Superintending Engineer
EDC-I, SRE
Replacement of Damage 05 MVA T/F in Pilakhni Industrial other related work in the area of EDD I SRE
2020_PVVNL_473138_1
07/W/EDC-I/SRE/2020-21
Open Tender
Electrical Works
Lump-sum
30 days
Clock Tower
Please refer Tender documents.
2 documents required · 2 mandatory
₹1,180
SE EDC I SRE
₹2,000
Yes
1 Jun 2020
20 May 2020
29 May 2020
20 May 2020
29 May 2020
20 May 2020
120 days
Amount
Detail of Work
Opening of neutral LT/HT cable connection of 05 MVA damaged T/F at 33/11 KV S/S Pilkhani Industries.
Drain out of T/F oil from 05 MVA damage T/F at 33/11 KV S/S Pilkhani.
Shifting of T/F oil drum to the JE Store.
Opening of radiator conservation tank and other accessories of damage 05 MVA T/F at 33/11 KV S/S Pilkhani Industries.
Cutting of earthing flat of damaged 05 MVA T/F.
Safely shifting of damaged 05 MVA T/F from the plinth to safe place of S/S by private crane. (distance Approx. 20 mtr)
Drain out of T/F oil from 05 MVA T/F at 33/11 KV S/S Ghateda, Saharanpur.
Opening of radiators, conservator tank and other accessories of 05 MVA T/F at 33/11 KV S/S Gatehda, Saharanpur.
Safely shifting of 05 MVA T/F from switchyard to road side of 33/11 KV S/S Gatehda, Saharanpur.
Safely loading of 05 MVA T/F in private truck by crane at 33/11 KV S/S Gatehda, Saharanpur.
Safely loading of radiators, conservator tank and other accessories and T/F oil drums in private truck by crane at 33/11 KV S/S Gatehda, Saharanpur.
Safely carriage of 05 MVA T/F with radiators, conservator tank and other accessories and T/F oil drums (7 No.) by private truck from 33/11 KV Jainbagh S/S to 33/11 KV S/S Pilkhani Industries.
Safely unloading of radiators, conservator tank and other accessories and T/F oil drums (7 No.) by private crane at road side of 33/11 KV S/S Pilkhani.
Safely unloading of 05 MVA T/F by private crane at road side of 33/11 KV S/S Pilkhani Industries.
Safely shifting of 05 MVA T/F by private crane from road side to plinth with proper alignment at 33/11 KV S/S Pilkhani industries.
Safely shifting of radiators, conservator tank and other accessories and T/F oil drums by private crane from road side to switchyard near plinth of 33/11 KV S/S Pilkhani industries.
Fixing of radiators, conservator tank and other accessories of 5 MVA T/F at 33/11 KV S/S Pilkhani industries.
Pouring of T/F oil from T/F oil drums to 5 MVA T/F for topping up the level of oil in the T/F.
Neutral & Body Earting of 05 MVA T/F by boring of 60 feet deep and fixing of 60 feet G.I. pipe 1/5 dia (ZIndal class B) and connecting with 06 No. copper wire with toe made of copper at bottom of G.L/ pipe T/F providing of required charcoal and salt in pipe.
Welding of earthing form MS flate for 05 MVA T/F properly
Making of netural and LT/ HT cable connection of 05 MVA T/F properly.
L.A.’s/P.I’s/C.T.’s/P.T.’s and fuse set structure:-Fabrication & Erection of Post Insulators/Fuse set and Plinth for the same as per drawing a) Excavation of earth (030x0.30x1.0)m for 8 nos. pits of above structure.
b) Fabrication & erection of above structure by using M.S. channel of size (125x65) mm size and 3.5 m minimum height with 02 Nos. M.S. Angle (50x50x6) mm size on top of structure for installation L.A’s, P.I’s. & fuse set, C.T.’s & P.T’s (01 No. each)
C) C.C. work of ratio 1:3:6 (cement, coarse sand and 25 mm stone grit) for the above plinth for structure of L.A.’s, P.I.’s. C.T.’s & Fuse Set 4 Nos. after ramming of earth of size (0.3x0.3x1.0)m over stone pad.
D) 12 mm thick plaster with cement mortar ratio 1:4 (cement & fine sand) of plinth of 0.4 m upper side.
Paint work of Structure peroperly.
Fixing of Control pannel Double T/F in Control room and making connection peroperly.
Fixing of Fuse set Peroperly.
Fixing of TPMO Set peroperly.
Safely Carriage and installation of Battery of Battery Charger.
SAINI ASSOCIATES
M/S FAGGU RAM AND COMPANY
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart shows the information on this page on a best-effort basis and does not guarantee that it is accurate, complete or current. Check it against the buyer's official notice and documents before you act on it; the official record prevails. TenderKart is not liable for any loss or claim arising from the use of this information. If you notice any error or omission, please let us know at .