Electrical work in connection with provision of Electronics interlocking under remodeling work at LJN yard, Proposal for extension of electric loco shed at Lucknow Jn. yard, CYM Building at coaching Depot ASH and development of goods platform surface, fencing etc. at Pardhan and approach road at BKT Railway Stn.
SRDEE-LJN-04-2026
SRDEE-LJN-04-2026
Open
6 Months
Lucknow, Uttar Pradesh
₹0
₹1.6 L
2 Jun 2026
2 Jun 2026
15 Jun 2026
A-Electrical work in connection with provision of Electronics interlocking
Supply and recessing/fixing of PVC Conduit pipe 25 mm (Medium) conforming to IS 9537/ Part III/1983 (Latest version) with accessories, junction box, etc including making chase, plastering/ clamping etc as per technical specifications.
Supply of PVC insulated multi stranded copper conductor single core FRLS cable 2.5 2 Sq. mm conforming to IS: 694(latest version), and drawing in laid (recessed /surface) PVC conduit pipe for wiring of point wiring/ circuit wiring/sub main/ Main as required as per technical specification including connections, testing and commissioning.
Supply of PVC insulated multi stranded copper conductor single core FRLS cable 4.0 3 Sq. mm conforming to IS: 694 (latest version), and drawing in laid (recessed /surface) PVC conduit pipe for wiring of point wiring/ circuit wiring/sub main/ Main as required as per technical specification including connections, testing and commissioning.
Supply of PVC insulated multi stranded copper conductor single core FRLS cable 6.0 4 Sq. mm conforming to IS: 694 (latest version), and drawing in laid (recessed /surface) PVC conduit pipe for wiring of point wiring/ circuit wiring/sub main/ Main as required as per technical specification including connections, testing and commissioning.
Wiring for circuit / sub main wiring along with earth wire with the following sizes of 5 FRLS PVC insulated copper conductor, single core cable in surface/recessed PVC conduit as required. 2 x 10sq. mm+ 1 x 10 sq. mm earth wire.
Supply and Installation of Ceiling rose 3 plate as per IS No. 371/1999 (Latest Version) including connections, Testing and commissioning as per Tech. Specification.
Supply of PVC insulated multi stranded copper conductor single core FRLS cable 1.5 7 Sq. mm conforming to IS: 694 (latest version), and drawing in laid (recessed /surface) PVC conduit pipe for Earth Wire as required as per technical specification including connections, testing and commissioning.
Carting of Material from Railway site supervisor's depot to site (Only for the material supplied by Railway and returning of Released material from site to store depot of Supervisor)
Supply, Erection, Testing and Commissioning of following Modular Type switch 6/10A (1-way) complete in all respect.
Supply, Erection, Testing and Commissioning of following Modular type Plug socket outlet 2/3 Pin 6/10A complete in all respect.
Supply, Erection, Testing and Commissioning of following Modular Type switch 16/20A (1-way) complete in all respect.
Supply, Erection, Testing and Commissioning of following Modular type Plug socket outlet 5/3 Pin 16/20A complete in all respect.
Supply, Erection, Testing and Commissioning of following Modular type step type Electronic Fan Regulator complete in all respect.
Supply and Erection of Modular type switch blanking set to fill the blank space White finished mounting cover plate complete in all respect.
Supply and Erection of Fan Sheet Cover POP type complete in all respect including hardware material for fixing.
Supply and Erection of Junction Box cover POP type complete in all respect including hardware material for fixing.
Supply and Erection of white finish single mounting cover plate with base frame suitable 3 module suitable for mounting of Modular type piano switches/ plug Socket, fan regulator and connection to wiring.
Supply and Erection of white finish single mounting cover plate with base frame suitable 8 module suitable for mounting of Modular type piano switches/ plug Socket, fan regulator and connection to wiring.
Supply and Erection of white finish single mounting cover plate with base frame suitable 12 module suitable for mounting of Modular type piano switches/ plug Socket, fan regulator and connection to wiring.
Supply and Erection of Modular Metal boxes concealed Boards suitable for mounting of 3 module white finish single mounting cover plate with Frame and Modular type piano switches/ plug Socket, fan regulators. Metal board boxes are to be concealed in wall.
Supply and Erection of Modular Metal boxes concealed Boards suitable for mounting of 8 module white finish single mounting cover plate with Frame and Modular type piano switches/ plug Socket, fan regulators. Metal board boxes are to be concealed in wall.
Supply and Erection of Modular Metal boxes concealed Boards suitable for mounting of 12 module white finish single mounting cover plate with Frame and Modular type piano switches/ plug Socket, fan regulators. Metal board boxes are to be concealed in wall.
Installation, connection with Twin core PVC insulated flexible copper conductor HRFR cable of size 14/0.193 mm (0.41 Sq. mm) testing and commissioning of 1200/ 1400 mm sweep AC ceiling fan/Air Circulator (on the installed CI/MS Box) including earthing as per technical specification. (NOTE:- A.C. Ceiling fan/Air Circulator in packed conditions will be supplied by Railways.)
Supply and recessing/fixing on surface of 6 SWG GI wire conforming to IS: 280/2006 (Latest Version) for loop earthing as required for earthing of installation as per IE Rule.
Supply, Installaion, Testing and Commissioning of SPN MCB Distribution Board 8 Way 25 double door made with 1.2mm thickness CRCA sheet fully powder coated of 50-70 micron with 01 No. MCB 02 Pole 40 Amp 10 KA 230V as incoming and 06 Nos. MCB of 6-20 Amp single pole 10 KA 230 Volt as outgoing complete in all respect including connection as required.
Supply, Erection, Testing and Commissioning of following Modular type Socket with MCB 25 Amps for AC Unit complete in all respect.
Fabrication, Supply and Fixing of Fan Hook with clamp duly painted made of 50x6 mm MS Flat with nut bolts suitable to fix on PP shelter bracing angle as required.
Fabrication and Supply of Ceiling Fan Down Rod 3 feet long fabricated by 12 mm mild steel pipe duly painted with clamp, Fastners, Insulator and split pin complete in all respect
Installation on Wall/Ceiling with grouting of M.S. Nut Bolts 3/8 inch dia, connection 29 with Twin core PVC insulated flexible copper conductor FR cable of size 14/0.193 mm including testing & commissioning of pre-wired indoor LED fitting complete with as per technical specification including earthing complete in all respect. NOTE:- LED fitting will be supplied by Railways in packed conditions.
Supply, Installation, Testing and Commissioning of Phase Selector TPN Distribution Board with Metal door powder painted with inbuilt 3 Nos 63 Amp Phase Selector, 100 A copper 30 busbar for each phase and neutral bar duly wired and provision for 8 Module for incomer, 24 module for SP outgoing (8 Way in each phase), earth bar and Din rail etc. conforming to IS: 13032/1991 and IS 8623 (Pt I and III)/1993. along with supply and fixing of 01 No. MCB 63 Amp 4 pole, 10 KA, 230 VAC and 24 No. MCB Single Pole 6/10/16/25 Amp 10 KA, 230 VAC complete in all respect including connection as required.
Supply, Installation, Testing and Commissioning of Earthing with pipe 4.5 meter long 31 and 40 mm dia with masonry enclosure on the top with RCC Cover including earth connection to equipment with 4 mm dia G.I. wire in 15 mm dia G.I. pipe and using salt and charcoal for pipe earth electrode as per drawing L/16/STD/86 as enclosed as per IS 3043/1987 (latest Version).
Supply, erection, testing & commissioning of maintenance free earthing arrangement 32 (Chemical earthing with low impedance, corrosion resistant & long life). Earth electrode is made up of high tensile low carbon steel circular rods bonded with copper on outer surface and interconnection of earth electrode with suitable size copper strip. The earth electrode shall be of minimum 17.0 mm diameter and 3.66 meter length as per details given technical specification
Laying of L. T. Cable of required size in open/air/along wall/ along pole with clamping arrangement conforming to IS:1255/1983 (Latest Version). (Cable will be supplied by Railway)
Laying of 1 No. XLPE insulated and PVC sheathed power cable of grade 1.1 KV size 3½/4 core size exceeding 25 sq mm but not exceeding 400/120 Sq mm Alluminium conductor cable direct in ground including excavation, sand cushioning, protective covering and refilling the trench 34 etc. as required. Cable laying should be as per IS-1255/1983 with latest ammendments. Digging of trench in all kinds of soil up to the depth of 1000 mm and 350 mm wide for laying of cable with supply and placing of second-class bricks, approx. 10 bricks per meter, refilling of cable trench with solid earth consolidating by ramming by 270 mm above the surrounding level over trench. (Cable will be supplied by Railway)
Laying and Fixing of one No. Additional PVC/XLPE Insulated PVC sheathed aluminium conductor L.T. power cable 3½/4 core of grade 1.1 KV of size exceeding 25 sq mm but not exceeding 400/120 Sq. mm in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench etc. as required. Cable laying should be as per IS-1255/1983 with latest ammendments. Digging of trench in all kinds of soil up to the depth of 1000 mm and 350 mm wide for laying of cable with supply and placing of second- class bricks, approx. 10 bricks per meter, refilling of cable trench with solid earth consolidating by ramming by 270 mm above the surrounding level over trench. (Cable will be supplied by Railway)
Supply, Installation, Testing and Commissioning of Busbar Chamber System 200 A Rating Four Pole 4 way type conforming to IS:8623 and IS:2147 with latest version busbar layout 36 stack layer type short circuit withstand capacity 35 KA Degree of protection IP 31 fabricated with sheet steel (CRCA) 1.6 mm thickness and epoxy powder coated, bus bar section made of ETP grade copper dull tin plated with DMC support, Neutral bus bar fully rated, top and bottom end plate detachable suitable for 440 V 50 HZ AC Supply complete in all respect.
Supply and making outdoor end termination with heat shrinkable jointing kit 37 conforming to IS: 13573/1992 (Latest version) complete with all accessories including aluminium lugs suitable for 3 core 120 Sq. mm HT XLPE aluminium conductor cable of 11 KV (Earthed) grade complete in all respect as required.
Laying of 1 No. 11 KV (E) XLPE insulated armoured Aluminium conductor 3 core 120 Sq. mm cable conforming to IS:7098 (Pt.II) (Latest version) in ground in single trench in one tier hirizontal formation at depth of not less than 1 meter below ground level including excavation, sand 38 cushioning of 80 mm thick all-round etc. protective covering with bricks on side & top, refilling the trench as per technical specification including testing and commissioning. Digging of trench in all kinds of soil up to the depth of 1000 mm and 350 mm wide for laying of cable with supply and placing of second-class bricks, approx. 10 bricks per meter, refilling of cable trench with solid earth consolidating by ramming by 270 mm above the surrounding level over trench. (Cable will be supplied by Railway)
Laying of 1 No. additional 11 KV (E) XLPE insulated armoured Aluminium conductor 3 core 120 Sq. mm cable conforming to IS:7098 (Pt.II) (Latest version) in ground in the same above trench in one tier hirizontal formation at depth of not less than 1 meter below ground level including 39 excavation, sand cushioning of 80 mm thick all-round etc. protective covering with bricks on side & top, refilling the trench as per technical specification including testing and commissioning. Digging of trench in all kinds of soil up to the depth of 1000 mm and 350 mm wide for laying of cable with supply and placing of second-class bricks, approx. 10 bricks per meter, refilling of cable trench with solid earth consolidating by ramming by 270 mm above the surrounding level over trench. (Cable will be supplied by Railway)
Supply, Fabrication and Erection of angle iron 35 x 35 x 5 mm / 40 x 40 x 6 mm / 50x 40 50 x 6 mm conforming to IS: 808/1989 (Latest Version)/M.S. Plate for making structure/ bracket as supporting arrangement for any equipment complete with clamp, nut bolt etc. complete in all respect as per site requirement.
Supplying, fabrication, installing, fixing of MS sheet junction box (outdoor type) size 450x450x200 mm made of 1.6 mm thick M.S. sheet having lockable cover duly painted with gray 41 paint over red oxide primer duly naming 240/415 volts with red paint complete with 3 phase aluminium bus-bar one for neutral with Al. strips 40x10 mm fixed with bus-bar insulators including suitable size of cable gland in bottom side for incoming & outgoing cable and including double earthing stud complete in all respect.
Cutting of CC work of Platform/Road for laying of cable and supply of Cement and sand for repairing of the CC work of platform/Road as per the directive of site in charge complete in all respect.
Supply, Installation, Testing and Commissioning of Busbar Chamber System 63 A Rating Four Pole 4 way type conforming to IS:8623 and IS:2147 with latest version busbar layout 43 stack layer type short circuit withstand capacity 35 KA Degree of protection IP 31 fabricated with sheet steel (CRCA) 1.6 mm thickness and epoxy powder coated, bus bar section made of ETP grade copper dull tin plated with DMC support, Neutral bus bar fully rated, top and bottom end plate detachable suitable for 440 V 50 HZ AC Supply complete in all respect.
Supply & Laying of 100 mm dia C. I. Pipe (Spun pipe) conforming to IS 1536/2001 with latest amendment class LA & ISI Marked
Cement Concrete Foundation, ratio 1:2:4 with 20 mm and down graded stone aggregate and coarse sand as per site requirement.
Manufacturing, Supply, Erection, Testing and Commissioning of Feeder Pillar equipped with three phase & Neutral bus bar aluminium capable for 400 Amp capacity for each 46 phase and neutral. Feeder panel box shall be made with 1.6 mm CRCA sheet duly painted size 1000 mm height x 600 mm width x 350 mm depth with both side hinged door along with locking arrangement and feeder pillar to be grouted on ground with help of four No. mounting angle of size 50x50x6 mm of length 500 mm above ground the cost should also be include the cost of end cable termination with proper size cable lugs & cable glands.
Excavation of trenchless track by horizontal direct drilling (HDD) method under 47 Railway track/busy road etc. at a depth of minimum 120 CM below ground level as per direction of site engineer incharge along with Supply and Laying of HDPE Pipe of 150/160 mm inner dia confirming to relevant IS in HDD portion. (HDPE Pipe shall be supplied by Contractor)
All work pertaining to Horizontal Directional Drilling (HDD)/Boring and trench less cabling. It includes supply, transportation and insertion of self-lubricated HDPE pipe and laying of 48 cable in boring under the track/road by using different sizes of pipes depending on total number of cables will be crossed. The depth of horizontal boring should be minimum 3.0 Mtrs from rail flange/road level. This item will be used for track crossing of running lines. By using self-lubricated HDPE pipe of 120/125 mm outer dia in the bore and the laying of cables in the bore and the laying of cables in the bore under the track/road. (HDPE Pipe shall be supplied by contractor)
Supply and Laying of G.I. Pipe 80 mm dia. class B ISI marked under road/rail clamping with erected pole or wall as per technical specification for passing cable of different size.
Installation, on wall with grouting of MS Nut & bolt 3/8" dia, connection with Twin core 50 PVC insulated flexible copper conductor HRFR cable of size 14/0.193 mm (0.41 Sq. mm) including testing & commissioning of Exhaust fan 300/380/450 mm sweep complete with louver shutters as per Tech. specification including earthing. NOTE:- Exhaust Fan & Louver shutters will be supplied by Railways in packed conditions.
Installation and Commissioning of LED Street Light/Flood Light fitting on pole including connection with Twin core PVC insulated flexible copper conductor cable of size 1.5 Sq. mm complete in all respect. ( LED Street Light/Flood Light fitting will be supplied by Railway)
Supply, Installation, Testing and Commissioning of 7 Mt. High Hot dip galvanized octagonal pole with longitudinal seam weld throughout the length with bottom 130 mm across face, 52 Top 70 mm across face made of 3 mm thick High Tensile plate and 220 mm x 220 mm x 12 mm base plate complete with one arm of 500 mm for fitting installation and 04 No. M20 (EN 8 Gr) x 700 mm long J type foundation bolt set complete in all respect with RCC foundation as per attached drawing. The material shall be inspected at manufacturer's premises by RITES and inspection charges shall be borne by the firm.
Supply of Double wall corrugated (DWC) pipes for under ground power cable 53 protection with IS:14930 Part - II mark on duly printed at every one meter interval along with the socket coupler with IP 67 protecting for coupling where ever required. The DWC pipe shall be rodent proof and fire resistant and size of outer dia 90 mm and inner dia 76 mm.
Excavation of cable trench of 110 Cm Depth and 30 Cm wide in all kinds of soil and its refilling with the same excavated soft soil.
Laying of DWC pipe (90/76 mm) with socket coupler in trenches as per requirement.
Supply and Fixing of Hot Dip galvanized perforated type cable tray 100 mm width and 50 mm height made with 14 SWG Sheet.
Supply and fixing of Hot Dip galvanized type cover plate for 100 mm width cable tray with 18 SWG Sheet.
Supply and Fixing of Coupler plate with hardware for 50 mm Height Hot Dip galvanized/powder coated type trays
Supply, Installation, Testing & Commissioning of MCCB 32/63 Amps, 4 pole breaking 59 capacity 25 KA at 415 V,50 Hz, thermal release range 25-32A/50-63 A, Ics = 100% Icu including hard wares and insulators as required along with sheet steel enclosure duly painted complete in all respect.
Supply, Installation, Testing and Commissioning of Slim surface mounted Round LED 60 downlight 18 W, rated voltage 240 VAC, 50 Hz, operating voltage range 90-260 volt, operating temperature range -10 degree C to +50 degree C, colour temperature 6000K, White powder coated, pressure die cast aluminum housing, integral Driver and accessories pre- wired up to terminal block, luminaire lumen out put not less than 2048 lumen complete in all respect.
Supply, Installation, Testing and Commissioning of Slim surface mounted Square LED 61 downlight 18 W, rated voltage 240 VAC, 50 Hz, operating voltage range 90-260 volt, operating temperature range -10 degree C to +50 degree C, colour temperature 6000K, White powder coated, pressure die cast aluminum housing, integral Driver and accessories pre- wired up to terminal block, luminaire lumen out put not less than 2048 lumen complete in all respect.
Installation, Testing and Commissioning of 5/7 Mtr. High Hot dip galvanized octagonal 62 pole with longitudinal seam weld throughout the length Including supply of 04 No. M20 (EN 8 Gr) x 700 mm long J type foundation bolt set complete in all respect with RCC foundation. (Railway will supply only 5/7 Mtr long Octagonal pole with arm)
Supply, Installation, Testing and Commissioning of 30 W Pressure die cast aluminium alloy ACD12 housing (Heat sink) for effective thermal management, sturdiness & excellent corrosion resistant, Epoxy powder coated after phosphochromate treatment in metallic grey finish well glass 63 fitting with high efficiency long life SMD LEDs with lumen efficacy of > 140 lm/W with viewing angle 120 degree to ensure better uniformity of light distribution total system lumen output not less than 3300 lms. Operating temperature -10 degree C to +55 degree C, operating voltage range 140 V - 270 V, Average life L70B50: 50000 hours, Integral Electronic driver with APFC, lower THD, Output Short Circuit Protection, Surge Voltage Protection, Over voltage protection & other safety test as per IS:15885 Part 2/Sec 13, CCT 5700 K, THD < 10, PF > 0.95 complete in all respect as required.
Supply, Installation, Testing and Commissioning of 20 Mt. Hot dip Galvanized suitable for wind velocity of 50 M/Sec as per IS 875 Part 3 1987 latest version High Mast system alongwith head frame, steel wire rope, double drum winch, galvanized lantern carriage suitable for 8 luminaries & its CG boxes & lightning finial, integral type high powered reversible power tool for raising and lowering of lantern carriage, gear box coupled with the winch & torque limiter, 64 foundation bolt of special steel with nuts washers, anchor plates, templates, LED beam flood light luminaries 200 W, shallow foundation considering the safe soil bearing capacity at site as 10 T/Sq. Mtr. at 2 Mtr Depth, twin dome aviation obstruction light, heavy gauge hot dipped galvanized lighting finals, Feeder Panel comprising main incoming switch MCB's, time switch, contactor, reversing starter and protective system etc. as required and maintenance free Earthing etc. The material shall be inspected at manufacturer's premises by RITES and inspection charges shall be borne by the firm.
Cutting of Steel Rail Pole 60/90 lbs 1.55 Mtr. Length pieces by hacksaw blades/gas cutting complete in all respect.
Supply of Paint and painting of 1.55 Mtr. Long single Rail pole 60/90 lbs grouted for protection of high mast.
Erection/Grouting of 60/90 lbs 1 to 1.55 Mtr. Long steel Rail pole in cement concrete 67 1:3:6 (1 Cement : 3 Coarse sand : 6 graded stone aggregate 40 mm nominal size) foundation including excavation refilling etc. complete with 0.3 Mtr. Long portion will be in ground including cement concrete plinth completed in all respect. These poles will be grouted as per CEE's Drawing No. L/CEE/GKP/2010/2 as enclosed.
Fabrication of Decorative Hexagonal Platform with brick work and Cement Morter plaster along with supply of materal according to the CEE's Drawing No. L/CEE/GKP/2010/2 as enclosed.
Supply, Erection, Testing and Commissioning of Iron Clad Plug Socket 20 Amp with SP 69 MCB 20 Amps and Metal clad plug top 20 amp. As per technical specifications. ( MCB will be supplied by the Railway) Square
Providing and fixing internally illuminated signs (SINGLE SIDED) to identify key points like direction to facilities, Platforms, Exit and Main utilities accessed inside station and on platforms, made boxes out of aluminium extruction with sign face in 4 mm thick cast acrylic, internal illumination using Power LED's of white colour and the face acrylic covered with coloured cast vinyl 70 film as per graphic guidelines, including mounting sign using suspenders, brackets as per site location and all suspenders, brackets should be hot dipped galvanized. The graphic artwork to be referred from templates & guidelines shared for execution as per the specified type faces and in specific languages, sign cost to include all detailing, getting shop drawings and artworks approved before fabrication, finishing, transport, installation, cranes/scaffolding for hoisting the sign, screws, nuts, bolts, fasteners, electrical connections, drivers for LED Lights including connecting the sign from the nearest power point provided and approved by the Engineer-in-charge.
Dismantling of Damaged Single Rail/Tubular Pole and handed over to concern SSE
Installation, Testing and Commissioning of 1.5 TR Split type Air Conditioner both indoor and outdoor including fixing arrangement etc. (1.5 /2 TR Air Conditioner will be supplied by Railway)
Supply and commissioning of Extra copper pipe line along with insulation and other accessories for connecting indoor unit to outdoor unit for 1.5/2 Ton Split type air conditioner.
Supply and Fixing of Extra drain piping system for 1.5/2 Ton Split type air conditioner.
Supply and Fixing of Extra Flexible copper cable cord of 4 Sq. mm for 1.5/2 TR split type air conditioner.
Supply and Installation of Stand of suitable size for outdoor unit of 1.5/2 TR split type air conditioner as per diectives of Site Engineer and suitable to site condition.
Supply installation testing & commissioning of MCCB 100 Amps , 4 pole breaking 77 capacity 25 KA at 415 V,50 Hz, thermal release range 80-100 A, Ics = 100% Icu including hard wares and insulators as required as per CEE'S Specification No. CEE/Spec./LT-Panel with 400Amp. ACB/06 December - 2008 or latest.
"Design, manufacture, supply, installation, testing and commissioning of LT distribution board cubicle modular design free standing, floor mounting, dust & vermin proof as per CEE's Specification No. CEE/Spec./L.T.-Panel with 400 Amp. ACB/06 December - 2008 and comprising of: - 1. MCCB 4 pole 35 KA rupturing capacity 400A with adjustable thermal setting 70-100% - 01 No.
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
GCC-APRIL-2022.pdf
ATTACHMENT
EARTHING.pdf
ATTACHMENT
BGFormat-NEW_merged.pdf
ATTACHMENT
PipeEarth.pdf
ATTACHMENT
LTPanel.pdf
ATTACHMENT
ACS 1 10
ATTACHMENT
GCCACS11_compressed.pdf
ATTACHMENT
HighMast.pdf
ATTACHMENT
HMFOUND.pdf
ATTACHMENT
FencingHM-CArea.pdf
ATTACHMENT
RBSTANDARD_1.pdf
ATTACHMENT
SIGNAGE-SPEC.pdf
ATTACHMENT
OCTAPole.pdf
ATTACHMENT
Exp.ASHCYM.pdf
ATTACHMENT
TCASHCYM.pdf
ATTACHMENT
GCCACS-01to10_compressed.pdf
ATTACHMENT
Download all tender documents and submit your bid