| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹24.3 LAccepted-AOC | L1 | Accepted-AOC LOWEST BIDDER | |
| 2 | L2₹25.9 L+₹68,526 (2.71%)Rejected-Finance | L2 | Rejected-Finance HIGHER BIDDER | |
| 3 | L3₹29.8 L+₹4.6 L (18.2%)Rejected-Finance | L3 | Rejected-Finance HIGHER BIDDER | |
| 4 | L4₹34.9 L+₹9.7 L (38.3%)Rejected-Finance 17 1A BALLYGUNGE CIRCULAR ROAD KOLKATA 700 019 | KOLKATA | WEST BENGAL | 700019 | L4 | Rejected-Finance HIGHER BIDDER |
Tender Value
₹27.3 L
EMD Value
₹54,600
Closing Date
22 Nov 2022, 6:00 pmClosed
VIVEK TANENIA
GARRISON ENGINEER (CENTRAL) KOLKATA T37 NAPIER ROAD HASTING KOLKATA 700022
8497/E8
2022_MES_558796_1
8497/E8
Open Tender
Miscellaneous Works
Works
270 days
KOLKATA
AS PER TENDER DOCUMENTS
9 documents required · 9 mandatory
₹500
GE (C) KOLKATA
₹54,600
Yes
13 Feb 2023
19 Oct 2022
23 Nov 2022
19 Oct 2022
22 Nov 2022
3 Nov 2022
19 Oct 2022 - 2 Nov 2022
Amount
Taking down point wiring (light, fan, socket and power complete including fixtures and fittings such as switches ceiling roses, pendents , regulators, sockets, light fittings etc. removing materials to store for keeping in safe custody for refixing or for taking credit (credit for above items should be made as per conditions separately) and making good distrubed surfaces of walls, floors, etc.complete all as specified and directed.
M&L Point wiring with PVC insulated and unsheathed FRLSH cable single core multistranded copper conductor 1.5 sqmm size, 1100 volts grade cable conforming to IS - 694 1990 drawn through and including PVC casing caping of suitable size with all accessories including fabricated MS terminal boxes fixed flush with wall surface with 3 mm thick plastic masonite laminated sheet top cover fixed with cadmium screw for mounting switches, sockets, regulator etc including 1.5 sq mm FRLSH stranded PVC insulated and unsheathed copper conductor earth continuity conductor to common earth and connecting to earth dolly for one light or fan point controlled by one switch single pole one way for light/ ceiling fan/ exhaust fan /call bell point/ Switch socket outlet 5 amps complete all as specified and as directed. Note: Red coloured cable shall be used for live connection, black coloured cable shall be used for neutral connection and green coloured cable shall be used for earthing. Separate cable for earthing and neutral to be used for each individual circuit from the distribution board..
All as per item No. 2.00 here-in-before but one 3 pin 5 amps socket outlet on the same board with other switch complete all as specified and directed by Engineer-in-charge.
All as per item No. 2.00 here-in-before but one 3 pin 5 amps switch socket outlet on the independent board with other switch complete all as specified and directed by Engineer-in-charge.
M&L fo Point wiring surface type with 2.5 sqmm (Nominal Area) PVC insulated stranded single core unsheathed FRLSH copper conductor cable 1100 Volts grade drawn through with and including PVC casing caping with all fittings and accessories of casing caping (like Tee, Bend etc) complete fixed to walls / ceiling etc with and including 2.5 Sqmm (nominal area) PVC insulated unsheathed, stranded, single core FRLSH copper cable as earth continuity wire connecting to common earth point (including supply & fixing of 1.6 mm thick pressed mild steel terminal boxes of suitable size with 3 mm thick PVC /plastic laminated sheet, top cover suitable sizes of brass screws and washers etc. for mounting sockets for 5 pin, 16 Amp Switch socket combination on independent board complete all as specified and directed.
S&F Switch piano, flush type, SP, one way, 5/6 Amps 230/240 Volts, white/ivory finish complete all as specified and directed. Make:- Anchor Product Code No 14111/Legrand cat no-677200/ Havells cat no -AHFSXXW101/ Plaza / Cona.
S&F Switch socket combination multipurpose 2 in 1, 3 pin 15 Amps & 5 Amps 230/240 volt flush type complete all as specified and as directed. Make:- Anchor Cat No- 14614/ Legrand cat no-673042/Havells/ Plaza / Cona.
S&F Socket outlet 3/5 pin, 6 Amps, 240 volt flush type complete all as specified and as directed. Make:- Anchor 14304 / Havells AHEKPOW063/ Legrand 673044.
S&F Lamp holder suitable for batten fittings complete all as specified and directed by the Engr-in-Charge. Make:- Anchor Cat No- 395538/51205/ Havell's Cat no-AHLHAMW000/Legrand/ Plaza / Cona.2391
S&F Ceiling rose surface bakelite three terminals 240 volts complete all as specified and as directed. Make:- Anchor Cat No 39040/3290/ Havells/ Plaza / Cona.2086
S&F Ceiling fan regulator electronic Step type, solid state, , 240 volts, complete all as specified and as directed. Make:-Cona -- 9381 /Anchor .. 14502 / Havells.. Coral 80w
Cutting & Chasing required on brick wall not exceeding 10 CM girth for concealed conduit wiring and making good to disturbed surface with cement mortar 1:3 and distemper / colour wash etc to match with existing surfaces including facing / finishing complete all as specified and directed.
M&L for earthing as per IS:3043 with galvanized steel earth plate electrode 600 mm x 600 mm x 6.0 mm thick buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metre below normal ground level connected to galvanized strip 32 mm x 6 mm as earthing lead protected by GI pipe medium grade 15 mm bore for protection of GI earth wire and 20 mm dia GI pipe medium grade for watering with alternate layers of charcoal /coke and salt including all accessories like nut, bolts, reducer, nipple, wire meshed/screened funnel and making brick masonry finished chamber of internal size 300 mm x 300 mm x 300 mm with concrete base, covered with a Cast Iron hinged cover resting over the Cast Iron frame painted with bitumastic paint which shall be embedded in the block masonry including excavation works, refilling, connected to main switch/MCB DB for feeding the electric supply to domestic quarters complete all as specified and as shown in electrical plate No. 5 of SSR Part-I and testing of earth resistance as required complete all as specified and directed.
Taking down unserviceable rusted / damaged MCB DBs of any type and way along with any type MCB and keeping serviceable MCB in safe custody in re-use in the work and making good to the distubed surfaces of walls etc. complete all as specified and as directed.
Taking down unserviceable rusted / damaged MCB TP/SPN/SP of any type and way along with any type MCB and keeping serviceable MCB in safe custody in re-use in the work and making good to the distubed surfaces of walls etc. complete all as specified and as directed.
S&F MCB SPN DB made up with sheet metal double door, phosphorised, power coated, neutral link, earth bar and din rail, 4 way with 200 amps rated bus bar, 240 volts complete all as specified and as directed. Make:- L&T Cat part No.DBSPN004DD/Legrand cat no- 507600or equivalent ABB/ C&S Electric Ltd.
S&F Sheet metal enclosure for DB's when MCBs to be used 8 way single pole and neutral double door with 200 amps rated bus bar complete 240 volts complete all as specified and as directed. Make:- L&T Cat part No.DBSPN008DD/Legrand cat no- 507601or equivalent ABB/ C&S Electric Ltd.as per direction of engineer in charge.
S&F Sheet metal enclosure for DB's when MCBs to be used 12 way single pole and neutral double door with 200 amps rated bus bar complete 240 volts complete all as specified and as directed. Make:- L&T Cat part No.-DBSPN012DD/Legrand cat no- 507602or equivalent ABB/ C&S Electric Ltd.as per direction of engineer in charge.
S&F MCB TPN DB double door made up with sheet metal, phosphorised, power coated, neutral link, earth bar and din rail, 4 way TPN with 200 amps rated bus bar, 415 volts complete all as specified and as directed. Make:- L&T Cat part No.-DBTPE004DD/Legrand cat no- 507660 or equivalent ABB/ C&S Electric Ltd.
S&F MCB TPN DB double door made up with sheet metal, phosphorised, power coated, neutral link, earth bar and din rail, 8 way TPN with 200 amps rated bus bar, 415 volts complete all as specified and as directed. Make:- L&T Cat part No.-DBTPE008DD/Legrand cat no- 507662 or equivalent ABB/ C&S Electric Ltd.
S&F MCB 6 to 32 Amps, SP, 240 Volts , 'B' curve breaking capacity 10 kA complete all as specified and as directed. Make:- Legrand Cat Part No 408595, L & T Cat part No.BB10060B to BB10320B or equivalent in Hager/ Siemens/ ABB/ Schneider.
S&F MCB 6 to 32 Amps, SP, 240 Volts , 'C' curve breaking capacity 10 kA complete all as specified and as directed. Make:- Legrand Cat Part No-408587- 408595, L & T Cat part No.BB10060C to BB10320C or equivalent in Hager/ Siemens/ ABB/ Schneider.
S&F MCB 40 Amps, DP 240 Volts ,B- Curve breaking capacity 10 KA complete all as specified and as directed. Make:- Legrand Cat Part No 408617 or equivalent in L&T Cat part No.BB20060B to BB20320B/ Hager/ Siemens/ ABB/ Schneider.
S&F MCB 32 Amps, DP 240 Volts ,C- Curve breaking capacity 10 KA complete all as specified and as directed. Make:- Legrand Cat Part No 408617 or equivalent in L&T Cat part No.BB20060C to BB20320C/ Hager/ Siemens/ ABB/ Schneider.
S&F MCB 63 Amps, TP 415 Volts ,C- Curve breaking capacity 10 KA complete all as specified and as directed. Make:- Legrand Cat Part No 408683 or equivalent in L&T Cat part No.BBBB40630C/ Hager/ Siemens/ ABB/ Schneider..
M&L for repair bldg main panels through carrying out check all electrical connections including incoming and out going UG cables any size ,lugs, busbar,voltmeter, ammeter ,cableglands ,insulator on busbar, and tightning all these conecctions properly with proper size of new nut bolts washer as per the site requirments and taking out the serviceable UG cables from the panel anf refixing these cables properly after necessary re alignment with necesssary MS clamps as specified and insulation of busbar with colour code insuation tapes and preparation of surfaces internal and external of panels by cleaning with dry cloth /removal dust particles by using air blower and scratching the old painted surfaces as directed and painting two coat of synthetic enamel paint over a coat of red oxide prime and writting existing letters /numbers or as directed and repair the existing PCC foundation of the LT panel as per site requirment or directed and preperation of old surfaces of the panel foundation by scrapping and applying one coat of cement base point and testing complete with all electrical connection made complete all as specified and as directed.
M&L for earthing complete with galvanised steel earth plate electrode 60 cm x 60 cm x 6.00 mm thick burried in ground (earth pit not less than 2.25 m deep below ground level) with top edge of the plate not less than 1.5 m below normal ground level, connected to GI strip 4 mm as earthing lead by means of bolts, nuts, check nuts and washers of GI or steel, GI strip proected by 40 mm bore light grade GI pipe and other end connected to earth test point as directed including funnel with watering pipe 20 mm bore light grade galvanised iron, wire mesh, charcoal or coke common salt laid in alternative layer of 15 cm (complete thickness) all round the earth electrode, concrete earth pit in PCC (1:3:6) type C-1, 50 mm thick pre-cast RCC (1:2:4) type B-1 normal mix cover slab reinforced with 8 mm dia TMT bar 10 cm c/c bothways and single handle of 10 mm dia round bar including necessary excavation, earth work etc. in soft / loose soil and disposal pf soil to a distance n. exc. 50 m and necessary testing on completion all as shown in electrical plate No. 3 MES Schedule Part-I complete all as specified and directed.
S&F RCCB double pole sensitivity 30 mA, 2 module 240 volts, 40 Amps complete confirming to IS-12640 (part I) including taking down old isolator/MCB complete all as specified and as directed. Make- L&T cat no BG204003 Havells Cat no DHRGCTDF0300401 / Legrand Cat no DX3 411852
S&F MCCB 4 pole 250A, 36KA, 415V thermal and magnetic adjustable type including making all fixing arrangement, cutting welding of existing panel board as per site requirment and painting the disturbed part of panel as per the existing colour of the panel and electric connection including taking down old one. complete all as specified and directed. Make:-Havells IHLFN440250 Legrand cat No- 4203 49/Schneider LV525313
S&F MCCB 3 pole 160A, 25KA, 415V thermal and magnetic adjustable type including making all fixing arrangement, cutting welding of existing panel board as per site requirment and painting the disturbed part of panel as per the existing colour ofthe panel and electric connection including taking down old one complete all as specified and directed. Make:-Havells Cat Part No. IHLGHTO0160/ Legrand cat no- 4203 07/ Schneider LV516303
S&F MCCB 3 pole 100A, 25KA, 415V thermal and magnetic adjustable type including making all fixing arrangement, cutting welding of existing panel board as per site requirment and painting the disturbed part of panel as per the existing colour of the panel and electric connection including taking down old one complete all as specified and directed. Make:-Havells Cat Part No. IHLASDC30100 / Legrand cat no - 4203 05/ Schneider LV510307
S&F MCCB 4 pole 160A, 36KA, 415V thermal and magnetic adjustable type including making all fixing arrangement, cutting welding of existing panel board as per site requirment and painting the disturbed part of panel as per the existing colour ofthe panel and electric connection including taking down old one complete all as specified and directed. Make:-Havells Cat Part No. IHLGHF0100 Make:-Havells IHLANFO160 / Legrand cat No- 4203 47/Schneider LV516313
S&F Aviation obstruction light in yellow coloured die cast aluminium alloy housing with built in 75 VA step up transformer, heat resistant, clear thick glass dome mounted on hinged die-cast aluminium ring secured to the body by two studs and wing nuts with neon spiral lamp plugged into spring loaded high tension nylon socket and wired upto the terminal block having degree of protection- IP 54 including dismantling and taking down existing unserviceable/worn out aviation light from RCC over head tank of height not more than 21.0 Mtr complete all as specified and directed. Make- Bajaj ,Cat part No BJAOL 1with neon lamp or equivalent model in Philips / Wipro etc
Taking down old burnt/unserviceable submain wiring with aluminum/copper conductor PVC insulated cable of any size drawn through PVC casing caping/ PVC Conduit pipe including GI wire accessories etc. and making good disturbed surfaces of walls, floors, etc complete all as specified and directed.
M&L Sub main wiring with 2 runs of single core FRLSH type PVC insulated unsheathed stranded copper conductor of size 4.0 Sqmm and one run of PVC insulated unsheathed multistrand copper conductor FRLSH type of size 4.0 Sqmm as earth lead drawn pvc casing caping including all fittings complete all as specified and as directed. Note:- Two runs of 4 Sqmm conductor as main wire and one run of 4 Sqmm conductor as earth wire with one run of PVC Casing Caping shall be measured as one unit.
M&L Sub main wiring with 2 runs of single core FRLSH type PVC insulated unsheathed stranded copper conductor of size 6.0 Sqmm and one run of PVC insulated unsheathed multistrand copper conductor FRLSH type of size 6.0 Sqmm as earth lead drawn through PVC conduit of size 25 mm dia including all fittings complete all as specified and as directed. Note:- Two runs of 6 Sqmm conductor as main wire and one run of 6 Sqmm conductor as earth wire with one run of PVC conduit shall be measured as one unit.
M&L Sub main wiring with 2 runs of single core FRLSH type PVC insulated unsheathed stranded copper conductor of size 10.0 Sqmm and one run of PVC insulated unsheathed multistrand copper conductor FRLSH type of size 10.0 Sqmm as earth lead drawn through PVC conduit of size 25 mm-40mm dia including all fittings complete all as specified and as directed. Note:- Two runs of 10 Sqmm conductor as main wire and one run of 10 Sqmm conductor as earth wire with one run of PVC conduit shall be measured as one unit.
S&F Changeover Switch for bldg lift services, in sheet steel enclosure, four pole, 250 Amps, Manual type, 415 V complete all as specified and as directed. Make: L&T Cat Part No. CO32500OSOO or Make: Havells Cat part No. IHCNFE0250.
Taking out old U/S LT UG cable of any size and any description including GI pipe of any dia fixed with bldg and bricks for fixing of existing bldg service cables protection where ever appeared complete all as directed by Engineer-in-Charge.
Supply & Laying for bldg service LT cable XLPE insulated electric cables with Al conductor ,1100 volts grade ,cross sectional area 25 Sq mm 3.5 core.in ground/fixed on wall ,roofwith saddles and fixing screws etc. and electric connection complete all as specfied and directed. Make- Havells / POLYCAB /KEI/PLAZA
Supply & Laying for bldg service LT UG cable XLPE insulated electric cables with Al conductor ,1100 volts grade ,cross sectional area 35 Sq mm 3.5 core.in ground/fixed on wall ,roofwith saddles and fixing screws etc. and electric connection complete all as specified and directed. Make:-Havells / POLYCAB /KEI/PLAZA
Taking down old aluminium strip/ GI strip of any size and refixing the same with new saddles ,clamps,screws etc to its original position and taking down existing unserviceable/worn out complete all as specified and directed.
S&F Galvanised iron strip of size 32 x 6 mm with saddles and fixing screws etc buried in ground incl taking down old unserviceable one complete all as specified and as directed.
S&F Air termination aluminium single pointed rod 12 mm dia, 300 mm long incl taking down old unserviceable one complete all as specified and as directed.
S&F Test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm,drilled and screwed including 3 Nos 8mm dia 25mm long hex. head screw incl taking down old unserviceable one complete all as specified and as directed.
B M ENTERPRISE
m d yasin
M A ENTERPRISES
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .