| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹9.4 LAccepted-AOC 366 SEC 3 GANGYAL GARDEN GANGYAL JAMMU JAMMU JAMMU KASHMIR 180010 | JAMMU | JAMMU AND KASHMIR | 180010 | L1 | Accepted-AOC Being L1 |
Tender Value
₹9.7 L
EMD Value
₹19,400
Closing Date
11 Sept 2017, 2:00 pmClosed
Executive Engineer University Works Department
Executive Engineer University Works Department University of Jammu
Supply and Installation of 125 KVA DGSET in the Brig. Rajinder Singh Auditorium at New University Campus, Jammu
2017_UDJK_43975_1
Fresh eNIT 270 dated 16-08-2017
Open Tender
Electrical Works
Item Rate
30 days
University of Jammu
Please refer Tender documents.
2 documents required · 2 mandatory
₹500
Yes
Executive Engineer University Works Department
₹19,400
Yes
30 Sept 2021
23 Aug 2017
12 Sept 2017
23 Aug 2017
11 Sept 2017
23 Aug 2017
Amount
Providing, Installing, testing and commissioning of silent type Diesel generating set alongwith having prime power rating of 125 KVA 415 volts at 1500 RPM, 0.8 lagging power factor at 415V suitable for 50 Hz, 3 Phase system and for 0.85 load factor and consisting of the followings:- a) Diesel Engine:- Diesel Engine 4 stroke water cooled electric start of 156 BHP at 1500 RPM suitable for above output of alternator at 40 degree C, 50% RH at at 1000 Meter MSL and conforming to BS 5514, BS 649, IS 10000 capable of taking 10% over loading for one hour after 12 hours of continuous operation. The engine will be fitted complete with all the required accessories. b) Engine mounted instrument panel fitted with and having digital display for following: (i) Start-Stop Switch with key (ii) Water temperature indication (iii) Lubrication oil pressure indication (iv) Lubrication oil temperature indication (v) Battery charging indication (vi) RPM Indication (vii) Over Speed indication (viii) Low lub oil trip indication (ix) Engine hours indication c) Alternator:-Synchronous alternator rated at 125 KVA 415 volts at 1500 RPM, 3 Phase 50 Hz. AC Supply with 0.8 lagging power factor at 40 degree C, 50% RH and at 1000 meter MSL. The alternator shall be having SPSD enclosure, brushless continuous duty, self-excited and self-regulated through AVR conforming to IS:4722/BS 2613 suitable for tropical conditions and with class-F/H insulation. d) Base Frame and Foundation:-Both the engine and alternator shall be mounted on suitable base frame made of MS Channel with necessary reinforcement which shall be installed on suitable existing cement concrete foundation and vibration isolation arrangement as per recommendations of manufacturer. e) Fuel Tank:-Minimum Daily Service fuel tank of 225 litres capacity fabricated out of 3mm thick M.S Sheet complete with all standard accessories and fuel piping between fuel tank and diesel engine with MS Class ‘C’ pipes of suitable dia complete with valves, level indications and accessories as required as per specifications. f) Exhaust System:-Dry exhaust manifold with hospital exhaust silencer and catalytic convertor. g) Starting System:-12V/24V DC starting system comprising of starter motors: voltage regulator and arrangement for initial excitation complete with suitable Nos. of batteries plates, 180 Amp. hour capacity lead acid type as required as per specifications. h) Acoustic and weather proof enclosure with arrangement for fresh air intake for cooling of the engine and alternator, extraction, discharging hot air in to the atmosphere as per specifications. Including construction of base platform for placing of Genset. The size of platform is (15’X9’X 1’-6”) of M-10 Grade (1:3:6) 1Cement,3Sand,6 (20mm) crushed course agg. including plastering the exposed surface in C:M 1:4(Including all the taxes applicable, contractor profit and overhead) (Make Engines:- Cummins, Catterpiller, Kirloskar Green, Mahindra, Ashok Leyland) (Make Alternators:- Stamford, Leyroy sommers, Kirloskar Green, Mahindra,Ashok Leyland).
Earthing with Copper Plate 600mmx600mmx3mm thick including accessories and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcoal/coke and salt as required.
Supply and laying 4mm copper wire on surface/recess for connection.
Supply & Laying of following size PVC insulated PVC sheathed aluminum conductor 1100 volts graded armoured cable including end termination, cost of thimbles, nuts, bolts clamp glades etc. connection, testing and commissioning including digging the trench where required and refilling back complete job (Make Havells/Polycab/Plaza/Grandley) 3.5 CORE 185 SQMM
Supply and fixing of 315 Amp online I-O-II four pole with advanced neutral change over switch confirms to IS 13947(Part-3) IEC:60947-3 (Make Havells/Legrand/ HPL/ I.A/Anchor) including providing the MCCB panel/ Enclosure/ Busbars.
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .