Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹97.3 LAccepted-AOC | ₹97.3 L | L1 | Accepted-AOC Awarded the work with the approval of TPC |
| 2 | L2₹97.8 LRejected-Finance GOLAGHAT | GOLAGHAT | ₹97.8 L | L2 | Rejected-Finance Rejected during Financial Evaluation |
| 3 | Rejected-Technical | - | - | Rejected-Technical Non Responsive |
| 4 | Rejected-Technical | - | - | Rejected-Technical Non Responsive |
| Sl No | Description | Qty | Unit | RAJEEB ELECTRICALS L1 | J.B. Engineers & Associates L2 |
|---|---|---|---|---|---|
| 1.10 | Renovation and modification of 33/11 kV Sariahtali DSS from Auto-recloser based Sub-station to conventional Sub-station under Nalbari ESD-I, APDCL | 1 | LOT | 12,69,434.08 ₹97,32,252.48 Lowest | 12,76,152.08 ₹97,83,810.48 |
Tender Value
₹97.8 L
EMD Value
₹2 L
Closing Date
1 Jan 2026, 12:00 pmClosed
CGMPP_D
CGMPPD6th floor Bijulee Bhawan Paltanbazar
Renovation and modification of Sariahtali DSS from Auto recloser based SS
2025_APDCL_49301_1
APDCL_CGMPPD_Sariahtali_DSS
Open Tender
Electrical Works
Turn-key
Nalbari
Please refer Tender documents.
2 documents required · 2 mandatory
₹5,000
₹2 L
CGMPPD6th floor Bijulee Bhawan Paltanbazar
28 Aug 2026
12 Dec 2025
3 Jan 2026
12 Dec 2025
1 Jan 2026
22 Dec 2025
12 Dec 2025 - 17 Dec 2025
19 Dec 2025
Renovation and modification of 33/11 kV Sariahtali DSS from Auto-recloser based Sub-station to conventional Sub-station under Nalbari ESD-I, APDCL
BoQ_Ver3.0
Name of the Bidder/ Bidding Firm / Company :
ANNEXURE - 1 1. Renovation and modification of 33/11 kV Sariahtali DSS from Auto-recloser based Sub-station to conventional Sub-station under Nalbari ESD-I, APDCL
NUMBER #
TPGO-DBCR with earth switch & GI mounting structure 800 Amps
11 kV 10 kA Lightning Arrestor (station type, class 2)
11 kV 5 kA Lightning Arrestor (line type, distribution class )
11KV Indoor VCB Panel - 9 Unit Equipped with IEC 61850 compliant numerical relays, 0.5s accuracy class cat-A, E2, M2, C2 class Vacuum Circuit Breaker of 26.3kA STC, 1200 A busbar & other components as per standard Technical specification of APDCL
Battery charger 110V suitable for charging 150AH, 110V Battery Bank , Dual mode double circuitry SCR Variac Float & Boost Charger
150AH 110V Maintenance Free Battery Bank (VRLA Battery Bank)
415V AC Distribution Board (O/g feeders 6 Nos.)
110V DC Distribution Board (O/g feeders 4 Nos.)
11 kV Grade (armoured) 1Cx 300 sqmm
XLPE Cable jointing Kit-11 kV, 1Cx300 sqmm (outdoor type)
ACSR Wolf conductor
Aluminium Lug- 300 sqmm
GI Nuts & Bolts with washer (assorted)
33 kV Polymeric Pin Insulator (FRP-34mm)
33 kV Disc Insulator (polymeric) 70 kN B&S type
H/w fittings for Disc Insulator B&S 70 kN tension type
PG clamp for ACSR Wolf
Control Cable, 1.1 kV Grade (copper), 4C x 2.5 sqmm
Control Cable, 1.1 kV Grade (copper), 2C x 2.5 sqmm
Control Cable, 1.1 kV Grade (copper), 7C x 2.5 sqmm
GI earthing Pipe 50mm dia 3m length 3.15 mm thickness with perforated holes of 15mm dia at 30 cm interval along length of the pipe
Installation of earthing system with MS flats 50x10mm (for earthing mat) with GI flat riser 25x6mm (for earthing conductor) and GI pipe 50mm dia of length 3000mm for earth electrodes) including excavation of earth welding etc. as necessary
GI Strip 25x3 mm for DTR earthing
GI Strip 50x6 mm for DTR Neutral earthing
Construction of RCC switchyard Cable Trenches Size (500x675)mm including trays of MS/GI for cable including supply of all materials and installation of 75 mm RCC slab for cover as per specification and drawing
RCC foundation for 33KV Isolator as per standard drawing and technical specifications
Switch yard gravelling of 0.15 mtr. (thickness) by 40mm size crushed stone
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.24 MB
BOQ_78275.xls
BOQ • 0.32 MB
Bid_Sariahtali.pdf
Tender Documents • 4.82 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].