| # | Company | Quoted % | Amount | Rank | Status |
|---|---|---|---|---|---|
| 1 | L1₹17.8 LAdmitted-Finance | L1 | Admitted-Finance | ||
| 2 | L2₹18.6 L+₹72,340.53 (4.06%)Admitted-Finance N A | NA | NA | 121004 | L2 | Admitted-Finance | ||
| 3 | L3₹20.1 L+₹2.3 L (12.8%)Admitted-Finance C 5 156 YAMUNA VIHAR EAST DELHI DELHI 110053 | NORTH EAST DELHI | DELHI | 110053 | L3 | Admitted-Finance | ||
| 4 | L4₹20.6 L+₹2.7 L (15.4%)Admitted-Finance | L4 | Admitted-Finance | ||
| 5 | L5₹22.0 L+₹4.2 L (23.4%)Admitted-Finance | L5 | Admitted-Finance |
Tender Value
₹21.5 L
EMD Value
₹43,060
Closing Date
16 Mar 2026, 3:00 pmClosed
Er. CHANDER SINGH RAWAT
The Executive Engineer (E), West Electrical Division (M-131N), PWD, 41 Rama Road, Zakhira New Delhi-15, Telephone No. 25459518, e-mail ID [email protected]
Installation of Air conditioner at Asha Jyoti Home Nirmal Chhaya Complex.
2026_PWD_288281_1
89/EE(E)/West Elect Div(M-131N)/PWD/2025-26
Open Tender
Electrical Works
Works
30 days
Work
Please refer Tender documents.
13 documents required · 13 mandatory
₹0
₹43,060
17 Mar 2026
7 Mar 2026
16 Mar 2026
7 Mar 2026
16 Mar 2026
7 Mar 2026
Supplying , Installation, Testing and Commissioning of Air Cooled Hi Wall split type Air conditioners complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU) i/c drain pipe R-32/R-410/ R-407 Green Refrigerant, wireless Remote control, suitable for working between 180- 260V with low & high voltage cutoff and 50 hz ,1 phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary compressor. The system shall be able to deliver 100% of the rated capacity upto 42 0C. Min 5 year Original Equipment Manufacturer (OEM) warranty both compressor and Printed Circuit Board (PCB). Must comply : Electrical cable IS 694 or IS 9968 temperature sensing control IS /International Electrotechnical Commission (IEC) 60730, hermetic compressor IS 10617, heat exchanger IS 11329, capacitor IS 2993 and motor IS 12615. Complete as per CPWD specification and IS : 1391 Part II 2023. The system shall be able to operate up to 50 0C (out door ambient temperature).
2.0 TR with 5 Star BEE Rating
Providing and fixing of readymade MS fabricated and duly painted, wall bracket type stands for mounting the Split A.C. outdoor unit including grouting on the wall and making good the damages to surface complete with rubber vibration pads on outdoor unit bolts etc. complete as required
SITC of 5 KVA capacity Automatic Line Voltage stablizer copper bound wall mounted having following specifiation with TDR. :- (a) Input Voltage : 170-275 volt (b) Output Voltage : 230 volts (+ 10%)
Supplying, Installation, testing and commissioning including vaccumiazation and Nitrogen testing of following nominal sizes of soft/hard drawn copper refrigerant piping for VRV/VRF system, complete with fittings, with suitable adjustable ring type hanger supports, jointing/brazing including accessories, insulated with XPLE Class-O tubular insulation/with Class-O closed cell elastometric nitrile rubber tubular sleeves sections of 19 mm thick insulation as given below for Suction and Liquid lines, all accessories as per specifications etc. as required :
6.4 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm
15.86 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm
Providing and carrying out core cutting in RCC/brick masonry wall for passing refrigerant pipes, drain pipe and control cable of air-conditioning unit up to 4 TR, including filling the core opening with PU foam and making good the surface after installation, complete as required.
Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.
2 X 6 sq. mm + 1 X 6 sq. mm earth wire
4 X 6 sq. mm + 2 X 6 sq. mm earth wire
Supplying & fixing suitable size Gl/PVC box wih modular plate and cover in fronton surface or inrecess including oviding and fixing 25 Amodular socket outlet and 25 A modular SP MCB, "C" curve including connections, painting etc. as required. (BOX SHOULD BE MINIMUM 4 MODULE)
Supplying and fixing of industrial multicore flexible 4 Core Cable PVC insulated & Sheathed with bare Annealed copper conductor as per IS 694-1900 including connection and testing as required.
Credit to the Contractor on as-is-where-is basis,including dismantling, collection, loading, unloading, Transportation, and all incidental charges, complete as directed by the Engineer-in-Charge.
Assorted types of 1.5 TR Split AC
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.63 MB
BOQ_382229.xls
BOQ • 0.48 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .