| # | Company | Quoted % | Amount | Rank | Status |
|---|---|---|---|---|---|
| 1 | L1₹1.3 CrAdmitted-Finance | -9.31% | ₹1.3 Cr | L1 | Admitted-Finance |
| 2 | L2₹1.4 Cr+₹9.7 L (7.27%)Admitted-Finance SHIV SHAKTI NAGAR PLOT NO 35 NIWARU ROAD JHOTWARA JAIPUR 302012 | JAIPUR | RAJASTHAN | 302012 | -3.16% | ₹1.4 Cr+₹9.7 L (7.27%) | L2 | Admitted-Finance |
| Sl No | Description | Qty | Unit | Navyug Engineering L2 | Gitaa Equipment Industries L1 |
|---|---|---|---|---|---|
| 1.00Supplying, Installation, Testing & Commissioning of floor mounted dust and vermin proof compartmentalised cubical type main fire pump Control Panel made out of CRCA sheet , required hardware ,duly treated for derusting in 7 tank process with dephosphating and with powder coating on both side of panel in desired shade The panel having PU/ Neoprene rubber gasket of not less than 3mm thickness , separate detachable gland plate M.S. base channel ,hinged door with locking arrangement for equipment/switchgear . Thickness of sheet shall not be less than 1.6 mm up to 600 mm length / width of any compartment and be of 2.0 mm above 600 mm. Load bearing structure shall be of 2.0 mm thick sheet supported by base M.S. channel if required . Side walls and cable alley compartments having bolted type doors and having accessories / switch gear (as per Specf Ch-06 & 08) as below:- complete in all respect. All as per pre approved by Engineer in charge. | |||||
| 1.01Incomer:- | |||||
| 1.02400 Amp. TPN MCCB (adj.O/L) with Extended ROM, 36 kA, with Thermal magnetic release, Analouge Ammeter, Voltmeter, Selector switches,CT, Indicating Lamps, 500 Amps FP Alum. Bus bar with with heat shrinkable sleeves. | |||||
| 1.03Out going:- | |||||
| 1.04(a) 200 Amp. TPN MCCB(adj.O/L) with Extended ROM, 36 kA, with Thermal magnetic release, Analouge Ammeter, Voltmeter, Selector switches,CT, Indicating Lamps for 'ON', 'OFF', 'TRIP' 1 no. DOL Starter of rating upto 75 HP with thermal over load relay, timer, push buttons, Auto / Manual selector switch, Single phase preventor - 2 Sets | |||||
| 1.05(b) 63 Amp. TPN MCCB (adj.O/L) with Extended ROM, 16 kA, with Thermal magnetic release, Digital Ammeter, Voltmeter, Selector switches, CT, Indicating Lamps for 'ON', 'OFF', 'TRIP' 1 no. DOL Starter of 5 - 15 HP with thermal over load relay, timer, push buttons, Auto / Manual selector switch, Single phase preventor - 1 Set | |||||
| 1.06(c) One no. Diesel Engine Auto Starting kit with Auto Manual selector switch & 3 attempt starting device, timers, relays, Indicating lamp for High / Low Lub. Oil pressure, High water temperature and engine ON indication, DC ammeter & voltmeter | |||||
| 1.07(d) System controller to control Operation Main Electric pumps, Diesel pump, jockey pump in sequence consisting of relays, timers, sensors, annuciation window for fault indication. | |||||
| 1.08 | (e) Appropriate Test Certificate/ report of product/accessories from OEM/Panel Manufecturer shall be submitted. | 1 | Each | 1,86,000 ₹1,86,000 | 1,85,000 ₹1,85,000 Lowest |
| 2.00 | Supply of Painted/ Powder coated galvanized steel Flush Fire doors of 2 hrs. Fire rating and tested in accordance with IS 3614 Part 2 & BS 476 Part 22 as per prototype tested and certified at CBRI Roorkee or equivalent laboratory. Door frames to be double rebate profile of 143 x 57mm manufactured from 1.6mm galvanized steel sheet, profile to have bending radius of 1.4 mm supplied in assembled form ready to install at site. Door Shutter in 46mm +2 mm thick manufactured from 1.2mm galvanized steel sheets, lock seam jointed at stile edges to form a double skin fully flush shell. Infilled honeycomb insulation material to be provided for structural rigidity & additional reinforcements & sound Insulation, The internal construction of the door should be appropriate for all hardware fixtures (SS Ball BearingHinges-4"x3"X3mmGeze,Door Closer, Dead LockWith 70mm EPC,Handle-300X19mm, Vision Panel,Flush Bolt etc.) as required, vision panel grooves wherever applicable shall be provided as per recommendations with beading and screw. (Hardwares to be paid seperately as per your requirement.) Size: 1800 x 2100mm- Double Leaf | 10 | Each | 50,400 ₹5,04,000 | 40,000 ₹4,00,000 Lowest |
Tender Value
₹1.5 Cr
EMD Value
₹2.9 L
Closing Date
21 Aug 2026, 6:00 pmClosed
Executive Engineer M and H, Dn. 2 Jaipur
Executive Engineer M and H, Dn. 2 Jaipur
SITC of Fire Fighting, Fire Deduction work at SDH Merta City, Distt Nagaur.
2026_MEDIC_584345_3
NIT No.13/2026-27EEM and HDiv 2 Jaipur/
Open Tender
Electrical Works
Percentage
365 days
Merta City Nagaur
Please refer Tender documents.
3 documents required · 3 mandatory
₹1,000
Yes
RTGS/NEFTRTGS/NEFT/Any other money Transfer System
₹2.9 L
18 Sept 2026
8 Aug 2026
24 Aug 2026
8 Aug 2026
21 Aug 2026
8 Aug 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | PUMP ROOM EQUIPMENT | - | - | - | - |
| 2 | Supplying, Installation, Testing & Commissioning of Electrical Driven fire fighting duty pump as per TAC and IS 12469-1988., Factory assembled in Pump make OEM for Sprinkler / Hydrant applications suitable for automatic operation and consisting of following details given as A, B, C, D, E, F, G and H. | - | - | - | - |
| 3 | (A) End Suction / Horizontal Axially split casing volute type Single / Multi stage Centrifugal pump complete for delivery of below mentioned discharge and Head | - | - | - | - |
| 4 | (B) Material of construction : Pump Casing - Cast Iron, Impellor - Bronze, Shaft - SS 410, Packing - Mechanical Seal | - | - | - | - |
| 5 | (C)Pump shall be capable of furnishing not less than 150 % of rated capacity at a head not less than 65 % of the rated head. The shut off head shall not exceed 120 % of rated head | - | - | - | - |
| 6 | (D) Squirrel cage induction motor (IE-3 Class) suitable for 3 phase, 415 V, 50 HZ, Ac supply , Class -F Insulation, Synchronous speed 2900 / 1500 RPM, T.E.F.C confirming to IP:55 , of required HP suitable for the above pump ,along with flexible (Love Joy type) coupling , coupling guard complete in all respect . | - | - | - | - |
| 7 | ( E) Common bed plate fabricated from mild steel channel for installation of pump and Motor including anti vibration pads. | - | - | - | - |
| 8 | (F) The Hydrostatic tests (2 times of design operating head or 1.5 times the shut off head whichever is higher) and performance tests (to determine developed head, Pump BHP and efficiency v/s Flow) of pumps along with trip test shall be carried out at manufacturer’s works in Physical presence of Department’s representatives. | - | - | - | - |
| 9 | (G) Physical & Chemical Test reports of i) Pump casing (ii) Impeller (iii) Shaft (iv) Shaft sleeve and Dynamic Balance certificate is to be submitted by OEM | - | - | - | - |
| 10 | (H)Suitable size Reinforced cement concrete (M-30) foundation with foundation bolt, Nozing Angle of size 40mm x40mm x5 mm ( Cost of RCC Foundation to be paid Extra ). All as per pre approved by Engineer in charge. | - | - | - | - |
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 5.51 MB
Tendernotice_2.pdf
PDF • 7.44 MB
Tendernotice_3.pdf
PDF • 2.69 MB
Tendernotice_4.pdf
PDF • 0.07 MB
Annexure-A-BSR-2022.pdf
Tender Documents • 0.26 MB
T-and-C-for-Electrical-work-DLP--Annexure-B---3-.pdf
Tender Documents • 0.24 MB
Special-TandC-for-Electrical-work--Annexure-C---3-.pdf
Tender Documents • 0.35 MB
BOQ_1037843.xls
BOQ • 0.60 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .