulated, PVC exutruted Inner Seath Armoured LT UG Cable as per IS-1554 (Part- 1) or IS-7098 Part-1, Armouring strip thickness and resistivity as per IS-3975
Supply
300 Sqmm, 3.5 Core, (32 GI Strips - 4 x 0.8 mm)
240 Sqmm, 3.5 Core (32 GI Strip 4 x 0.8 mm)
185 Sqmm, 3.5 Core, (28 GI Strips - 4 x 0.8 mm)
120 Sqmm, 3.5 Core, (23 GI Strips - 4 x 0.8 mm)
95 Sqmm, 3.5 Core, (21 GI Strips - 4 x 0.8 mm)
50 Sqmm, 3.5 Core, (18 GI Strips - 4 x 0.8 mm)
16 Sqmm, 4 Core, (11 GI Strips - 4 x 0.8 mm)
HT UG Cable
Supply of 11 KV, 3 Core, XPLE HT UG Cable with pressure extruded inner sheeth, ROUND WIRE ARMOURED as per IS-7098 (Part-2) Armouring wires dia and Resistivity as per IS-3975
Supply
240 Sqmm, (55 GI Wires - 3.15 mm Dia)
Arranging HT Power supply
Arranging required HT Power supply from CESCOM wth Submission of application for Power supply, Obtaining Power sanction, CEIG / CEA Approval from Electrical Inspectorate , Feasibility report, Preparing wiring Diagram, Completion report, Agreement papers as per the requirement of CESCOM, Liasioning and Final Servicing of the Installation with Permanent power supply ( Excluding Deposits & other Charges to be remitted to CESCOM.)
Percentage BoQ At Par
BoQ_Ver4.0
NIT No: RITES/BLR/HAS-MAQ/EXT-ELE/LT/2026
Name of the Bidder/ Bidding Firm / Company :
PRICE SCHEDULE - "D" DSR 2023 Civil Items (This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only )
NUMBER #
Part D - CIVIL DSR 2023 - Civil Items
Clearing jungle including uprooting of rank vegetation, grass, brush wood, trees and saplings of girth up to 30 cm measured at a height of 1 m above ground level and removal of rubbish up to a distance of 50 moutside the periphery of the area cleared
Earth work in surface excavation not exceeding 30 cm in depth but exceeding 1.5 m in width as well as 10 sqm on plan including getting out and disposal of excavated earth upto 50 m and lift upto 1.5 m, as directed by Engineer-in- Charge
All kinds of Soils - Total Area
Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m.
All kinds of soil
Excavation work by mechanical means (Hydraulic excavator)/ manual means in foundation trenches or drains (not exceeding 1.5m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soils as directed, within a lead of 50 m.
Ordinary rock ( 20 % )
Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift upto 1.5 m.
Excavating, supplying and filling of local earth (including royalty) bymechanical transport upto a lead of 5km also including ramming andwatering of the earth in layers not exceeding 20 cm in trenches, plinth, sides of foundation etc. complete.
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level :
1:4:8 (1 Cement : 4 coarse sand (zone-III) derived from natural sources : 8 graded stone aggregate 40 mm nominal size derived from natural sources)
1:3:6 (1 Cement : 3 coarse sand (zone-III) derived from naturalsources : 6 graded stone aggregate 20 mm nominal size derived from natural sources)
Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, PortlandPozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairingstrength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge; for the following grades of concrete
Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement contentin design mix is more than 110% of the minimum specified cementcontent, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement.
All works upto plinth level :
Concrete of M25 grade with minimum cement content of 330 kg /cum
All works above plinth and upto floor V level
Concrete of M25 grade with minimum cement content of 330 kg /cum
Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level.
Total qty of RCC concrete Assuming 120 Kg per cum
Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete above plinth level.
Total qty of RCC concrete Assuming 125 Kg per cum
Centering and shuttering including strutting, propping etc. and removal of form fo
Foundations, footings, bases of columns, etc. for mass concrete
Columns, Pillars, Piers, Abutments, Posts and Struts
Columns below plinth
Lintels, beams, plinth beams, girders, bressumers and cantilevers
Weather shade, Chajjas, corbels etc., including edges
Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level in all shapes and sizes in :
Cement mortar 1:6 (1 cement : 6 coarse sand)
Random rubble masonry with hard stone in foundation and plinth including levelling up with cement concrete 1:6:12 (1 cement : 6 coarse sand : 12 graded stone aggregate 20 mm nominal size) upto plinth level with :
Cement mortar 1:6 (1 cement : 6 coarse sand)
Coursed rubble masonry (first sort) with hard stone in foundation and plinth with :
Cement mortar 1:6 (1 cement : 6 coarse sand)
Providing and fixing factory made uPVC glazed/wire mesh windows/ doors comprising of lead free uPVC multi-chambered frame, sash and mullion/coupler (where ever required) extruded profiles having minimum wall thickness of 1.70 mm for Series R1 and R2 profiles and 2.10 mm for Series R3 and R4 profiles conforming to EN: 12608 in any shape, colour and design duly reinforced with galvanized mild steel section made of required shape & size as per CPWD Specification, uPVC extruded glazing beads, interlocks and Inline sash adaptor (where ever required) of appropriate dimension, EPDM gasket, hardware, SS 304 grade fasteners of minimum 8 mm dia with counter sunk head, comprising of matching polyamide PA6 grade sleeve for fixing frame to finished wall as per IS 1367 : Part 1 to 14, plastic packers, plastic caps and necessary stainless steel screws etc. Profile of frame, sash & mullion (if required) shall be mitred cut and fusion welded/mechanically jointed duly sealed at all corners, including drilling of holes for fixing hardware and drainage of water etc. After fixing frame the gap between frame and adjacent finished wall shall be filled with weather proof silicon sealant over backer rod of approved size and quality, all complete as per approved drawing conforming to CPWD specification & direction of Engineer-in-Charge. Section of steel reinforcement and cross sections of uPVC profiles to be as per design approved by Engineer-in-
Two track two panels sliding window made of (small series)frame 52 x 44 mm &sash 32 x 60 mm both having wallthickness of 1.9 ± 0.2 mm and single glazing bead ofappropriate dimension. (Area of window upto 1.75 sqm)
Providing and fixing M.S. grills of required pattern in frames of windows etc. with M.S. flats, square or round bars etc. including priming coat with approved steel primer all complete.
Fixed to steel windows by welding
Providing wood work in frames of doors, windows, clerestory windowsand other frames, wrought framed and fixed in position with hold fastlugs or with dash fasteners of required dia & length (hold fast lugs ordash fastener shall be paid for separately).
Second class teak wood
Providing and fixing 35 mm thick factory made laminated veneer lumberdoor shutter conforming to IS : 14616 and TADS 15:2001 (Part B), fixingwith butt hinges of required size with necessary screws, all completeas per directions of Engineer- in-charge andpanelling with panels of :(Note:- Butt hinges and necessary screwsshall be paid separately)
12 mm thick one side Pre-laminated particle board (decorativelamination on one side and other sides balancing lamination)grade -1, medium density flat pressed, three layer particleboard FPT - I or graded wood particle board FPT-1 conformingto IS : 3087 bonded with BWP type synthetic resin adhesiveas per IS : 848 and pre-laminated conforming to IS : 12823,Grade -1, Type II marked :
Providing and fixing ISI marked flush door shutters conforming to IS : 2202 (Part I) non-decorative type, core of block board construction with frame of 1st class hard wood and well matched commercial 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters:
35 mm thick including ISI marked Stainless Steel butt hingeswith necessary screws
Providing and fixing aluminium sliding door bolts, ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868), transparent or dyed to required colour or shade, with nuts and screws etc. complete :
Providing and fixing aluminium tower bolts, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868 ) transparent or dyed to required colour or shade, with necessary screws etc. complete :
Providing and fixing aluminium handles, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade, with necessary screws etc. complete :
Providing and fixing aluminium hanging floor door stopper, ISI marked,anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour and shade, with necessary screws etc. complete.
Single rubber stopper
ProvidingandfixingpressedsteeldoorframesconformingtoIS:4351,manufactured from commercial mild steel sheet of 1.60 mm thickness,including hinges, jamb, lock jamb, bead and if required angle thresholdof mild steel angle of section 50x25 mm, or base ties of 1.60 mm,pressed mild steel welded or rigidly fixed together by mechanical means,including M.S. pressed butt hinges 2.5 mm thick with mortar guards,lock strike-plate and shock absorbers as specified and applying a coatof approved steel primer after pre-treatment of the surface as directedby Engineer-in-charge:
Profile B -Fixing with adjustable lugs with split end tail toeach jamb
Painting with synthetic enamel paint of approved brand andmanufacture to give an even shade :
Two or more coats on new work
12 mm cement plaster:
1:6 (1 cement : 6 fine sand)
15 mm cement plaster on the rough side of single or half brick wall ofmix :
1:6 (1 cement: 6 fine sand)
Distempering with 1st quality acrylic distemper (ready mixed) having VOC content less than 50 gms/litre, of approved manufacturer, of required shade and colour complete, as per manufacturer's specification.
New work (two or more coats) with a base coat of white washing with lime
Finishing walls with premium acrylic smooth exterior paint with silicone additives of required shade:
New work (Two or more coats applied @ 1.43 ltr/10 sqm over and including priming coat of exterior primer applied @ 2.20 kg/10sqm)
Steel work in built up tubular (round, square or rectangular hollow tubesetc.) trusses etc., including cutting, hoisting, fixing in position andapplying a priming coat of approved steel primer, including welding andbolted with special shaped washers etc. complete.
Hot finished welded type tubes
Making plinth protection 50 mm thick of cement concrete 1 : 3 : 6 (1 Cement : 3 Coarse sand : 6 graded stone aggregate 20 mm nominal size) over 75 mm of dry brick ballast 40 mm nominal size well rammed and consoildated and grouted with fine sand including finishing the top smooth
Providing and fixing precoated galvanised iron profile sheets (size,shape and pitch of corrugation as approved by Engineer-in-charge)0.50 mm (+ 0.05 %) total coated thickness with zinc coating 120grams per sqm as per IS: 277, in 240 mpa steel grade, 5-7 micronsepoxy primer on both side of the sheet and polyester top coat 15-18microns. Sheet should have protective guard film of 25 micronsminimum to avoid scratches during transportation and should besupplied in single length upto 12 metre or as desired by Engineerin-charge. The sheet shall be fixed using self drilling /self tappingscrews of size (5.5x 55 mm) with EPDM seal, complete upto anypitch in horizontal/ vertical or curved surfaces, excluding the cost ofpurlins, rafters and trusses and including cutting to size and shape wherever required. sqm 671.55 12.51 Providing and fixin
Supplying and fixing rolling shutters of approved make, made of required size M.S. laths, interlocked together through their entire length and jointed together at the end by end locks, mounted on specially designed pipe shaft with brackets, side guides and arrangements for inside and outside locking with push and pull operation complete, including the cost of providing and fixing necessary 27.5 cm long wire springs manufactured from high tensile steel wire of adequate strength conforming to IS: 4454 - part 1 and M.S. top cover of required thickness for rolling shutters.
Please Enable Macros to View BoQ information
stage.html
html • 0.04 MB
techsummary_312789.pdf
finsummary_312789.pdf
aoc.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.11 MB
TenderDocumentExternaEleHassan250226.pdf
Tender Documents • 0.82 MB
SLDOFSWRHASSANRAILWAYSUBSTATIONYARD.pdf
Other Document • 0.79 MB
BOQ_312789.xls
BOQ • 1.36 MB
Download all tender documents and submit your bid