| 1 | L1₹23.7 LAccepted-AOC | L1 | Accepted-AOC Lowest bidder | |
| 2 | L2₹25.8 L+₹88,525 (3.56%)Rejected-Finance 0000 UNNAMED ROAD GAJIYA KANTIT VINDHYACHAL MIRZAPUR UTTAR PRADESH 231307 | MIRZAPUR | UTTAR PRADESH | 231307 | L2 | Rejected-Finance Other than lowest bidder | |
| 3 | L3₹25.9 L+₹95,725 (3.85%)Rejected-Finance INDEX NO E 29 CWE JRC 352 3 GURU NANAK PURA EAST JALANDHAR CITY PIN 144001 | JALANDHAR CITY | JALANDHAR | PUNJAB | 144001 | L3 | Rejected-Finance Other than lowest bidder | |
| 4 | L4₹26.5 L+₹1.6 L (6.36%)Rejected-Finance 5B FF NAND VIHAR AZAD NAGAR NEAR GODARA PETROL PUMP HISAR HARYANA 125001 | HISAR | HARYANA | 125001 | L4 | Rejected-Finance Other than lowest bidder |
Tender Value
₹40 L
EMD Value
₹80,000
Closing Date
31 Dec 2024, 6:00 pmClosed
GE Kapurthala
GE Kapurthala
Repair/Maintenance of distribution board and connected items at Mil Stn Beas under GE Kapurthala.
2024_MES_686762_1
GE KPT- /2024-25
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Area under GE Kapurthala
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
Yes
GE Kapurthala
₹80,000
Yes
1 Feb 2025
3 Dec 2024
7 Jan 2025
3 Dec 2024
31 Dec 2024
17 Dec 2024
Amount
Taking down old unsv MCB DB and S&F sheet metal enclosure for MCB DB double door single pole & Neutral 4 way with 200 Amps rated bus bar complete all as specified and as directed by Engr-in-Charge. Make : Legrand/L&T /Havells or equivalent in list of Makes as per Appx B-1.
Taking down old unsv MCB DB and S&F sheet metal enclosure for MCB DB double door single pole & Neutral 8 way with 200 Amps rated bus bar complete all as specified and as directed by Engr-in-Charge. Make : Legrand/L&T /Havells or equivalent in list of Makes as per Appx B-1.
Taking down old unsv MCB DB and S&F sheet metal enclosure for MCB DB double door Triple pole & Neutral 4 way with 200 Amps rated bus bar complete all as specified and as directed by Engr-in-Charge. Make : Legrand/L&T /Havells or equivalent in list of Makes as per Appx B-1.
S & F in repair Miniature Circuit Breaker (MCB) ‘B’ Curve (In accordance with IS/IEC 60898-1) 240 V, 50 Hz,10 kA Suitable for lighting and other domestic loads Single pole 6 to 32 Amp complete all as specified and as directed by Engr-in-Charge.
S & F in repair Miniature Circuit Breaker (MCB) ‘B’ Curve (In accordance with IS/IEC 60898-1) 240 V, 50 Hz,10 kA Suitable for lighting and other domestic loads Single pole & neutral 6 to 32 Amp complete all as specified and as directed by Engr-in-Charge.
S & F in repair Miniature Circuit Breaker (MCB) ‘B’ Curve (In accordance with IS/IEC 60898-1) 240 V, 50 Hz,10 kA Suitable for lighting and other domestic loads Triple pole & neutral 6 to 32 Amp complete all as specified and as directed by Engr-in-Charge.
S & F in repair Miniature Circuit Breaker (MCB) ‘B’ Curve (In accordance with IS/IEC 60898-1) 240 V, 50 Hz,10 kA Suitable for lighting and other domestic loads Triple pole & neutral 40 Amp complete all as specified and as directed by Engr-in-Charge.
S&F in repair VTPN DB, Double door, IP 43, 4 way, 415 Volt including incommer as MCCB 100A, 10 KA fixed type 01 Nos, MCB SP 5 to 32 - 12 Nos complete incuding taking down existing DB any type and connecting it with existing cables complete all as specified and as directed by Engr-in-Charge.
Taking down old unsv bus bar any type and S&F of new aluminium busbar panel TPN 200 Amp , 415 volt complete all as specified and as directed by Engr-in-Charge. Make : Havells/Indo Asian/Legrand or equivalent in list of Makes as per Appx B-1.
Taking down old unsv bus bar any type and S&F of new aluminium busbar panel TPN 100 Amp , 415 volt complete all as specified and as directed by Engr-in-Charge. Make : Havells/Indo Asian/Legrand or equivalent in list of Makes as per Appx B-1.
M&L for earthing complete with galvanized iron or steel or steel earth plate electrode of size 60cmx60cmx6.3mm thick buried directly in ground, vertically to a depth not less than 2.25 mtr below normal ground level with top edge of earth plate at depth of not less than 1.5 mtr below ground level surrounded from all sides with alternate layers of charcoal and common salt and connected to GI Strip of size 32x6 mm by means of GI bolts, nuts washers & check nuts electrode connected to main switch board or main control board or on poles or on transformer and GI pipe light grade 20 mm bore for watering including providing funnel and wire mesh GI frame and 10 cm thick suitably reinforced RCC pit cover PCC chamber pit with PCC 1:3:6 type C2 using 40mm graded stone aggregates complete all as specified and as directed by Engr-in-Charge including excavation and earth work, disposal of surplus soil to a distance not exceeding 50 mtr all as specified and shown in plate No 5 of SRR-1991 Part-1.
M&L for Earthing complete with galvanized steel earth plate electrode 60 cm x 60 cm x 6 mm thick surrounded with charcoal and salt, buried directly in ground (earth pit not less than 2.25 metre deep below ground level) with top edge of plate not less than 1.5 metre below normal ground level connected to galvanized earth lead wire 4 mm dia by means of bolts, nuts, check nuts and washers of galvanized iron or steel all as shown in electrical Plate No 3 of MES SSR Part-I connected to main switch board or main control board all as specified and testing on completion including provision of earth wire protected by galvanized iron 15 mm dia light grade pipe and watering pipe shall be 20 mm bore light grade including all excavation and earth work in any type of soil, PCC pit with pre-cast RCC cover, charcoal/salt, funnel etc complete all as specified and as directed by Engr-in-Charge.
Supply and fixing aluminum thimbles crimping type of size 16 to 25 Sqmm complete all as specified and as directed by Engr-in-Charge.
Supply and fixing aluminum thimbles crimping type of size 50 to 120 Sqmm complete all as specified and as directed by Engr-in-Charge.
Taking out old defective service cable/underground cable from trenches/floors/road/wall/pipe/pole LT cable of any size/description including segregating the serviceable cable by cutting down defective portion after testing by meggar and relaying complete all as specified and directed by Engr-in-Charge. (Note : Excavation and earth work will be measured separately under respective item)
Supply, Laying, jointing and testing XLPE insulated LT cable, 1100 volts grade (heavy duty) with stranded aluminium conductor, cross sectional area 10 Sqmm 2 core fixed along the poles or passing through pipes or laid under floors or through walls complete all as specified and directed by Engr-in-Charge. Note : Earthwork, sand cushioning, brick protection and GI pipe to be measured and paid for separately under respective items.
All as per description of serial item No.16 here in before but cross sectional area 16 Sqmm 2 core complete all as specified and directed by Engr-in-Charge.
All as per description of serial item No.16 here in before but cross sectional area 16 Sqmm 4 core complete all as specified and directed by Engr-in-Charge.
All as per description of serial item No.16 here in before but cross sectional area 25 Sqmm 3½ core complete all as specified and directed by Engr-in-Charge.
All as per description of serial item No.16 here in before but cross sectional area 35 Sqmm 3½ core complete all as specified and directed by Engr-in-Charge.
All as per description of serial item No.16 here in before but cross sectional area 50 Sqmm 3½ core complete all as specified and directed by Engr-in-Charge.
All as per description of serial item No. 16 here in before but cross sectional area 70 Sqmm 3½ core complete all as specified and directed by Engr-in-Charge.
Excavation in trenches in soft/loose soil not exceeding 1.50 mtr wide and not exceeding 1.50 mtr in depth for laying of cables and getting out including trimming of sides complete all as specified and directed by Engineer-in-Charge.
Returing, filling in, including spreading, leveling watering and well ramming in layers not exceeding 25 cms thick each layer complete all as specified and directed by Engineer-in-Charge.
Removal of surplus soil to a distance not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed by Engineer-in-charge.
Material and labour for sand cushioning with a layer of sand 8cm thick before laying of cable and 15 cm thick after laying of cable in trenches complete all as specified and as directed by Engr-in-Charge. Note : For payment purposes 18cm thickness shall be considered.
Supply & laying old size sub class 'B' bricks laid flat in trenches over the cable with the length of brick perpendicular to the direction of cable length, adjacent/abutting each other complete all as specified and directed by Engineer-in-charge.
M&L for straight through joint (epoxy) for LT 1100 Volts grade, aluminum conductor including jointing kits, aluminium ferrules and labour complete for making joints and testing size 70 to 95 Sqmm, 3.5 core complete all as specified and as directed by Engr-in-Charge.
All as per Item No 28 above but cable size 25 to 50 Sqmm, 3.5 core complete all as specified and as directed by Engr-in-Charge.
All as per item No 28 above but cable size 10 to 16 Sqmm, 4.0/2.0 core complete all as specified and as directed by Engr-in-Charge.
Supply and fixing in replacement 50mm dia pipe for GI protection, light grade for cable protection incl all fittings laid in trenches or fixed on pole all as specified and as directed by Engr-in-Charge.
Supply and fixing in replacement 80mm dia pipe for GI protection, light grade for cable protection incl all fittings laid in trenches or fixed on pole all as specified and as directed by Engr-in-Charge.
Taking down old unsv main switches any type and S&F of new street light switch using timer for automatic switching of street light based on LUX level of natural light, The sensor along with suitable power contactor MCB support terminal shell be housed in enclosure made out of anti rust/ shock proof/ termite proof/ confirming to IP54 suitable for 16Amp load (Contactor shall be used of Make of ABB/BCH/Legrand/ Indo Asian/Havells or equivalent in list of makes as mentioned in Appx B-1.
M & L for Locating & pinpointing conductor and insulation faults of low and high resistance, intermittent or flashing nature in XLPE LT underground power cables of the rating 415Volt with the help of Pre-locator with time domain laptop based reflectometer/ electrometer using pulse echo method, impulse current method & decay method, and using DC high voltage surge generator to produce surge to trace route and pinpointing fault with the help of dual channel digital sound system, magnetic & acoustic for location of fault with acoustic transducer (pickup) and the amplifier with headphones, after pinpointing of fault location necessary excavation upto 10 mtr length and taking out of faulty cable for repair/replacement of joint, relaying of cable/ cover & brick protection, refilling of soil and removal of surplus soil etc all as specified and directed by Engr-in-Charge. Note:- 1. The joint shall be measured and paid separately under relevant item. The qty of item will be executed at different times during currency of contract or as required basis as directed by Engr-in-Charge. Hence, contractor shall quote his rate accordingly for arranging and executing the items accordingly. 2. Fault should be detected and rectified within 24 hrs from intimation to contractor after that penalty be levied on contractor at the rate of Rs 500 per hour till the rectification.
J.K & Company (BID ID -3202945)
Northern cable fault locatoers (BID ID -3203233)
SUN MANN ENGINEERS (BID ID -3197320)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .