Loading…
Loading…
Tender Value
₹1.1 Cr
EMD Value
₹2.1 L
Closing Date
15 Oct 2026, 3:00 pm
No
No
Single Packet System
Normal Tender
No
Not Applicable
Lowest to Highest
60 days
Expenditure
Capital (M & P)
Above/Below/Par
TENDER
14 conditions · 2 needing a document upload
The tenderer must have minimum average annual contractual turnover of V/N or "V" whichever is less ;where V= Advertised value of the tender in crores of Rupees N= Number of years prescribed for completion of work for which bids have been invited. The average annual contractual turnover shall be calculated as an average of 'total contractual payments" in the previous three financial years, as per the audited balance sheet. However, in case balance sheet of the previous year is yet to be prepared/ audited, the audited balance sheet of the fourth previous year shall be considered for calculating average annual contractual turnover. The tenderers shall submit requisite information as per Annexure-VIB, along with copies of Audited Balance Sheets duly certified by the Chartered Accountant/ Certificate from Chartered Accountant duly supported by Audited Balance Sheet
(a)The tenderer must have successfully completed or substantially completed any one of the following categories of work(s) during last 07 (seven) years, ending last day of month previous to the one in which tender is invited: (i)Three similar works each costing not less than the amount equal to 30% of advertised value of the tender, or (ii)Two similar works each costing not less than the amount equal to 40% of advertised value of the tender, or (iii)One similar work costing not less than the amount equal to 60% of advertised value of the tender. (b)(1) In case of tenders for composite works (e.g. works involving more than one distinct component, such as Civil Engineering works, S&T works, Electrical works, OHE works etc. and in the case of major bridges - substructure, superstructure etc.), tenderer must have successfully completed or substantially completed any one of the following categories of work(s) during last 07 (seven) years, ending last day of month previous to the one in which tender is invited: (i)Three similar works each costing not less than the amount equal to 30% of advertised value of each component of tender, or (ii)Two similar works each costing not less than the amount equal to 40% of advertised value of each component of tender, or (iii)One similar work each costing not less than the amount equal to 60% of advertised value of each component of tender.
Defination of Similar Work :- Similar works for the above tender shall be:- Supply, installation, testing and commissioning of any LT/HT Electrical Work
50 conditions · 6 needing a document upload
Valid copy of PAN and GSTIN needs to be furnished along with the documents.
Tender Form (First Sheet) as per 'Annexure- I'
For Sole Proprietorship firm a)Affidavit as per 'Proforma- I'.b)Special power of Attorney as per proforma given in 'Proforma-II' to be submitted by sole proprietor firm duly notarized.(Not required if tender documents are submitted by proprietor himself)
For Partnership firm a)Self/Notary attested copies of Partnershipdeed. b)Special Power of Attorney as per proforma given in'Proforma-III' to be submitted by Partnership firm. (Not required if one or more partners are authorized in Parternership deed tosign on behalf of the firm.)
For Limited Company a) Copy of Memorandum & Articles of Association of Company. b)Self /Notary attested copy of resolution passed by Board of Directors authorizing its Director/Employee to deal with tender on behalf of company. c)Attested copy of Notarized Special Power of Attorney including ratification clause duly signed by person authorized by the company.(D) A copy of Certificate of Incorporation
Please enter the percentage of local content in the material being offered. Please enter 0 for fully imported items, and 100 for fully indigenous items. The definition and calculation of local content shall be in accordance with the Make in India policy as incorporated in the tender conditions.
The total cost is including GST. Hence tenderer are advised to quote the tender inclusive of GST
All the dismantled material should be handed over to E.I.C. at site with proper challan.
All materials which will be utilized for this work shall confirm to relevant IS specifications.
All the materials should be got inspected and approved by the competent representative of Sr.DEE/G/RNY & Engineer in Charge should be contacted before execution of work.
The contractor(s) have to supply all petty stores, which may be required for successful commissioning of the equipments, but not mentioned in the schedule of works. The rate quoted against each item shall be inclusive of those petty stores.
Joint Test reports with EIC for earth resistance to be submitted with submission of bill.
The Contractor shall execute the work to entire satisfaction of the site Engineer, SR DEE/RNY or his representative.
Switchgears like MCCB,MCB, RCCB , etc. should be of Make:- ABB/Siemens/ Legrand/ L&T.
All Switch, socket, power unit, ceiling rose, holder, AC starter, Modular box, Modular plate etc make should be of Crompton, Kolors(Kany Kom)/ Anchor/C&S/Legrand.
Distribution Box should be of make. C&S/Legrand/L&T/ABB.
Indoor LED lights should be of Make:-Crompton/Phillips/ Kolors/Jaquar.
Tunnel LED lights should be of Make:- Crompton/ Phillips/Bajaj.
High Bay LED lights should be of Make:- Crompton/Phillips/Jaquar/Kolors.
GI pipe should be of Make:-Jindal/Bansal/Hindustan/Tata/Nezone
HDPE pipe should be of Make:-AJA Plus/Swastik/Sudhakar Marketing Agencies/Jain.
Industrial fan should be of Make:-Bajaj/ Crompton/ Orient/ Usha/ Polar .
Switch and Socket should be of Make:-Kolors (Kany Korn)/ Anchor/ Richa/C & S/ Benlo/Legrand
Industrial socket should be of make:- Hensel/ABB/L&T/Scheinder/Legrand.
Cable tray should be of make:- ABB/Legrand/L&T.
XLPE Cable should be of Make:-Havell's/ Richa/ Polycab/ Kolors/ Anchor/BCH/KEI /Finolex.
Wiring cable upto and including 1100 volt should be of Make:- Havell's, Polycab, Finolex,Mescab, Richa make confirming to IS:694-1990 (Re-affirmed 2000) with latest amendments.
Colour coding should be used in all wiring. For Positive- Red, Negative - Black & Earth - green.
The drawing of panel board should be approved by the competent authority before fabrication and commissioning.
Tenderer should submit the documents as per the Annexure-'A' attached at the time of submission of bill.
Payment terms: Payment 70-80% of the payment shall be made to the contractor/firm against the supply of material of the work
For any damage to railway, recovery will be made as per cost of damage to railway.
Successful Tenderer shall produce & hand over test and Guarantee certificate issued by manufacturer of all the equipment/ Component at the time of supply to Railways, failing which bill of the work will not be passed.
Successful contractor must follow guidelines as per extant rules of IR Shramik Kalyan Portal.
Insurance policy has to be taken against contract by contractor, indemnifying the Railways of any financial implication arising due to payout of claims on account of damages, accidents, untoward incidents etc. during the execution of work.
Details(Qualification,ID & address proof and etc) of Nominated Supervisor/Engineer for the work should be submitted before execution of the work.
Contractor has to ensure minimum labor wage payment as per latest minimum wage Act. In case of any complain and if found to be true, then work will be terminated immediately without any notice.
All staff at site should wear all safety gears,PPE kit,Helmet, Insulated Hand Gloves,Safety harness and follow all safety precaution including to avoid any untoward incident .
All staff at site should wear all safety gears and follow all safety precaution to avoid any untoward incident. If staff is found without proper safety gear, then work will be stopped and penalty of Rs 50,000 per day per site will be imposed.
If staff as per message of SSE/Office is not provided by Agency, then penalty of Rs 50,000 per day per site will be imposed for delay in work on Agency.
No work can be carried out without availability of site supervisor. if site supervisor is not available , then work will be stopped and penalty will be imposed as per GCC.
Police verification,Pan card/AADHAAR card should be submitted for all manpower engaged before the execution of the work.
At NHLN-Electrical works in connection with construction of CNC-UFWL plant.
RNY-EL-T-02-2026-27~NFR
RNY-EL-T-02-2026-27
Open
Works - General
180 Days
Kamrup, Assam
₹0
₹2.1 L
23 Sept 2026
23 Sept 2026
1 Oct 2026
78 items across 2 schedules
| # | Description | Unit | Qty | Rate | Amount |
|---|---|---|---|---|---|
| — | — | — | 98,38,675.27 | ||
| — | 4.00 | — | — | ||
| Dismantling, Shifting & Re-installation, Testing & Commissioning of 500 kVA & 250kVA transformer Using man power with necessary tools & accessories as per direction of EIC at site. | — | — | — | 2,00,000 | |
| — | 2.00 | — | — | ||
| Supply. Installation, testing and commissioning of MS cubical type floor mounted double door Out-door LT panel board of suitable size and suitable for 415 V, 50 Hz AC supply made out of CRCA sheet not less than 14 SWG. Having i) 400A, 4P, 36kA, Ics=100%Icu, FTM(Thermal Magnetic) Release, Fixed over load, Fixed short circuit, Main MCCB - 1 No, ii) 250A, 4P, 36kA, Ics=100%Icu, FTM(Thermal Magnetic) Release, Fixed over load, Fixed short circuit, Sub Main MCCB - 2 No, iii) Fabrication of Panel board with 14 SWG CRCA sheet including CC foundation, cable alley, digital function meter, LED indicator lamp,CT,6A SP MCB, 500A, 4 pole & amp; neutral copper busbar, LED indication lamp with voltmeter & amp; ammeter and all accessories as per direction of EIC at site - 1 job | — | — | — | 7,42,558.76 | |
| — | 2.00 | — | — | ||
| Supply. Installation, testing and commissioning of MS cubical type floor mounted double door Out-door LT panel board of suitable size and suitable for 415 V, 50 Hz AC supply made out of CRCA sheet not less than 14 SWG.) having i) 400A, 4P, 36kA, Ics=100%Icu, FTM(Thermal Magnetic) Release, Fixed over load, Fixed short circuit, Main MCCB - 1 No, ii) 250A, 4P, 36kA, Ics=100%Icu, FTM(Thermal Magnetic) Release, Fixed over load, Fixed short circuit, Sub Main MCCB - 2 No, iii) Fabrication of Panel board with 14 SWG CRCA sheet including CC foundation, cable alley, digital function meter, LED indicator lamp,CT,6A SP MCB, 500A, 4 pole & amp; neutral copper busbar, LED indication lamp with voltmeter & amp; ammeter and all accessories as per direction of EIC at site - 1 job | — | — | — | 7,42,558.76 | |
| — | 2.00 | — | — | ||
| Supply. Installation, testing and commissioning of outdoor MS cubical type LT feeder pillar box of suitable size and suitable for 415 V, 50 Hz AC supply made out of CRCA sheet not less than 14 SWG. The panel shall be totally enclosed, dust and vermin proof, neoprene gasket of thickness not less than 2 mm shall be used between all adjacent units and beneath all covers so that the joints are effectively dust vermin proof. The busbar chamber shall have three phase & neutral copper busbar of same ratings. The drawing of panel board should be approved by the competent authority before fabrication and commissioning. The panel shall be painted with two coats of primer & two coats of exterior coating by spray painting and shall consists of (i) 125A, 4P, 36kA, Ics=100%Icu, Adjustable over load Setting & Short circuit setting, MCCB - 1 Nos.(ii) 63A, 4P, 36kA, Ics=100%Icu, Adjustable over load Setting & Short circuit setting, MCCB - 4 Nos. (iii) 40A, TPN, 'C' Series, MCB - 1 Nos. (iv) Fabrication of Panel board with 14SWG CRCA sheet including CC foundation and 200A TPN Copper busbar, cable alley, C C Foundation etc and all accessories - 1 job | — | — | — | 1,39,695.02 | |
| — | 700.00 | — | — | ||
| Supply, installation, testing & commissioning of 120 Sqmm, 1100-volt grade, single core XLPE insulated and PVC sheathed Aluminium multistrand armoured cable | — | — | — | 3,45,100 | |
| — | 10.00 | — | — | ||
| Supply and erection of earthing by made of B class GI pipe of 3000 mm length, 50 mm diameter & 3.6 mm thickness.The GI Strip ( should be welded with the earth pipe. The pipe is provided with a tapered casing at the lower end in order to facilitate the driving. A funnel with perforated plate to be provided at the top of the pipe for pouring water during dry season to have an effective earth value.The connecting conductor from earth electrode tothe distribution panel board should not be thinner than 8 SWG GI wire to carry the fault current. The earth fill shall be of homogeneous layer of common earth soil. Where soil restivity is high, earth restivity enhancing material may be used, Bentonite or similar earth enhancing material may be used in rocky soil. Earth box to be precasted RCC andThe values of earth resistance measured should be painted on the Earth pit cover/lid along with the date of measurement. As per Drg. No. DRG NO:PCEE/ELG/DRG/2024/1 dated 30.09.2024 & as perTechnical circular no. EL/PS/2024/1 (EARTHING SYSTEM). | — | — | — | 16,865 | |
| — | 500.00 | — | — | ||
| Supply, installation, testing & commissioning of 50Sqmm, 1100-volt-grade, 4-core XLPE insulated and PVC sheathed Copper multistrand armoured cable conforming to IS 1554(PART - I) & IS 7098(PART - I) with latest amendment | — | — | — | 3,79,815 | |
| — | 4.00 | — | — | ||
| Supply. Installation, testing and commissioning of outdoor MS cubical type floor mounted double door LT panel board of suitable size andsuitable for 415 V, 50 Hz AC supply made outof CRCA sheet not less than 14 SWG. Thepanel shall be totally enclosed, dust andvermin proof, neoprene gasket of thickness not less than 2 mm shall be used between alladjacent units and beneath all covers so thatthe joints are effectively dust vermin proof. Thebusbar chamber shall have three phase &neutral copper busbar of same ratings. Thedrawing of panel board should be approved bythe competent authority before fabrication andcommissioning. The panel shall be painted withtwo coats of primer & two coats of exteriorcoating by spray painting and shall consists ofthe following: (i) 250A, 4P, 50kA,Ics=100%Icu, Adjustable over load Setting &Short circuit setting, MCCB - 1 No.(ii) 125A, 4P,36kA, Ics=100%Icu, Adjustable over loadSetting & Short circuit setting, MCCB - 4 Nos.(iii) 63A, 4P, 36kA, Ics=100%Icu, Adjustableover load Setting & Short circuit setting, MCCB- 1 Nos.(iv) 3 Phase Digital Ammeter - 1 No.(v)3 Phase Digital Voltmeter - 1 No.(vi) LEDIndicator R/Y/B - 3 Nos.(vii) Fabrication ofPanel board with 14SWG CRCA sheet includingCC foundation and 300A TPN Copper busbar),cable alley, C C Foundation etc and allaccessories. | — | — | — | 4,68,533.88 | |
| — | 20.00 | — | — | ||
| Supply installation, testing and commissioning of 18/20 watt indoor light. | — | — | — | 6,582.2 | |
| — | 12.00 | — | — | ||
| Supply installation, testing and commissioning of industrial fan. | — | — | — | 61,281.6 | |
| — | 30.00 | — | — | ||
| Supply, installation, testing & commissioning of 36-watt 240V AC tunnel light. | — | — | — | 2,35,200 | |
| — | 40.00 | — | — | ||
| Supply, installation, testing & commissioning of 80-watt high bay light. | — | — | — | 5,24,800 | |
| — | 10.00 | — | — | ||
| Supply, installation, testing &commissioning of 63A(3P+N+E), IP 67 industrial socket (Hensel Cat No. AS169 TS) as per direction ofEIC at site. | — | — | — | 96,766.4 | |
| — | 10.00 | — | — | ||
| Supply, installation, testing & commissioning of industrial Single phase three pin 240V AC socket 415V AC. | — | — | — | 55,836.9 | |
| — | 4.00 | — | — | ||
| Supply, installation, testing & commissioning of VTPN distribution box having 1. 200A TPN - 01 Nos. 2. 63A TPN -04 Nos. 3. 40A DP- 08 Nos. | — | — | — | 5,00,028 | |
| — | 500.00 | — | — | ||
| Supply, installation, testing & commissioning of 25 Sqmm, 1100-volt grade, single core XLPE insulated and PVC sheathed Aluminium multistrand armoured cable. | — | — | — | 97,055 | |
| — | 1000.00 | — | — | ||
| Supply, installation, testing & commissioning of Hot Dip galvanised with suitable size as per site requrement having thickness not less than 1.6 mm cable tray with cover & hardware for fittings Cable tray suitable of cable size. | — | — | — | 7,25,780 | |
| — | 1000.00 | — | — | ||
| Laying of above LT XLPE insulated armoured aluminium cables as per instruction of site engineer . | — | — | — | 12,910 | |
| — | 1000.00 | — | — | ||
| Excavation of trench of size 60 Cm width x 90 Cm depth for laying of CI pipe/cable with sand/brick/clamp protection as required and filling of earth / ramming as required as per direction of EIC at site. | — | — | — | 1,19,000 | |
| — | 400.00 | — | — | ||
| Horizontal machine borring under track crossing at a depth of 2.0 mtr below GL including required size HDPE pipe observing all necessary safety for human life and others movement as per direction of engineer at site. | — | — | — | 21,22,600 | |
| — | 1000.00 | — | — | ||
| Supply and laying of HDPE pipe 50 mm dia to withstand 8.0 Kg/sq mm pressure confirming to IS:4984/2016 (complete with necessary jointing of pipes as per standard procedure) as per direction of EIC at site. | — | — | — | 1,83,990 | |
| — | 750.00 | — | — | ||
| Supply and laying of HDPE pipe 110 mm dia towithstand 8.0 Kg/sq mm pressure confirmingto IS:4984/2016 (complete with necessaryjointing of pipes as per standard procedure) as per direction of EIC at site. | — | — | — | 2,05,170 | |
| — | 60.00 | — | — | ||
| Wiring of light point by PVC insulated unsheathed and stranded Copper Cable 2.5 sq.mm S/C confirming to IS - 694 through PVC Casingcaping/ conduit pipe/Cable tray suitable size including flash type 6 A controlling switch on PVC board with all accessories and ceiling rose /holder.etc. as required. | — | — | — | 15,123 | |
| — | 25.00 | — | — | ||
| Wiring of fan point by PVC insulated unsheathed and stranded Copper Cable 2.5 sq.mm S/C confirming to IS - 694 through PVC Casingcaping/ conduit pipe/Cable tray suitable size including flash type 6 A controlling switch on PVC board with all accessories and ceiling rose /holder.etc. as required. | — | — | — | 13,606.5 | |
| — | 25.00 | — | — | ||
| Supply, installation, wiring & commissioning of 16A SS type combined power point. | — | — | — | 15,025.25 | |
| — | 3.00 | — | — | ||
| Supply, installation, testing & commissioning of 8 way double door metal SPN DB consisting 40A, MCB DP- 1 no, 25A MCB DP- 1 nos & 10A MCB SP- 4 no as per direction of EIC at site. | — | — | — | 29,076 | |
| — | 1.00 | — | — | ||
| Supply, installation, testing & commissioning of 8 way double door metal TPN DB consisting 63A, MCB TPN - 1 no, 40A, MCB DP- 2 nos, 25A MCB DP- 1 nos & 10A MCB SP- 2 nos as per direction of EIC at site. | — | — | — | 14,266 | |
| — | 200.00 | — | — | ||
| Supply & Wiring of point wiring/Main Line/Submain Line / single core copper conductor 1.0 sqmm | — | — | — | 2,712 | |
| — | 500.00 | — | — | ||
| Supply & Wiring of point wiring/Main Line/Submain Line / single core copper conductor 2.5 sqmm. | — | — | — | 16,795 | |
| — | 500.00 | — | — | ||
| Supply & Wiring of point wiring/Main Line/Submain Line / single core copper conductor 4.0 sqmm. | — | — | — | 24,770 | |
| — | 500.00 | — | — | ||
| Supply & Wiring of point wiring/Main Line/Submain Line / single core copper conductor 6.0 sqmm. | — | — | — | 37,265 | |
| — | 500.00 | — | — | ||
| Supply & Wiring of point wiring/Main Line/Submain Line / single core copper conductor 10.0 sqmm. | — | — | — | 70,000 | |
| — | 1000.00 | — | — | ||
| Supply , testing and handing over of HT,11000 volt grade, 240 sq mm 1 core XLPE insulated, Insulation Screening with Extruded Semi Conducting Compound in Combination with Copper Tape, AL Round Wire Armoured, and Overall PVC Sheathed Cable heavy duty power cables aluminium armoured cable as per IS:7098(PART 2) 2011 with up to date amendments including all as per site requirement. | — | — | — | 16,17,910 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
Annexure_1.pdf
ATTACHMENT
GCCUpdateduptoACS-11_1.pdf
ATTACHMENT
ACS-8_2.pdf
ATTACHMENT
ACS-09.pdf
ATTACHMENT
ACS-10.pdf
ATTACHMENT
GCCACS11.pdf
ATTACHMENT
TechCircularwithDrgforEarthingandCableLayingUG.pdf
ATTACHMENT
JPO8.5.24-CablediggingworksNFR.pdf
ATTACHMENT
TD-022026-27_1.pdf
ATTACHMENT
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .