Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹18.0 LAccepted-AOC | L1 | Accepted-AOC L1 | |
| 2 | L2₹25.3 L+₹5.4 L (27.2%)Rejected-Finance | L2 | Rejected-Finance Other than L1 | |
| 3 | L3₹25.9 L+₹6.0 L (30.1%)Rejected-Finance 306 SHIV BARI MARG PANCHVATI NAGAR BATHINDA 151001 PB | BATHINDA | BATHINDA | PUNJAB | 151001 | L3 | Rejected-Finance Other than L1 |
Tender Value
₹35 L
EMD Value
₹70,000
Closing Date
28 Jan 2020, 6:00 pmClosed
GE (AF) BHISIANA
GARRISON ENGINEER (AF), MILITARY ENGINEER SERVICES, BHISIANA, PIN-151201
Repair and Maint of External Elect Supply External Water Supply and DG Sets alongwith connected Works at 44 WEU under GE (AF) Bhisiana
2019_MES_310138_1
GE/BHI-56/2019-20
Open Tender
Miscellaneous Works
Item Rate
180 days
GE (AF) BHISIANA
Please Refer Tender Documents
8 documents required · 8 mandatory
₹500
GE (AF) BHISIANA
₹70,000
Yes
4 Jun 2020
28 Dec 2019
29 Jan 2020
28 Dec 2019
28 Jan 2020
11 Jan 2020
Amount
Excavation in trenches not exc. 1.5 m wide and not exceeding 1.5m depth for foundation of poles/laying of cables/stay/strut etc not exceeding 10 Sq m on plan and getting out in soft/loose soil. all as specified and as directed by Engineer-in-Charge.
Returning, filling including spreading, leveling watering and well ramming in layers not exceeding 25 cm as directed.all as specified and as directed by Engineer-in-Charge.
Removing excavated material (soil) n.exc 50m and depositing where directed at a level not exceeding 1.5 mtr above the starting point all as specified and as directed by Engineer-in-Charge.
M&L for providing Fazilka river sand as in sand cushioning with a layer of sand 8cm thick before laying of cable and 15cm thick after laying of cable in trench complete all as specified and directed by Engr-in-Charge.
M&L for brick protection cover of UG cable by old size bricks common burnt clay building bricks sub class `B’ laid dry and flat abutting each other with width equal to length of brick and gap between adjacent brick not exceeding 10mm complete all as specified and directed by Engineer-in-Charge.
M&L for making bore below the road for crossing the GI pipe light grade 50 mm dia for cable protection and fill the putty on both sides of the GI pipe after crossing the armoured cable to avoid the water inside complete all as specified and directed by Engr-in-charge.
M&L for making bore below the road for crossing the GI pipe light grade 80 mm dia for cable protection and fill the putty on both sides of the GI pipe after crossing the armoured cable to avoid the water inside complete all as specified and directed by Engr-in-charge.
M&L for galvanized steel tubing 80 mm light garde (ISI marked) for protection of cable fixed to pole/walls or laid in floors, road crossing ducts with all necessary fittings and fittings and fixed with clamps, bolts, nuts and washers etc complete all as specified and directed by Engr-in-charge.
All as per item No.8 above but having size 50 mm
M&L for taking down unserviceable LT UG cable any type from trenches and removing the fault and relaying of LT UG cable after rectifing the fault and making cable in serviceable condition of 1100 V grade UG cable of size from 185 to 300 sq mm, 3½ core. (NOTE 1 : striaght throuigh joints measure and paid seaprately ) NOTE 2 : Excavation, Returning, filling, removal, sand cushioning & brick protection will be measured and paid separately.
M&L for taking down unserviceable LT UG cable any type from trenches and removing the fault and relaying of LT UG cable after rectifing the fault and making cable in serviceable condition of 1100 V grade UG cable of size from 70 to120 sq mm, 3½ core. NOTE 1: striaght throuigh joints measure and paid seaprately NOTE 2 : Excavation, Returning, filling, removal, sand cushioning & brick protection will be measured and paid separately.
M&L for taking down unserviceable LT UG cable any type from trenches and removing the fault and relaying of LT UG cable after rectifing the fault and making cable in serviceable condition of 1100 V grade UG cable of size from10 to 50 sq mm, 2 to 4 core. NOTE 1: striaght throuigh joints measure and paid seaprately NOTE 2 : Excavation, Returning, filling, removal, sand cushioning & brick protection will be measured and paid separately.
M&L for cable jointing kit for 1100 volts grade cable for straight through joint complete with Jointing material heat Shrink type and accessories suitable for 3 ½ / 4 core XLPE, armoured, Al conductor cable of size 10 to 50 sqmm, complete all as specified and directed by Engr-in-charge.
All As per Item No.13 but for cable of size 70to 120 sqmm
All As per Item No.13 but for cable of size185 to 300 sqmm
Taking out U/S LT Cable from trench/on wall of 95 to 120 sqmm complete all as specified and directed by Engr in Charge
Taking out U/S LT Cable from trench/on wall of 50 to 70 sqmm complete all as specified and directed by Engr in Charge
Taking out U/S LT Cable from trench/on wall of 25 to 35 sqmm complete all as specified and directed by Engr in Charge
Taking out U/S LT Cable from trench/on wall of 10 to 16 sqmm complete all as specified and directed by Engr in Charge
Supply, laying, jointing and testing LT cable XLPE insulated, armoured and PVC bedded 1100 volts grade,heavy duty with aluminium conductor 120 Sqmm 3.5 core laid in ducts/through pipes, in floor, on poles, in trenches complete all as specified.
Supply, laying, jointing and testing LT cable XLPE insulated, armoured and PVC bedded 1100 volts grade,heavy duty with aluminium conductor 95 Sqmm 3.5 core laid in ducts/through pipes, in floor, on poles, in trenches complete all as specified.
Supply, laying, jointing and testing LT cable XLPE insulated, armoured and PVC bedded 1100 volts grade,heavy duty with aluminium conductor 70 Sqmm 3.5 core laid in ducts/through pipes, in floor, on poles, in trenches complete all as specified.
Supply, laying, jointing and testing LT cable XLPE insulated, armoured and PVC bedded 1100 volts grade,heavy duty with aluminium conductor 50 Sqmm 3.5 core laid in ducts/through pipes, in floor, on poles, in trenches complete all as specified.
Supply, laying, jointing and testing LT cable XLPE insulated, armoured and PVC bedded 1100 volts grade,heavy duty with aluminium conductor 35 Sqmm 4 core laid in ducts/through pipes, in floor, on poles, in trenches complete all as specified.
Supply, laying, jointing and testing LT cable XLPE insulated, armoured and PVC bedded 1100 volts grade,heavy duty with aluminium conductor 35 Sqmm 3.5 core laid in ducts/through pipes, in floor, on poles, in trenches complete all as specified.
Supply, laying, jointing and testing LT cable XLPE insulated, armoured and PVC bedded 1100 volts grade,heavy duty with aluminium conductor 25 Sqmm 4 core laid in ducts/through pipes, in floor, on poles, in trenches complete all as specified.
Supply, laying, jointing and testing LT cable XLPE insulated, armoured and PVC bedded 1100 volts grade,heavy duty with aluminium conductor 16 Sqmm 4 core laid in ducts/through pipes, in floor, on poles, in trenches complete all as specified.
Supply, laying, jointing and testing LT cable XLPE insulated, armoured and PVC bedded 1100 volts grade,heavy duty with aluminium conductor 10 Sqmm 2 core laid in ducts/through pipes, in floor, on poles, in trenches complete all as specified.
Dismantling/disconnection of LT connections from ACB by taking down proper shutdown,opening the ACB (Panel) installed at various locations for servicing ,overhauling all moving contacts,fixed contacts,tripping coil including testing the insulation value of moving and fixed contacts and cleaning the carbon from contact point with petrol etc and greasing oiling the all moving parts including testing all meters/relay such as under voltage relay and servicing,shut trip coil etc including reassembling the ACB and testing after completion of work all as directed by Engr-in-Charge. Note : Complete servicing and maintenance will be carried out at site only
Material and labour for preparation of old steel surfaces including welding work of doors of panels/feeder piller/Jn box,hinges with locking arrangement and applying one coat of synthetic enamel ivory paint/(Smoke grey) to steel LT Panel/bus bar box and junction boxes surface after disconnecting the electrical connections and reconnecting LT cables after painting, complete as specified and directed by Engr-in-Charge.
Supply and fix in replacement of MCCB 160 Amps,4 Pole 16 Ka with fixed thermal and fixed magnetic settings by disamantling old one from panel/feeder pillar box all as directed by Engr-in-Charge.
Supply and fix in replacement of MCCB 160 Amps,4 Pole 25 Ka with fixed thermal and fixed magnetic settings by disamantling old one from panel/feeder pillar box all as directed by Engr-in-Charge.
Supply and fix in replacement of MCCB 200 Amps,4 Pole 25/26KA Ka with fixed thermal and fixed magnetic settings by disamantling old one from panel/feeder pillar box all as directed by Engr-in-Charge.
Supply and fix in replacement of MCCB 250 Amps,4 Pole 25/26 KAwith fixed thermal and fixed magnetic settings by disamantling old one from panel/feeder pillar box all as directed by Engr-in-Charge.
Supply and fix in replacement of MCCB 100 Amps,4 Pole 25 Ka with fixed thermal and fixed magnetic settings by disamantling old one from panel/feeder pillar box all as directed by Engr-in-Charge.
Supply and fix in replacement of MCCB 63 Amps,4 Pole 16KA with fixed thermal and fixed magnetic settings by disamantling old one from panel/feeder pillar box all as directed by Engr-in-Charge.
Supply and fix in replacement of MCCB 40 Amps,4 Pole 16 KAwith fixed thermal and fixed magnetic settings by disamantling old one from panel/feeder pillar box all as directed by Engr-in-Charge.
Material & labour for earthing with Galvanised Steel earth plate electrode 60cm x 60cm x 6.3mm thick buried directly in ground vertically at a depth not less than 2.25metre below normal ground level with top edge of earth plate at a depth not less than 1.5 metre below normal ground level, earth plate surrounded from all sides by 15cm thick packed layer of charcoal dust and common salt filling in alternate layers and electrode connections by using Galvanised Iron strip of 32 x 6 mm as earthing lead (upto the body of the equipment) by means of bolts, nuts, check nuts and washers made of galvanised iron and thimbles and protected by light grade 40mm dia GI pipe connected to main switch board or main control board and GI pipe medium grade 20mm bore for watering and including funnel , wire mesh , RCC pit cover and PCC chamber pit with PCC (1:3:6) type C-2 using 40mm graded stone aggregate, including excavation and earth work in any type of soil , returning , filling in approved soil and disposal of surplus soil to a distance not exceeding 50m all as specified and shown in electrical plate No 3 of SSR 1991(Part-I) complete all as specified and directed.
M & L for Earthing complete with galvanized iron earth plate electrode 60 cm x 60 cm x 6.30 mm thick, buried directly in ground (earth pit not less than 2.25 meters deep below normal ground level) with top edge of the plate not less than 1.5 mtrs below normal ground level connected to galvanized earth lead wire 4.00 mm dia by means of bolts, nuts, check nuts and washers of galvanized iron or steel all as shown in electric plate No 5 of SSR Part-I connected to continuous earth wire on main switch board all as specified or indicated and testing on completion including provision of earth wire protection by 15 mm dia medium grade GI pipe and watering pipe shall be 20 mm bore, medium grade including excavation & earth work, PCC pit with RCC cover, charcoal salt funnel, GI wire up to 7.5 mtrs length complete all as spd and directed.
Supply and fixing cable route indicator made out cast iron and embedded LT /HT Cable on the plate of size 80 mm dia 5 mm thick and gouting lugs of suitable size including gouted in PCC foundation of suitable size complete all as directed.
Supplying and fixing 1100 Volts grade heavy duty cable PVC insulated aluminium conductor , served with inner sheathing of PVC Tape and overall PVc sheathed in service connections suspended by insulating hangers not more than 1 meter apart including 4 mm suspension wire , one twin core cable flat or circular of size 10 Sqmm complete all as specified and directed.
Taking out U/S HT Cable from trench of any size complete all as specified and directed by Engr in Charge
Supplying, laying, jointing and testing underground cable XLPE insulated screened armoured and PVC bedded HT 11000 volts grade (heavy duty) with aluminium conductor 3 core, 95 Sqmm, laid in ducts/through pipes, in floor, on poles, in trenches complete all as specified.
M&L for PCC cable protection cover, class HV, Type 1, flat, of size 300mm x l80mm x 40mm for HT UG cable and gap between adjacent cover not exceeding 10mm complete all as specified and directed
Dismantling of HT cable Jointing Kit of any type and any size complete all as specified and directed by Engr in Charge.
M&L for Cable Jointing Kit for 11 KV (Earthed) grade cable for outdoor termination heat shrinkable type end joint complete with jointing material and acessories suitable foe 3 Core XLPE armoured aluminium conductor cable of size 50 to 95 Sqmm complete all as specified and directed by Engr in charge.
M&L for Cable Jointing Kit for 11 KV (Earthed) grade cable for indoor termination heat shrinkable type end joint complete with jointing material and acessories suitable foe 3 Core XLPE armoured aluminium conductor cable of size 50 to 95 Sqmm complete all as specified and directed by Engr in charge.
M&L for Cable Jointing Kit for 11 KV (Earthed) grade cable for indoor termination heat shrinkable type straight throught joint complete with jointing material and acessories suitable foe 3 Core XLPE armoured aluminium conductor cable of size 50 to 95 Sqmm complete all as specified and directed by Engr in charge.
M&L for calibration/overhauling/servicing of relay any type voltage,current(e.g. Earth fault relay/Over current relay,etc) for 11 KVA HT panel.The setting of these relays should be as per the PSPCL norms so that individual breaker/feeder should be tripped and fault is not travelled back to MRS and subsequently to PSPCL power house.The calibration of relay is to be done by a reputed firm and it is to be submitted to to the AGE E/M-I.All the calibration should be done in the presence of Engineer-in-charge.NOTE:-replacement cost of HRC fuses are included in quated rates
M&L for Disconnecting the existing servicing electric supply from HT 11KV system of any make type taking out switch gear from SF-6 circuit breaker(any type)/VCB/OCB,cleaning from inside and out side by using CRC-26 spray or any other cleaning agents which can improve the electrical conductivity or properties,greasing whereever required overhuling of switchgear ,checking the fixed/moving contacts of all the 3 phases adjusting electrical/electronic/mechanical components all as per mfg instruction manual and standard practice & reassembling the same after necessary servicing repair including testing and commissioning in its original position & necessary connection etc all as specified and directed.This work is to be get done from company authorised sales and supplier dealers and all as specified and directed.
Dismantling the existing defective Automatic voltage stabilizer oil/Air cooled type 3 phase 415 Volts AC supply any cap/type including disconnection of electric connection and opening the stabilizer ,removing the burnt parts and replacement of defective parts by providing new components/parts as per existing make and capacity.Prepare the old surface by using blow lamp/soft wire brush and spray painting with one coat primer and two coat of synthetic enamel paint,reassembling the same after necessary servicing repair including testing and commissioning in its original position & necessary connection etc all as specified and directed Note : (a) The spare parts shall be measured and paid separately in appropriate item in schedule. (b) Labour charges for repair/replacement of minor parts item costing upto Rs 500/- are included in the above item
Repair of coil upto 100 KVA.
Repair of synchronising motor suitable for 100 KVA stabilizer.
M&L for online De-hyderation and filtration at site from the transformer of various capactiy,(till the di-electric strength reaches 40 KV to 60KV withstand for one minute is achieved) complete all as directed by Engineer-in-Charge NOTE : Contractor will arrange filtration plant machine at site of transformer.Dehydration work will be carried out in working condition and electric supply will be taken from same transformer.
Supply & pouring of transformer oil with Di-electric strength not less than 50 KV di-electric strength in the sealed drum or filled in transformer/on site/workshop complete all as specified and directed by Engr-in-Charge
M&L for Scrapping/cleaning of outer surfaces of transformer and spray painting (smoke grey colour)with two coats of best quality synthetic enamel paint over one coat of red oxide primer complete including writing of MES No(white colour paint) all as directed by Engineer-in-Charge upto 500 KVA capacity transformer of any make/shape/size.
Prepration of old Steel Surfaces and applying two coat of synthetic enamel white paint to Steel tubular /PCC Pole and upto 1 Mtr height from ground level alternative in Yellow and black strips of 30 CM height each including numbering of Pole No with black paint complete all as specified and directed by Engr in charge.
Dismantling / Taking down of Old broken HT/LT Danger notice Plate of any size complete all as specified and directed.
Supply and fixing Danger notice Plate of 1.6 mm thick mild steel sheet , vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with MS Clamps , bolts and nuts of approved size, for LT ,20x15 CM size.
Supply and fixing Danger notice Plate of 1.6 mm thick mild steel sheet , vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with MS Clamps , bolts and nuts of approved size, for HT ,25x20 CM size.
Dismantling insulators any type and any size complete all as specified and directed.
Supply & fix disc type insulators, porcelain vitreous 145mm high and 255mm dia ball & socket type white, brown or green, existing single disc assembly with double disc assembl, working pressure 11000 Volt for fixing on existing lines.
M&L for Painting of Old painted surfaces of Cross Arms , Clamps etc worth on top of the LT / HT Poles of 9/11 Mtr height with one coat of aluminium paint after preparing the surface.
Trimming/cutting of trees branches.bushes obstructing the HT/LT lines making clear distance of 3 RM from the outer conductors of OH Lines all around and all substations fencing around pump house area, below surrounding of OHTs including removing of branches/ bushes of trees from site all as directed.
Supply and fix PVC Sintex box (200mm x250mm)having 04 Nos of aluminium bus bar mounted on insulator with the help of nut,bolts, clamps including single pole MCB of 6 amps, 2.5 sqmm copper conductors cable 3 core for connection of incoming and outgoing cables complete all as specified and directed by Engineer-in charge
Material and labour for disconnection and dismantling of existing transformer of capacity from 63 to 500 KVA for repair work and refixing and reconnecting the same complete all as directed as under:- i) Replacement of gasket, nuts bolts and washer ii) Replacement of neoprene rubber washer iii) Replacement of silica gel iv) Replacement of copper lugs including ACSR jumpers from HT OH line to primary side of TF v) Cleaning of bush insulator LT/HT side vi) Tightening of connection of earthing lead to neutral & body vii) Replacement of MS cable box cover as per requirement at site viii) Replacement of HT & LT bush ix)Replacement of HT & LT bush copper Rod x) Replacement of oil level indicator if required
S&F street light GI pipe bracket 25mm dia 1.50metre length (ISI marked) light grade bend to shape with two Nos MS clamp duly painted nuts and bolts etc complete all as specified and directed at site
Dismantling/Taking down of Street light/Flood light of any capacity and any size complete all as directed.
Supply and fix 60 W LED based street light luminaries new generation energy saving & environment friendly light fitting high power LEDs as light sources.LED luminous efficiency should be > 60Lm/w.It should have active power factor correctio (APFC) electronic gear (electronic driver).Luminaire housing shall be of pressure die-cast aluminium alloy LM24 for gear and extruded aluminium lamp housing (Heat shrink for better heat transmission.It shall have epoxy powder coated grey finish phosphochromate treatment,IP-66 protection class I operating voltage range should be fron 120 volt to 270 volt AC and frequency range 50Hz.fitting should be suitable for an ambient temparature from -40°C to 50 °C and humidity level 10% to 90% including connection with PVC unsheathed wire aluminium conductor 3 x 1.5sqmm with OH line or PVC junction box complete all as specified and directed by Engr-in-charge
S & F 200 watt LED Flood light luminaire of epoxy powder cated CRCA MS housing with epoxy powder coated aluminium heat sink with system wattage .with 120 degree view angle,>200 lumen/watt,luman maintenance>70% at 50,000hrs,colr temperature of 5000-6500K,> color rendering and LM80 test compliance.The driver must be integral APFC and constant current type having THD<15% and power factor>0.95 with short circuit protection,open protection,reverse polarity protection,high voltage protection complete with all accessories pre-wired and including connecting up with twin core twisted flexible copper conductor cable with suitable size complete all as directed at site.
Supply and fix sub main of 2x2.5 sqmm +1x1.5sqmm as earth wire with PVC conduit in surface /recessed as required.
Taking out unserviceable broken aviation, obstruction light from tower, water reservoir for necessary replacement/repair
Supply and fixing LED Aviation obstruction light , with light depended sensor , IP 65 Protected of capacity 6W with suitable lamp complete all as specified and directed .
M&L for removing normal earthing and M&L for commissioning, installation and testing of maintenance free UL approved copper bonded earth rod of 10 feet length, 17.2 mm dia. made of high tensile low carbon steel rod , molecularly bonded with 99.9% electrolytic grade copper on outer surface ( minimum copper bonding thickness - 250 microns) with exothermally jointed copper bus bar of 50 X 6 X 200 mm for connection. The rod and exothermic joint together successfully tested at 25 KA fault current by CPRI with 50 Kg eco friendly earth enhancing compound with each earth rod. The earth pit should be 125 mm dia. the compound should comply to IEC:62561-7 having passed leaching, corrossion, sulphur and resistivity test as per IEC: 62651-7 by NABL accredit Lab with FRP earth pit cover of top size lockable Lid. It includes GI Protection pipe light grade of size 40 mm dia. with GI strip of size 32X6 mm upto test point complete all as specified and directed by Engr-in-charge. Make JMV LPS Ltd/ OBO/ENNOV Infra solutions Pvt. Ltd/ erico /powerbolt including connecting of Strip between two earthing complete all as specified and directed by Engr in charge . (a) The test result of each set of earthing is less than 1 Ohm. All earthing test will be carried out in presence of MES Rep, manufacturer Rep and test result will be recorded in a register with sign of manufacturer & Engr-in-charge. (b) 5 Year gaurantee certificate from company for maintaining earth result less than 1 Ohm will be submitted by contractor (c) 1425 RTC SS universal clamp of size 175 x 50 x 3mm (d) Earth enhancing compound (PROCEM) ECS GB 25 tested as per IEC 62561-7-25Kg (e) Chemical earthing will be installed by manufacturer Rep and purchase voucher of earthing will be produced before payment. Payment shall be made only after getting satisfactory result.
M&L for removing normal earthing and M&L for commissioning, installation and testing of maintenance free UL approved copper bonded earth rod of 10 feet length, 17.2 mm dia. made of high tensile low carbon steel rod , molecularly bonded with 99.9% electrolytic grade copper on outer surface ( minimum copper bonding thickness - 250 microns) with exothermally jointed copper bus bar of 50 X 6 X 200 mm for connection. The rod and exothermic joint together successfully tested at 25 KA fault current by CPRI with 50 Kg eco friendly earth enhancing compound with each earth rod. The earth pit should be 125 mm dia. the compound should comply to IEC:62561-7 having passed leaching, corrossion, sulphur and resistivity test as per IEC: 62651-7 by NABL accredit Lab with FRP earth pit cover of top size lockable Lid. It includes GI Protection pipe light grade of size 40 mm dia. with GI strip of size 32X6 mm upto test point complete all as specified and directed by Engr-in-charge. Make JMV LPS Ltd/ OBO/ENNOV Infra solutions Pvt. Ltd/ erico /powerbolt including connecting of Strip between two earthing complete all as specified and directed by Engr in charge a) The test result of each set of earthing is less than 1 Ohm. All earthing test will be carried out in presence of MES Rep, manufacturer Rep and test result will be recorded in a register with sign of manufacturer & Engr-in-charge. (b) 5 Year gaurantee certificate from company for maintaining earth result less than 1 Ohm will be submitted by contractor (c) 1425 RTC SS universal clamp of size 175 x 50 x 3mm (d) Earth enhancing compound (PROCEM) ECS GB 25 tested as per IEC 62561-7-25Kg (e) Chemical earthing will be installed by manufacturer Rep and purchase voucher of earthing will be produced before payment. Payment shall be made only after getting satisfactory result.
S&F test point terninal block made of of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed inlcuding 3 Nos 8 mm dia 25 mm long hexagonal head screw complete all as specified and directed.
S&F of copper strip of size 20 x 3.15 mm on PVC/porcelain insulator at suitable distance with saddeles and fixing screw etc for roof/Wall conductors and down conductors above ground all joints of copper strip should be brazed properly complete all as specified and directed.
M&L for copper brazing for copper strips of various sizes laying on wall /roof etc with the help welding machine and skilled tradesmen by using welding rod etc by taking safety precaustions during brazing as directed by the AGE EM / users complete all as specified and as directed by Engr in Charge
M&L for fixing the procelin cleat with the help of nut,bolts clamps etc to fix the strips of various size and types to separate from groung and wall as directed at site by Engr in charge complete all as specified
M&L for PVC conduit heavy duty of 40 mm dia size for the protection of the earthing strip on wall/roof with the help nuts ,bolts clamps, PCC work etc as directed at site by Engr in charge
Servicing of DG set including replacement the set of fuel pre- filters and fine -filters,air filter element,flusing of radiator and filling coolent upto max. level & engine oil change including engine oil change,20 W 40 grade(20 Ltrs for 140 KVA DG Set ,12 ltrs for 40 KVA & 2X9 ltrs=18 ltrs for 20KVA sets) as per sample and make for the following capacities of DG sets. Each set shall be comprising complete set of pre/fine filters complete all as directed.
Supply and replace set of lube / engine oil filters as per sample and make for the following capacities of DG sets.
S & F in replacement of battery lead of copper conductor PVC insulated multi strand 1.25 Mtr long (two Nos) duly fixed with terminals and lugs complete all as directed.
Removal of old painted surface of DG Set complete with fuel tank by scraping with emry paper and cleaning by thinner and finishing the surface smooth for new paiting of two coat of spray painting with synethetic enamal paint complete including writing of SM/MES No and colour code all as directed by Engineer-in-Charge.
Supply and fix in replacement of generator door hinges metal type with nut bolts or screws for DG set any make any type complete all as specified and directed
S & F in replacement indicator lamps AC 230 V, LED type for the panel boards complete all as specified and directed.
S & F in replacement under/over voltage relay input voltage 110-220 V AC suitable for AMF panel complete all as specified and directed.
S & F in replacement engine starting relay DC 12V/24V suitable for AMF panel complete all as specified and directed.
S & F in replacement 8 pin relay Base Socket voltage range DC voltage 12 V to 230 V and AC voltage 12 V to 440V suitable for AMF panel complete all as specified and directed.
S & F in replacement contact element NO-NC suitable for AMF panel complete all as specified and directed.
S & F in replacement green colour Actuator Push button with complete set suitable for AMF panel complete all as specified and directed.
S & F in replacement Red colour Actuator Push button with complete set suitable for AMF panel complete all as specified and directed.
S & F in replacement Automotive relay, 12 VDC, 50 Amp power relay quick connected with complete set suitable for AMF panel complete all as specified and directed.
S & F in replacement Ameter of range as required for the Gen/ AMF panel complete all as specified and directed.
S & F in replacement Volt meter 0 to 600 V range suitable for the Gen/ AMF panel complete all as specified and directed.
Supply & Fixing in replacement contactor 200A, 4 pole suitable for AMF panel complete all as specified and directed.
Supply & Fixing in replacement contactor 50A, 4 pole suitable for AMF panel complete all as specified and directed.
Supply & Fixing in replacement main contactor 40A, 4 pole suitable for AMF panel complete all as specified and directed.
M&L for reconditioning of battery 12 volt 150 AH any make and any type opening up and taking out all dead battery cell plates, terminal post and mixture of acid using same container of battery and replacing of new solution battery cell, plates, making terminals all as specified and directed
S&F Battery Charger of capacity 12V suitable for AMF Panel complete all as specified and directed.
Supply and replace in repair Glow Sign Board box type size 1.50x0.46x0.23 m having base height 0.75 M, which is show Dg capacity,SM/MES Number and location including painting black colour on metal parts excavation and using PCC 1:2:4 for foundation complete all as specified and directed.
Repairing the self starter after removing from the Gen set of capacity from 20 kva to 140 KVA and transporting to an authorised sevice centre complete all as specified and directed.
Supply and fix in replacement Benjo bolts complete including warsher (02 washers for each bolt) complete all as specified and directed.
Supply and fix in replacement fuel pipe filter to FIP wire braided complete all as specified and directed.
Supply and fix in replacement fuel pipe upto 15 mm size from fuel tank to the DG set & over flow return complete all as specified and directed.
Material and Labour for painting of LT Panels including cleaning of exposed surface with brush and empry paper including two coat of painting with smoke grey paint, including cleaning of all terminals with CRC Sprey any size of LT Panel complete all as specified.
S&F in replacement on load change Over Switch 100 Amp in Sheet Steel enclosure complete all as specified and directed.
S&F in replacement on load change Over Switch 125 Amp in Sheet Steel enclosure complete all as specified and directed.
S&F in replacement on load change Over Switch 63 Amp in Sheet Steel enclosure complete all as specified and directed.
Taking out /down old unserviceable CI pipe of 150 mm dia including all fittings etc from trenches complete all as specified and directed. (Note : Earth work shall be measured and paid seperately )
Taking out /down old unserviceable CI pipe of 100 mm dia including all fittings etc from trenches complete all as specified and directed. (Note : Earth work shall be measured and paid seperately )
Taking out /down old unserviceable CI pipe of 80 mm dia including all fittings etc from trenches complete all as specified and directed. (Note : Earth work shall be measured and paid seperately )
Taking out /down old unserviceable GI pipe of 40/50 mm dia including all fittings etc from trenches complete all as specified and directed. (Note : Earth work shall be measured and paid seperately )
Taking out /down old unserviceable GI pipe of 25 mm dia including all fittings etc from trenches complete all as specified and directed. (Note : Earth work shall be measured and paid seperately )
Taking out /down old unserviceable GI pipe of 20 mm dia including all fittings etc from trenches complete all as specified and directed. (Note : Earth work shall be measured and paid seperately )
Supply , laying , jointing of CI Pipe spigot and socketed end pipes centrifugally class LA in any length of size 150 mm dia in trenches complete all as directed.
Supply , laying , jointing of CI Pipe spigot and socketed end pipes centrifugally class LA in any length of size 100 mm dia in trenches complete all as directed.
Supply , laying , jointing of CI Pipe spigot and socketed end pipes centrifugally class LA in any length of size 80 mm dia in trenches complete all as directed.
Supply and laying galvanised iron pipe, medium grade 50 mm bore with all new fittings, laid in trenches including jointing material etc complete all as specified and directed.
Supply and laying galvanised iron pipe, medium grade 40 mm bore with all new fittings, laid in trenches including jointing material etc complete all as specified and directed.
Supply and laying galvanised iron pipe, medium grade 25 mm bore with all new fittings, laid in trenches including jointing material etc complete all as specified and directed.
Supply and laying galvanised iron pipe, medium grade 20 mm bore with all new fittings, laid in trenches including jointing material etc complete all as specified and directed.
M&L for run lead joints for 150mm dia spigot and socketed CI pipe fittings including spun yarn etc.
M&L for run lead joints for 100mm dia spigot and socketed CI pipe fittings including spun yarn etc.
M&L for run lead joints for 80mm dia spigot and socketed CI pipe fittings including spun yarn etc.
Supply & fixing 150 mm dia sluice valve PN 1:6 ISI marked confirming to IS-14846, flanged and drilled, gun metal spindle and iron wheel including jointing material such as nuts, bolts, washers and rubber sheet etc complete all as directed by Engineer-in-Charge.
Supply & fixing 80 mm dia sluice valve PN 1:6 ISI marked confirming to IS-14846, flanged and drilled, gun metal spindle and iron wheel including jointing material such as nuts, bolts, washers and rubber sheet etc complete all as directed by Engineer-in-Charge.
Supply & fixing 100 mm dia sluice valve PN 1:6 ISI marked confirming to IS-14846, flanged and drilled, gun metal spindle and iron wheel including jointing material such as nuts, bolts, washers and rubber sheet etc complete all as directed by Engineer-in-Charge.
S & F Gun metal globe or gate valve (ISI marked), with iron wheel head, screwed both ends, suitable for 50 mm bore iron pipe and fixed including testing complete all as specifed and directed by Engr-in-Charge.
S & F Gun metal globe or gate valve (ISI marked), with iron wheel head, screwed both ends, suitable for 40mm bore iron pipe and fixed including testing complete all as specifed and directed by Engr-in-Charge.
S & F Gun metal globe or gate valve (ISI marked), with iron wheel head, screwed both ends, suitable for 25 mm bore iron pipe and fixed including testing complete all as specifed and directed by Engr-in-Charge.
S & F Gun metal globe or gate valve (ISI marked), with iron wheel head, screwed both ends, suitable for 20 mm bore iron pipe and fixed including testing complete all as specifed and directed by Engr-in-Charge.
M&L for brick masonary valve pit (type B) of size 90 x 90 x 90 cm cm (internal of chember ) depth of chember to be reckoned from the top of PCC in foundation to top the MS cover as 1.5 mtr and including MS sheet cover fabricated from 3 mm thick MS sheet and frame of angle iron 40 mm x 40 mm 6 mm with fixing arrangement , hinges and locking arrangement and painting two coat of synethetic enamel paint over a coat of red oxide primer on MS cover and frame , inlcuding necessary excavation and earth work in any type of soil , returning , filling in approved soil disposal of surplus soil to a distance not exc.50 mtr , 150 mm thick PCC (1:4:8) type D-2 using 40 mm graded stone aggregate as in foundation , brick work in cement motor (1:6) 15 mm thick plastering in cement mortoar (1:4) (both internally and externally) 100 mm thick PCC (1:2:4) type B1 using 20 mm graded stone aggregate as in flooring complete all as directed.
M&L for brick masonary valve pit (type B) of size 60 x 60 x 60 cm cm (internal of chember ) depth of chember to be reckoned from the top of PCC in foundation to top the MS cover as 1.5 mtr and including MS sheet cover fabricated from 3 mm thick MS sheet and frame of angle iron 40 mm x 40 mm 6 mm with fixing arrangement , hinges and locking arrangement and painting two coat of synethetic enamel paint over a coat of red oxide primer on MS cover and frame , inlcuding necessary excavation and earth work in any type of soil , returning , filling in approved soil disposal of surplus soil to a distance not exc.50 mtr , 150 mm thick PCC (1:4:8) type D-2 using 40 mm graded stone aggregate as in foundation , brick work in cement motor (1:6) 15 mm thick plastering in cement mortoar (1:4) (both internally and externally) 100 mm thick PCC (1:2:4) type B1 using 20 mm graded stone aggregate as in flooring complete all as directed.
M & L for CI fittings for Spigot & Socketed pipe as bends, tapers, tee pieces any type angle/radius and straight connection pieces etc upto 150 mm dia pipe as in repair etc complete all as specified and directed.
Cleaning of RCC over head tank reservoir up to 1 lakh gallon capacity by drain out the contaminated muddy water from bottom surfaces of the tank by using of pump and motor and cleaning the inside and bottom surfaces of walls with help of wire brush and using specified dosage of Potassium permanganate and cleaned water than drain out completely material to the entire satisfaction of Engr in Charge with and including writting letters 5 CM height capacity of Tank and date of Cleaning of tank , with synthectic enamel paint on the other surface of the tank complete all as specified and directed.
Cleaning of Undergroung water tank up to 1 lakh gallon capacity by drain out the contaminated muddy water from bottom surfaces of the tank by using of pump and motor and cleaning the inside and bottom surfaces of walls with help of wire brush and using specified dosage of Potassium permanganate and cleaned water than drain out completely material to the entire satisfaction of Engr in Charge with and including writting letters 5 CM height capacity of Tank and date of Cleaning of tank , with synthectic enamel paint on the other surface of the tank complete all as specified and directed.
Cleaning of over head sintex tank of 10000 gallon capacity by drain out the contaminated muddy water from bottom surfaces of the tank by using of pump and motor and cleaning the inside and bottom surfaces of walls with help of wire brush and using specified dosage of Potassium permanganate and cleaned water than drain out completely material to the entire satisfaction of Engr in Charge with and including writting letters 5 CM height capacity of Tank and date of Cleaning of tank , with synthectic enamel paint on the other surface of the tank complete all as specified and directed.
M&L for rewinding of submersible pump capacity 20 hp three phase with super enameled copper wire of existing gauge including replacement of bush and nut and bolts, washer with condenser of existing Capacity etc complete all as specified and as directed by Engineer-in-charge.
Physio-chemical bacteriological testing of water from the institute / lab as approved by the GE complete all as per IS : 10500 - 1991 including collection of water sample and submitting the same with institute / lab all as specified and directed by Engr-in-Charge.( Note : The water testing parameters will be given by the department)
Radioactive test of drinking water (Borewell water) as per IS-10500:2012 (Parameters : Gross Alpha & Gross Beta test) at department of Atomic Energy, Board of Radiation & Isotope Technology, BARC/BRIT, Navi Mumbai all as specified and directed by Engr-in-Charge
Arsenic test for drinking water from the institute / lab as approved by the GE complete all as per IS : 10500 - 1991 including collection of water sample and submitting the same with institute / lab all as specified and directed by Engr-in-Charge
Repairs to Valve Masonry Pit (by means of internal plastering, replacement of angle iron, MS Sheet etc) of following size :-
M&L for stopping leakege of GI Pipe upto 100mm dia by replacing any type of (bend, tee, elbow, reducer, end plug, taper, union, nipple, socket etc) all as specified and directed by Engr-in-Charge (Excavation deemed to be included in quoted rate)
50mm dia GI Pipe
40mm dia GI Pipe
25mm dia GI Pipe
Dismantling/taking down the centrifugal pump set of capacity 10 HP from foundation after disconnecting of discharge, suction and induction motor connection and shifting to the same to civil work shop at Bathinda for the following repair :- (a) Dismantling the complete pump and taken out main shaft and impeller from the pump by disconnection of all nuts, bolts and washers and minor repair and balancing of main shaft and impeller by necessary lathe and machine work and replacement with complete new gasket and mild steel nut, bolt and washer complete all as directed. (b) Replacement of ball bearing NBC 6312 including providing of required grease complte 02 Nos. (c ) Re-assembling the complete and fixing at site and connection of suction, discharge and the induction motor and testing the same on full load complete all as specified.
All as per item no. 144 above but having 5 HP pump.
M& L for servicing of RO Plant with carrying out following repair (a) repair to activated carbon filter with replacement of activted carbon (b) repair to dual media filter with replacement of sand media (c ) repair/replacement of micron filter (d) chemical washing of all RO membrane if required than replacment of Membrane
S&F DOL stater suitable for 5HP to7.5HP electric motors including necessary electric connections complete all as directed
S&F Star-Delta stater suitable for 10HP electric motors including necessary electric connections complete all as directed
S&F Star-Delta stater suitable for 20HP electric motors including necessary electric connections complete all as directed
Taking out U/S submersible motor from borewell of depth 500 ft with arrangement of manpower & chain pully & after repair refix the motor in same depth with the help of manpower & chain pully. Note: Any damage to motor, pipe and cable will be repaired by contractor
Aman Enterprises
M/s Luxmi Constructions
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .