Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹56.2 LAccepted-Finance | L1 | Accepted-Finance L1 Bidder. | |
| 2 | L2₹5.8 L−₹50.4 L (89.7%)Rejected-Finance 205 LOTUS ENCLAVE PUNDAG ROAD ARGORA RANCHI JHARKHAND 834002 | RANCHI | JHARKHAND | 834002 | L2 | Rejected-Finance L2 Bidder, , Not lowest Bidder. |
Tender Value
₹4.8 L
EMD Value
₹9,661
Closing Date
15 Sept 2021, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
EE(E)
Executive Engineer (E) Bhagalpur (Camp at Patna), 3rd floor CTO Bldg, Sanchar Parisar, Budh Marg, Patna-800001
Providing and Installation of Lightening Protection system Air Force Station under NFS2 Project Purnea in Bihar
2021_BSNL_87476_1
26/EDB/BSNL/NIT/2021-22
Open Tender
Electrical Works
Item Rate
30 days
NFS PURNIA BIHAR
Please refer Tender documents.
3 documents required · 3 mandatory
₹590
Yes
AO (Cash),GMTD,BSNL, Bhagalpur
₹9,661
Yes
5 Nov 2021
7 Sept 2021
17 Sept 2021
7 Sept 2021
15 Sept 2021
7 Sept 2021
90 days
Amount
Supply Installation Testing & Commissioning of Advanced Lightening Protection System(ALPS) working on the Principle of (ESE) Early Streamer Emission technology by roviding "PZ" Piezo Electrical type Air Terminal consist of capture head structured to generate a forced air circulation at its tip, support steel rod & transducer or piezoelectric stimulator with piezo electric ceramics & high voltage internal cable to connect the stimulator to the emitter point to apply voltage created in ceramic to emitter point having coverage radius up to 63 meter when mounted at an elevation pole height of 4.0 mtrs giving level I Protection with advancement triggering time of 45 us (micron second) & complying to NFC 17-102 etc as required. (Make: Franklin-France/Indelec/Pro-ESE make )
Providing and fixing Lightning Flash counter with two digit counter having lightning stroke counting range from 4KA to 150 KA(counting sensitivity 1 KA, 8/20us) in IP 65 enclosure without external power source complete with interconnection in series with down conductor path etc as required.(Make: Franklin-France/Indelec/Pro-ESE make )
Supplying and fixing of 50 mm dia B class G I Pipe of 4.0 meter length as an elevation pole ready to use assembly with threads at top to fix the existing "PZ type Air Terminal assembly unit" along with Base plate, foundation bolts, PCC foundation(1:2:4) of size 0.45 x 0.45 x 0.45 meter or wall mounting bracket, clamps, all fixing & grouting hardware's in case of fixing the same on mummty wall etc as reqd.
Providing & fixing copper Tape of size 25mm X 3mm thick on surface of wall/terrace as down conductor of ESE type lightning conductor work complete with saddling, clamping, drilling holes etc as reqd.
Jointing Copper tape (with another copper tape base of the finial or any other metallic object ) by Riveting/nut bolting/sweating & soldering etc reqd.
Providing and fixing Testing Joint made of 25mm x 3 mm thick copper Strip of 125 mm long with 4 nos of tinned bolts nuts, check nuts,spring washers mounted on 2 nos epoxy insulators in sheet steel enclosure etc as required.
Earthing with copper earth plate 600mm x 600mm x 3 mm thick including accessories & providing Masonry enclosure with cover plate having locking arrangement & watering pipe of 2.7 meter long etc with charcoal/coke & salt as reqd.
Providing & fixing 25mm x 5mm copper strip on surface or in recess for connections etc as reqd.(Note- To be laid from earth set to test joint)
Providing & fixing 25mm x 5mm copper strip in 40 mm dia G.I. Pipe from earth electrode i/c connections with brass nut bolts, spring washer, excavation & refilling etc as reqd. ((Note- To be laid from earth set to test joint)
Providing and installing 3 mtr lenth and 40 mm dia copper Chemical earthing Electrode after boring 150 mm dia , 12 feet deep in hard soil with the help of boring machine , and filling the hole with pouring compound around the electrode duly mix with black soil and water complete as reqd. (For Jack Earthing )
Supplying & wrapping of 6mm dia braided copper wire on existing jack including looping from exchange earthing testing & commissioning etc as required.
Supplying & fabrication of copper clamp approx. 150mmx20mm x1.6mm thick for fixing on existing jack & braided copper wire with G.I. nuts & bolts etc as required.
S I T C of Transient Voltage Surge Suppressor( TVSS) unit as per UL 1449 standards at service entry point of external commercial supply i.e. Type-I connection, suitable for 3 phase 4wire + Gnd (Wye )connection (3 wire + neutral + Earth) with L-L, L-N, L-E & N-E protection mode, Nominal voltage as L-L-400 V, L-N-230V, L-G-230V, 47-63 Hz frequency range, 600 volt let through voltage & surge current capacity 100KA/phase(L-N-100KA & N-G-100KA) with EMI/RFI attenuation of 40 dB in sheet steel enclosure complete with wiring & earthing etc as reqd. (M/s Emerson Liebert- Powersure model/M/s Schneider Electric-SquareD/ SS make)
S I T C of Transient Voltage Surge Suppressor( TVSS) unit for Type-II connection as per UL 1449 standards at distribution panel/branch panel end suitable for 3 phase 4wire + Gnd (Wye )connection (3 wire + neutral + Earth) with L-L, L-N, L-E & N-E protection mode, Nominal voltage as L-L-400 V, L-N-230V, L-G-230V, 47-63 Hz frequency range, 600 volt let through voltage & surge current capacity 25 KA/phase(L-N-25KA & N-G-25KA) with EMI/RFI attenuation of 40 dB in sheet steel enclosure complete with wiring & earthing etc as reqd. (M/s Emerson Liebert- Powersure model/M/s Schneider Electric-SquareD/ SS make)
Wiring for IP based CCTV system in recessed/concealed metal conduit along with 3+1 : 2390/ 4+1 : 2865 cable, junction boxes & other conduit accessories etc as reqd Note- No provision is made for electronic & hardware of CCTV & the same will be fitted by user(IAF) at later date as mentioned in point no-7 chapter - 3 of QRB PKG-1B).
Wiring for Access Control Device(ACD) & Security camera system in recessed/concealed metal conduit along with CAT-6 cable, junction boxes & other conduit accessories etc as reqd Note- No provision is made for ACD system hardware & software & the same will be provided by user(IAF) at later date as mentioned in point no-6 chapter - 3 of QRB PKG-1B).
SHREE RAM and SONS
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .