Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹19.3 LAccepted-AOC | L1 | Accepted-AOC AOC | |
| 2 | L2₹21.7 L+₹44,900 (2.11%)Rejected-Finance 306 SHIV BARI MARG PANCHVATI NAGAR BATHINDA 151001 PB | BATHINDA | BATHINDA | PUNJAB | 151001 | L2 | Rejected-Finance Other than L1 |
Tender Value
Refer Docs
EMD Value
₹40,000
Closing Date
16 Dec 2022, 6:00 pmClosed
GE (AF) BHISIANA
GE (AF) BHISIANA PIN-151201
AS PER BOQ/PRICE SCHEDULE
2022_MES_563952_1
GE/BHI/T-48/2022-23
Open Tender
Civil Works
Item Rate
273 days
GE (AF) BHISIANA
AS PER NIT/TENDER DOCUMENT
6 documents required · 6 mandatory
₹500
GE (AF) BHISIANA
₹40,000
Yes
23 Jan 2023
18 Nov 2022
19 Dec 2022
18 Nov 2022
16 Dec 2022
2 Dec 2022
23 Nov 2022 - 28 Nov 2022
Amount
Material & labour for earthing in replacement with Galvanised Steel earth plate electrode 60cm x 60cm x 6mm thick buried directly in ground vertically at a depth not less than 2.25metre below normal ground level with top edge of earth plate at a depth not less than 1.5 metre below normal ground level, earth plate surrounded from all sides by 15cm thick packed layer of charcoal dust and common salt filling in alternate layers and electrode connections by using Galvanised Iron strip of 32 x 6 mm as earthing lead (upto the body of the equipment) by means of bolts, nuts, check nuts and washers made of galvanised iron and thimbles and protected by light grade 40mm dia GI pipe connected up to main LT Panel /Test point and GI pipe medium grade 20mm bore for watering and including funnel , wire mesh , RCC pit cover and PCC chamber pit with PCC (1:3:6) type C-2 using 40mm graded stone aggregate, including demolition of unsv earthing, excavation and earth work in any type of soil , returning , filling in approved soil and disposal of surplus soil to a distance not exceeding 50m all as specified and shown in electrical plate No 3 of SSR 2020(Part-I) complete all as specified and directed.
Material & labour for earthing in replacement with Galvanised Steel earth plate electrode 60cm x 60cm x 6mm thick buried directly in ground vertically at a depth not less than 2.25metre below normal ground level with top edge of earth plate at a depth not less than 1.5 metre below normal ground level, earth plate surrounded from all sides by 15cm thick packed layer of charcoal dust and common salt filling in alternate layers and electrode connections by using Galvanised earth lead wire 4.0 mm as earthing lead (upto the body of the equipment) by means of bolts, nuts, check nuts and washers made of galvanised iron and thimbles and protected by light grade 40mm dia GI pipe connected up to main LT Panel /Test point and GI pipe medium grade 20mm bore for watering and including funnel , wire mesh , RCC pit cover and PCC chamber pit with PCC (1:3:6) type C-2 using 40mm graded stone aggregate, including demolition of old earthing, excavation and earth work in any type of soil , returning , filling in approved soil and disposal of surplus soil to a distance not exceeding 50m all as specified and shown in electrical plate No 3 of SSR 2020(Part-I) complete all as specified and directed.
S&F Earth continuity conductor or main earthing lead in replacement fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 25x4mm galvanised iron strip as earthing lead with saddles and fixing screws etc. complete all as specified & directed
S&F Earth continuity conductor or main earthing lead in replacement fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 32x6 mm galvanised iron strip as earthing lead with saddles and fixing screws etc.complete all as specified & directed
S&F of copper strip of size 20 x 3 mm on PVC/porcelain insulator in replacement at suitable distance with saddeles and fixing screw etc for roof/Wall conductors and down conductors above ground all joints of copper strip should be brazed properly complete all as specified and directed.
S&F of copper strip of size 32x6 mm on PVC/porcelain insulator in replacement at suitable distance with saddeles and fixing screw etc for roof/Wall conductors and down conductors above ground all joints of copper strip should be brazed properly complete all as specified and directed.
S&F Earth continuity conductor or main earthing lead in replacement fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 4mm galvanised iron wire as earthing lead with saddles and fixing screws etc. complete all as specified & directed
S&F air termination single pointed copper rod 12mm dia 300mm long in replacement complete all as specified and directed.
S&F air termination single pointed aluminium rod 12mm dia 300mm long in replacement complete all as specified and directed.
S&F test point terminal block made of of gun metal or phosphorus bronze size 75x75x25mm in replacement drilled and screwed inlcuding 3 Nos 8 mm dia 25 mm long hexagonal head screw complete all as specified and directed.
M&L for copper brazing for copper strips of various sizes laying on wall /roof etc with the help welding machine and skilled tradesmen by using welding rod etc by taking safety precautions during brazing as directed by the AGE EM / users complete all as specified and as directed by Engr in Charge
M&L for brazing for GI strips of various sizes laying on wall /roof etc with the help welding machine and skilled tradesmen by using welding rod etc by taking safety precaustions during brazing as directed by the AGE E/M / users complete all as specified and as directed by Engr in Charge
M&L for fixing the porcelin cleat with the help of nut,bolts clamps etc to fix the strips of various size and types to separate from ground and wall as directed at site by Engr in charge complete all as specified
M&L for PVC conduit heavy duty of 40 mm dia size for the protection of the earthing strip on wall/roof with the help nuts ,bolts clamps, PCC work etc as directed at site by Engr in charge
Supply only salt using for earthing pits as directed at site by Engr- in -Charge.
Supply only charcoal using for earthing pits as directed at site by Engr -in- Charge. Note For Ser Item No 15&16 (a) Contractor shall submit Purchase Voucher and Receipt Voucher alongwith RAR/Bill while Claiming payment.
M&L for concrete block of size 15cm x15cmx15cm by using 1:2:4 cement concrete for fixing of strips any type /size with the help of insulator to separate the strip from ground .Block will be 5cm below the ground level 10 cm above ground level including necssary work regarding the fixing of block complete all as specified and directed by Engr in Charge Note : Insulator shall be measured and paid under separately
M&L in replacement for Eco friendly earth enhancing compound for enhancing the earthing value of chemical earthing including necessary earth work deemed inclusive in the quoated rates complete all as specified and directed at site .
M&L in replacement for copper bounded earth rod of 10 feet length 17.2mm dia made of high tensile low carbon steel rod for replacement in existing chemical earthing including necessary earth work deemed inclusive in the quoated rates complete all as specified and directed by Engr in charge
M&L in replacement for FRP earth pit cover of top size lockable Lid in replacement of broken Cover including necessary earth work deemed inclusive in the quoated rates complete all asspecified and directed by Engr in Charge
M&L in replacement of sodium based bentonite powder to enhancement materials including necessary earth work complete all as specified and directed by Engr in Charge
M&L for Removing normal earthing and M&L for commissioning, installation and testing of maintenance free UL approved copper bonded earth rod of 10 feet length, 17.2 mm dia. made of high tensile low carbon steel rod , molecularly bonded with 99.9% electrolytic grade copper on outer surface ( minimum copper bonding thickness - 250 microns) with exothermally jointed copper bus bar of 50 X 6 X 200 mm for connection. The rod and exothermic joint together successfully tested at 25 KA fault current by CPRI with 50 Kg eco friendly earth enhancing compound with each earth rod. The earth pit should be 125 mm dia. the compound should comply to IEC:62561-7 having passed leaching, corrossion, sulphur and resistivity test as per IEC: 62651-7 by NABL accredit Lab with FRP earth pit cover of top size lockable Lid. It includes GI Protection pipe light grade of size 40 mm dia. with GI strip of size 32X6 mm upto test point complete all as specified and directed by Engr-in-charge. Make JMV LPS Ltd/ OBO/ENNOV Infra solutions Pvt. Ltd/ erico /powerbolt including connecting of Strip between two earthing complete all as specified and directed by Engr in charge. Note: (a) The test result of each set of earthing is less than 1 Ohm. All earthing test will be carried out in presence of MES Rep, manufacturer Rep and test result will be recorded in a register with sign of manufacturer & Engr-in-charge. (b) Earth enhancing compound (PROCEM) ECS GB 25 tested as per IEC 62561-7-25Kg. (c) Chemical earthing will be installed by manufacturer Rep and purchase voucher of earthing will be produced before payment. Payment shall be made only after getting satisfactory result.
M/s Luxmi Constructions
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .