Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹21.9 LAccepted-AOC | L1 | Accepted-AOC L1 | |
| 2 | L2₹24.4 L+₹1.3 L (5.81%)Rejected-Finance H NO 1346 SECTOR 13 P HISAR 125005 HARYANA | HISAR | HISAR | HARYANA | 125005 | L2 | Rejected-Finance Not being lowest | |
| 3 | L3₹25.3 L+₹2.2 L (9.69%)Rejected-Finance | L3 | Rejected-Finance Not being lowest | |
| 4 | L4₹27.3 L+₹4.3 L (18.5%)Rejected-Finance 5021 1 CAT III MODERN HOUSING COMPLEX MANIMAJRA CHANDIGARH | CHANDIGARH | CHANDIGARH | 160001 | L4 | Rejected-Finance Not being lowest |
Tender Value
₹45 L
EMD Value
₹90,000
Closing Date
20 Oct 2022, 6:00 pmClosed
Garrison Engineer
Garrison Engineer Chandimandir panchkula Haryana 134107
GE/CHM-63/2022-2023 REPAIR AND MAINTENANCE OF INTERNAL ELECTRIFICATION WITH FITTING AND FIXTURE IN PRESTIGIOUS AT CHANDIMANDIR
2022_MES_553323_1
GE/CHM-63/2022-2023
Open Tender
Civil Works
Item Rate
180 days
Chandimandir
Please refer Tender documents.
9 documents required · 9 mandatory
₹500
Garrison Engineer
₹90,000
Yes
17 Nov 2022
21 Sept 2022
27 Oct 2022
21 Sept 2022
20 Oct 2022
6 Oct 2022
Amount
Taking down carefully aluminum/copper point wiring on & including hard wood battens, surface conduit and board/blocks etc or through conduits for light , socket or power point ,fan point complete incl fitting such as switches ,sockets, ceiling rose , holder socket, light fitting, regulators and making good disturbed surfaces of wall, floor , ceiling etc and removing materials (other than those for which credit has been given by the contractor) to the MES stores yard for keeping in safe custody complete
Point wiring with approved colour code multi stranded copper conductor, PVC insulated and unsheathed FRLSH cable of size 1.5 Sqmm ,1100 volts grade, two run of single core cable for phase & neutral and one run of single core multi stranded copper conductor, PVC insulated and unsheathed FRLSH cable of size 1.5 Sqmm ,1100 volts grade for earth continuity conductor to common earth and connected to earth dolly in existing conduit terminated on and including new modular sunken box and suitable size of frame, cover for mounting switch, socket and regulator fixed on surface flush with wall , comprising of One light /bell/buzzer point controlled by one switch or one fan point controlled by one switch &fan regulator, complete all as specified and directed. Note : (i) Unit rate is inclusive of making good the disturbed surfaces by provding by wall putty/POP after mason work and finshing to match the original surface and nothing extra shall be paid on this account. (ii)Unit rate is inclusive of cutting chases in wall /foor/PCC for sunken box and making good the disturbed surfaces to match the original and nothing extra shall be paid on this account.
All as per serial item 02 herein before but for socket outlet 3 pin 5 Amps on same board complete all as specified and directed
All as per serial item 02 herein before but for socket outlet 3 pin 6 Amps on independent board complete all as specified and directed
All as per serial item 02 herein before but One socket outlet three pin ,6/16 Amp, independent board, with 2.5 Sqmm (nominal area ) FRLSH cable & 2.5 Sqmm (nominal area ) cable as earth continuity conductor
Material and labour for point wiring with approved colour code multi stranded copper conductor, PVC insulated and unsheathed FRLSH cable of size 1.5 Sqmm ,1100 volts grade, two run of single core cable for phase & neutral and one run of single core multi stranded copper conductor, PVC insulated and unsheathed FRLSH cable of size 1.5 Sqmm ,1100 volts grade for earth continuity conductor to common earth and connected to earth dolly in and including new concealed PVC conduit terminated on and including new modular sunken box and suitable size of frame, cover for mounting switch, socket and regulator fixed on surface flush with wall , comprising of One light /bell/buzzer point controlled by one switch or one fan point controlled by one switch &fan regulator, complete all as specified and directed. Note : Unit rate is inclusive of making good the disturbed surfaces by provding by wall putty/POP after mason work and finshing to match the original and nothing extra shall be paid on this account. Note :Unit rate is inclusive of cutting chases in wall /foor/PCC and making good the disturbed surfaces to match the original and nothing extra shall be paid on this account.
All as per serial item 06 herein before but for socket outlet 3 pin 5 Amps on same board complete all as specified and directed
All as per serial item 06 herein before but for socket outlet 3 pin 6 Amps on independent board complete all as specified and directed
All as per serial item 06 herein before but One socket outlet three pin ,6/16 Amp, independent board, with 2.5 Sqmm (nominal area ) FRLSH cable & 2.5 Sqmm (nominal area ) cable as earth continuity conductor
Electric Bell, AC, 230 volts, single pole complete all as specified and directed.
Ceiling rose, PVC or polycarbonate of size 65mmx50mm three terminals (ISI marked) complete all as specified and directed.
Lamp holder, 6 Amp PVC/Polycarbonate type with back plate angular type fixed on wall suitable for batten fitting complete all as specified and directed.
LED lamp 9 W B-22 type complete all as specified and directed
Switch modular type (ISI marked), single pole, one way 6 Amps, one module (ISI marked), complete all as specified & directed.
Switch modular type (ISI marked), single pole, one way 16 Amps, one module (ISI marked), complete all as specified & directed.
Socket shutters outlet 2/3 pin 6 Amp modular type multi purpose combined two module (ISI marked), complete all as specified & directed.
Socket shutters outlet 2 in 1 pin 6/16 Amp modular type multi purpose combined 2 module (ISI marked), complete all as specified & directed.
Modular switch type stepped fan regulator, single pole, 230 volt two module complete all as specified and directed.
Modular switch type bell push, single pole, 230 volt one module,(ISI marked) complete all as specified and directed.
LED light fitting 1x9W/1X10Wbulkhead luminaires including LED light driver holder connecting up with three core flexible copper conductor cable of suitable size fixed as in repair complete all as specified and directed.
LED lights fitting 1x 20W, 220V, AC decorative box type with driver, holder including LED tube light connecting up with three core flexible copper conductor cable of suitable size from ceiling rose fixed as in repair complete all as specified and directed.
LED light fitting mirror type with high out put diffuser 2 feet, 10 watt 220 V AC decorative type with driver holder and LED lamp including connecting up with three core flexible copper conductor cable of suitable size fixed as in repair complete all as specified and directed.
Surface mounted LED porch down light in engineering plastic housing with clear prismatic diffuser 5 watt capacity white light fixed as in repair complete all as specified and directed.
Taking down carefully old copper or aluminium sub main wiring of any Nos of wiring and size with earth wire on wooden batten/ surface conduit/ casing- capping complete with its all accessories and making good disturbed surfaces of wall , floors etc complete all as specified and directed.
Sub main wiring with two single core FRLSH PVC insulated and unsheathed cable with copper conductor of size 4 Sqmm (nominal area), 1100 Volt grade(with approved colour coding as per IS) with and including continuous earth wire of size 4 Sqmm PVC insulated and unsheathed FRLSH multi stranded copper conductor 1100 volts grade , and connected to main board drawing through PVC concealed conduit 25mm size(minimum size), cutting chases in walls for PVC concealed conduit and making good the disturbed surfaces after taking out old unserviceable sub main wiring complete by provding by wall putty/POP after mason work and finshing to match the original surfaces and nothing extra shall be paid on this account all as specified and directed. Note : (i) For the purpose of measurement, 2 single core of 4 sqmm and one single core of 04 sqmm cable along with PVC conduit shall be considered as 1 running metre. (ii) cutting chases and PVC conduit will be measured and paid separtely
Sub main wiring with two single core FRLSH PVC insulated and unsheathed cable with copper conductor of size 6 Sqmm (nominal area), 1100 Volt grade(with approved colour coding as per IS) with and including continuous earth wire of size 6 Sqmm PVC insulated and unsheathed FRLSH multi stranded copper conductor 1100 volts grade , and connected to main board drawing through PVC concealed conduit 25mm size(minimum size), cutting chases in walls for PVC concealed conduit and making good the disturbed surfaces after taking out old unserviceable sub main wiring complete by provding by wall putty/POP after mason work and finshing to match the original surfaces and nothing extra shall be paid on this account all as specified and directed. Note : (i) For the purpose of measurement, 2 single core of 6 sqmm and one single core of 06 sqmm cable along with PVC conduit shall be considered as 1 running metre. (ii) cutting chases and PVC conduit will be measured and paid separtely
Sub main wiring with four single core FRLSH PVC insulated and unsheathed cable with copper conductor of size 6 Sqmm (nominal area), 1100 Volt grade(with approved colour coding as per IS) with and including continuous earth wire of size 6 Sqmm PVC insulated and unsheathed FRLSH multi stranded copper conductor 1100 volts grade , and connected to main board drawing through PVC concealed conduit 25mm size(minimum size), cutting chases in walls for PVC concealed conduit and making good the disturbed surfaces after taking out old unserviceable sub main wiring complete by provding by wall putty/POP after mason work and finshing to match the original surfaces and nothing extra shall be paid on this account all as specified and directed. Note : (i) For the purpose of measurement, 4 single core of 6 sqmm and one single core of 06 sqmm cable along with PVC conduit shall be considered as 1 running metre. (ii) cutting chases and PVC conduit will be measured and paid separtely
Supply and fixing sub main wiring with two single core FRLSH PVC insulated and unsheathed cable with copper conductor of size 10 Sqmm (nominal area), 1100 Volt grade(with approved colour coding as per IS) with and including continuous earth wire of size 10 Sqmm PVC insulated and unsheathed FRLSH multi stranded copper conductor 1100 volts grade , and connected to main board drawing through PVC concealed conduit 25mm size(minimum size), cutting chases in walls for PVC concealed conduit and making good the disturbed surfaces after taking out old unserviceable sub main wiring complete by provding by wall putty/POP after mason work and finshing to match the original surfaces and nothing extra shall be paid on this account all as specified and directed. Note : (i) For the purpose of measurement, 2 single core of 10 sqmm and one single core of 10 sqmm cable along with PVC conduit shall be considered as 1 running metre. (ii) cutting chases and PVC conduit will be measured and paid separtely
Supply and fixing sub main wiring with four single core FRLSH PVC insulated and unsheathed cable with copper conductor of size 10 Sqmm (nominal area), 1100 Volt grade(with approved colour coding as per IS) with and including continuous earth wire of size 10 Sqmm PVC insulated and unsheathed FRLSH multi stranded copper conductor 1100 volts grade , and connected to main board drawing through PVC concealed conduit 25mm size(minimum size), cutting chases in walls for PVC concealed conduit and making good the disturbed surfaces after taking out old unserviceable sub main wiring complete by provding by wall putty/POP after mason work and finshing to match the original surfaces and nothing extra shall be paid on this account all as specified and directed. Note : (i) For the purpose of measurement, 4 single core of 10 sqmm and one single core of 10 sqmm cable along with PVC conduit shall be considered as 1 running metre. (ii) cutting chases and PVC conduit will be measured and paid separtely
Disconnecting the power supply and taking down carefully by unscrewing from boards fittings and fixtures such as DBs, Junction Box, Panels of any size complete with all MCCB's ,MCB's etc and removing from site, Complete all as specified and directed .
MCCB, 100 Amps, four pole,3 phase , 16KA, 415 volt with adjustable thermal and maganetic release complete all as specified and directed
Vertical TPN distribution board double door flush mounting with provisions for MCCBs incomer upto 100 to 125Amps & outgoing 4 way having IP 54 protection Complete all as specified and directed .
MCB DB, IP 43 protection, powder coated double door with locking arrangement suitable for surface and flush mounting, 12 way SPN with 200 Amps busbar 240V completed all as specified and directed.
MCB DB, IP 43 protection, powder coated double door with locking arrangement suitable for surface and flush mounting, 8 way SPN with 200 Amps busbar 240V completed all as specified and directed.
Sheet metal enclosure for DB, flush mounted single door suitable for 2 way SPN without busbar 240V completed all as specified and directed.
MCB, DP , 240 volt, 32Amps, 10 KA , 'B' series including connection with suitable size aluminium / copper lugs complete all as specified and directed
MCB, DP , 240 volt, 40 to 63Amps, 10 KA , 'B' series including connection with suitable size aluminium / copper lugs complete all as specified and directed
MCB ,SP , 240 volt, 6Amps to 32Amps, 10 KA , 'B' series including connection with suitable size aluminium / copper lugs complete all as specified and directed
MCB ,SP , 240 volt, 63Amps, 10 KA , 'B' series including connection with suitable size aluminium / copper lugs complete all as specified and directed
20 to 25 mm dia, rigid non metallic PVC concealed conduit, 'ISI marked', inclusive of all fittings (such as junction boxes, bends, elbows, tees, reducers, bell mouth tube ends) and all fixing accessories such as couplers lock nuts, saddless, pipe hooks etc for wiring, Complete all as specified and directed .
Cutting chases in brick walls, pinning in, making good to facings where required and pointing in cement mortar (1:3) to ends or edges of landings, steps, cills, sunshades, shelves, lintels, etc and cutting chases for concealed water tubing or concealed conduit wiring etc and making good, cutting not exceeding 10cm girth Complete all as specified and directed .
Earthing complete with galvanized steel earth plate electrode 60cmx60cmx6.00mm thick, burried directly in ground vertically to a depth not less than 2.25m below normal ground level, with top edge of the plate not less than 1.5m below normal ground level, earth plate surrounded by 15cm thick and packed alternate layers of charcoal dust and common salt, connected with and including earth lead of GI wire 4mm dia (8 SWG) by means of bolts, nuts, check nuts and washers of galvanized iron or thimbles and other end of the earth wire connected to main switch board and protected by galvanized iron pipe light grade 15mm dia bore including watering pipe 20mm dia bore GI light grade (ISI marked) with funnel and wire mesh, including all necessary excavation and earth work, PCC chamber in plain cement concrete (1:3:6) type C-1 and pit cover of presast RCC with MS frame etc and all as shown in electrical plate No 3 of MES Sch Part-I (2009), complete all as specified and directed. Note(s) :- (i) RCC pit cover shall be pre-cast of RCC (1:2:4) type B-1, 80mm thick reinforced with XPM not less than 4Kg/Sqm. (ii) PCC chamber shall be constructed 500 mm away from the edge of earth pit. (iii) Rate shall include earth lead and protection pipe of length 7.5m, excess beyond 7.5m length required at site shall be measured and paid separately. (iv) Earth resistance should be less than 3Ohm. In case the test results are not found below 3Ohm, complete earthing will be redone without any extra cost to Govt.
Supply, installing, testing and commissioning of Sealed maintenance free chemical earthing electrode, each individual earthing electrode having following specification :- (a) Diameter of the pipe-80 mm, thickness of the pipe-3.9 mm, Length of the pipe- 3000mm, Galvanised thickness- 80-100 micron, Type of galvanising- Hot dipped , Chemical used in the pipe- High conductive and crystalline conductive mixture ( CCM) , Chemical approx weight 12 Kg. (b) Ground back filled compound 50 kg as conforming to IS 3043 properly mixed the after all around the electrode. (c) Necessary boring in ground in any type of strata/soil and connecting to test point. (d) Construction of brick masonry earth pit of internal size 30cm x 30cm and 30cm deep including finishing work and fixing of CI cover as manufacturer specification complete all as specified and directed (e) Testing for proper working. NOTE- Earth resistance at each grid should be less than 1 ohm at test point .
Galvanised iron strip of size 32 x 6mm, fixed on wall or laid in floors/buried in ground, all as specified and directed.
Multipurpose PVC box with 05 Amps multipin socket and 05 Amps switch with necessary connection including taking down oldunserviceable/rusted box complete and making good the surface as per existing, fixed as in repair complete all as specified and directed
Multipurpose PVC box with 15 Amps multipin socket and 15 Amps switch with necessary connection including taking down oldunserviceable/rusted box complete and making good the surface as per existing, fixed as in repair complete all as specified and directed
Casing capping with fixing accessories of size 20mm width fixed as in repair complete all as specified and directed .
LED pannel surface mounted -2'x2' - 36 watts cool day light fitting with heat exchanger unit, LED driver, surge protection complete including cutting hole of required size in POP/false ceiling making good disturbed including taking down any type ceiling fitting complee all as specified and directed.
LED pannel Recess mounted -2'x2' - 36 watts cool day light fitting with heat exchanger unit, LED driver, surge protection complete including cutting hole of required size in POP/false ceiling making good disturbed including taking down any type ceiling fitting complee all as specified and directed.
LED pannel Recess mounted -2'x2' - 36 watts white light fitting with heat exchanger unit, LED driver, surge protection complete including cutting hole of required size in POP/false ceiling making good disturbed including taking down any type ceiling fitting complee all as specified and directed.
LED candle lamp, 4/5 watt , 230 volt Warm white with big threaded holder, fixed as in repair complete all as specified and directed.
LED candle lamp, 4/5 watt warm white, 230 volt with small threaded holder complete all as specified and directed.
GI bracket made of GI pipe Medium Grade of size 40mm dia 1.5 mtr length bend to shape of 120 degre fixed o pole/wall with clamp of size 50x6 of suitable length fixed with nuts/ bolts and 1.5 mtere long 1.5 sqmm 2 core flexible wire from connector / ceiling rose to light fitting fixed as in repair complete all as specified and directed.
LED secuirty light 35 watt LED with lence and water/ weather proof powder coated high pressure dia cast housing with IP-66 built- in control driver, aluminium reflector, heat resistant toughened clear glass, connector bolck, surge protection with 25 watt LED lamp fixed on ceiling/pole/wall/ with fixing arrangement fixed with nuts bolts and 1.5 sqmm 3 core flexible wire from ceiling rose to light fitting complete including taking down old secrity fitting any type all as specified and directed as per complete. Make : C&S or equivalant of Havells/CG
Aesthetically designed recessed mounted panel in a light weight plastic body 10 W LED 4000K, fixed as in repair complete all as specified and directed. Make-Havells TRIM LED PANEL SQUARE Cat part NO. LHEBLEP6IN1W010 or equivalent in Appx 'C'
Aesthetically designed recessed mounted panel in a light weight plastic body 10 W LED 6000K, fixed as in repair complete all as specified and directed. Make-Havells TRIM LED PANEL SQUARE Cat part NO. LHEBLEP7IN1W010 or equivalent in Appx 'C'
5 Watt LED red & green lamp 230 volt big threaded cool day light with big threaded lamp holder, fixed as in repair complete all as specified and directed
5 Watt LED red & green lamp 230 volt small threaded cool day light with big threaded lamp holder, fixed as in repair complete all as specified and directed
15 watt Red & green incandescent lamp, 230 volt, fixed as in repair complete all as specified and direced.
4/5 watt candle lampe E14 big threaded warm white with big threaded lamp holder, fixed as in repair complete all as specified and directed.
4/5 watt candle lampe E14 small threaded warm white with big threaded lamp holder, fixed as in repair complete all as specified and directed.
LED luminaire ,36w , suitable for recess mounting LED ultra slim ceiling light with extruded aluminium housing with milky diffuser recess mounting ultra slim led 2'x2' panel and including with 36 watts recess mounted complete with drivers and other acessories as per manufacturer's recommendations and connections from ceiling rose fixed as in repair complete all as specified and directed.
Surface mounting powder coated white CRCA full glow LED panel 45 watt capacity and size 2'X2' incl making all connections, fixed as in repair complete all as specified and directed.
3 module cover and plate with machine screw and washers suitable for 3 module sunken box, fixed as in repair complete all as specified and directed
4 module cover and plate with machine screw and washers suitable for 4 module sunken box, fixed as in repair complete all as specified and directed
6 module cover and plate with machine screw and washers suitable for 6 module sunken box, fixed as in repair complete all as specified and directed
Halogen lamp 50mm in size and capacity 40 watt, 240 V fixed as in repair complete all as specified and directed
Aesthetically designed recessed mounted LED downlighter 6'' round shape in a light weight plastic body 10 W LED 6000 K, fixed as in repair complete all as specified.
Aesthetically designed recessed mounted LED downlighter 6'' round shape in a light weight plastic body 10 W LED 4000 K, fixed as in repair complete all as specified.
Aesthetically designed recessed mounted LED downlighter 3'' round shape in a light weight plastic body 10 W LED 6000 K, fixed as in repair complete all as specified.
Aesthetically designed recessed mounted LED downlighter 3'' round shape in a light weight plastic body 10 W LED 4000 K, fixed as in repair complete all as specified.
White flexible/twisted copper cable two core 1.5 sqmm, fixed as in repair complete all as specified and directed
Track LED light with track accessories ( chanel min 1 mtr of 3 track lights etc) 09 watt, fixed as in repair complete all as specified and directed
Soft one frosted 40 watt BC 230 V T 55 milkhy lamp fixed as in repair complete all as specified and directed.
Engagement light with light red and green LED lamp complete all as specified and directed.
LED bed side fitting flexible type 3 watt fixed as in repair complete all as specified and directed.
Horizon Construction Company
Vasudeva Trading Co.
M/s APEX ENTERPRISES
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .