Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹9.7 LAccepted-AOC UC I USHA PARK HARI NAGAR NEW DELHI 64 | NEW DELHI | DELHI | 110001 | L1 | Accepted-AOC work order has been awarded | |
| 2 | L2₹9.7 L+₹116.04 (0.01%)Rejected-Finance A 111 JHILMIL COLONY EAST DELHI 110095 | SHAHDARA | DELHI | 110095 | L2 | Rejected-Finance Not L1 |
Tender Value
₹9.5 L
EMD Value
₹19,003
Closing Date
18 Dec 2023, 1:00 pmClosed
EEE-I/SSZ
Room No.5 First Floor Vishwakarma Nagar Near Hanuman MandirJhilmil Colony Delhi-110095
Renovation of Electrical Installation and Fans along with Installation of Semi High Mast Light Pole at Hardyal Singh Library in Mayur Vihar Phase-II in Ward No.196 under Shahdara South Zone.
2023_MCD_177362_1
EEE-I/SSZ/2023-24/19.3
Open Tender
Electrical Works
Item Rate
60 days
work
Please refer to tender documents
4 documents required · 4 mandatory
₹590
₹19,003
29 Jan 2025
11 Dec 2023
19 Dec 2023
11 Dec 2023
18 Dec 2023
11 Dec 2023
Amount
OD17036/2023-2024:DSR 1.10.3 Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with piano type switch, phenolic laminated sheet, suitable size M.S. box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required. Group C
OD17037/2023-2024:DSR 22 1.11 Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.
OD17038/2023-2024:DSR 1.12 Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit alongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required.
OD17039/2023-2024:DSR 1.14.2 Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
OD17040/2023-2024:DSR 22 (1.15.3) Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable and 1.5 sq.mm FRLS PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel/PVC conduit including dismantling as required.Group C
OD17041/2023-2024:(1.17.12) Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. 3x2.5 sq.mm.
OD17042/2023-2024:DSR 22 (1.17.21) Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. 3*4 sq.mm.
OD17043/2023-2024:(19.1) Supply, installation, Testing and commissioning of 1200mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Currect (BLDC) Motor, class of insulation:B, 3 nos blades, 30 cm down rod, 2 nos. canopies, shackle kit, safety ropr, copper winding, power factor not less than 0.9, service value (CMM/W) minimum 6.00, Air delivery minimum 210 CMM, 350 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C(max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, Earthng etc. complete as required.
OD17044/2023-2024:(2.12.2) Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. 63 Amps
OD17045/2023-2024:(2.12.1) Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40 Amps
OD17046/2023-2024:(2.10.1) Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. (Single Pole)
OD17047/2023-2024:(1.23.1)Supplying and fixing following piano type switch/ socket on the existing switch box/ cover including connections etc. as required.5/6 amps switch
OD17048/2023-2024:DSR 2022 (14.15.1) Supplying and laying of following size DWC HDPE pipe lSI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.in the existing trench complete as required.63 mm dia (OD-63 mm & ID-51 mm nominal)
OD17049/2023-2024:DSR 2022 7.6.1 Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required.Upto 35 sq. mm
OD17050/2023-2024:DSR 2022 7.5.1 Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.Upto 35 sq. mm.
OD17051/2023-2024:Providing and laying earth connection from earth electrode with 6 SWG dia G.I. Wire in 15 mm dia G.I. pipe from earth electrode including connection with G.I. thimble excavation and re-filling as required.
OD17052/2023-2024:Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. (but without charcoal/ coke and salt ) as required.
OD17053/2023-2024:1.50.1 Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required. Upto 450 mm sweep.
OD17054/2023-2024:2.3.2 Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 8 way double door
OD17055/2023-2024:2.2.1 Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. 100 A, 16 KA,TPMCCB
OD17056/2023-2024:1.57 Supplying & fixing suitable size GI box wih modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, "C" curve including connections, painting etc. as required
OD17057/2023-2024:1.32 Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required.
OD17058/2023-2024:1.24.4 Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. 5/6 A socket.
OD17059/2023-2024:1.24.1 Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. 5/6 A switch.
122.1.47:Supply of 250 mm (10 inch) sweep 1250 rpm exhaust fan Fresh Air Type complete with shutter blades etc. as required.
122.2.19:Fabrication,Supplying,Installation,testing,Commissioning of 12 mtr high mast System with its accessories ,Mast shaft shall be in one section , hot dip galvanized 4mm thick(Single dip ) inside & out sides &suitable for wind velocity as per IS 875 part3 .There shall be in longitudinal seam weld per section and No circumferential weld. It should also included accessories For High Mast head frame ,2 point suspension system, 5*2.5 sqmm Cu conductor with steel wire rope 5mm dia. (7/19construction) single drum winch ,galvanized lantern carriage arrangement suitable for 4/6 Nos. Flood Light luminaries symmetrically And its control gears boxes and lighting finial ,the mast shall have integral type manual tool mounted at the base compartment of its raising and lowering operation with foundation bolts and Anchor plate and control panel housing suitable RCC (1:2:4) shallow foundation of size 1m(L) x 1m wide and 2m deep i/c excavation of earth, providing cutting, bending and placing in position, reinforcement of cold twisted bars of 12 mm dia -2100mm long (approx.) - 16 nos.and reinforcement of cold twisted bar of 8 mm dia - 3700 mm (approx.) - 13 nos. (with 150 mm spacing) as required with positioning of foundation bolts and providing DWC HDPE pipe for cable entry & exit as required for the high mast considering The safe soil bearing capacity at site as 10T/sqm at 2mts. Depth with all material i/c 4Nos S.P MCB,63Amp.DPIsolator etc as reqd. Logo/Name of manufacturer shall be embossed on the pole. Galvanization as per relevant IS.
122.2.25:Providing and fixing of Stainless steel name plate of size 6×8 sq inch made of 20 gauge sheet including engraved name of area representative duly painted along with SS clamp nut bolt etc as required
122.2.27:SITC of 30W LED Flood Light luminaire fitted with lens, made of pressure die cast aluminium housing & toughened glass cover complete with the following specification as reqd with IP 66 protection (a) Total system wattage =30 watt +/- 5% (b) Luminaire Efficacy>=100 Lm/w (c) Power Factor>=0.95 (d) Protection Class- IP-66
122.2.30.a:SITC of 150W LED Flood Light luminaire fitted with lens, made of pressure die cast aluminium housing & toughened glass cover complete with the following specification as reqd with IP 66 protection (a) Total system wattage =150 watt +/- 5% (b) Luminaire Efficacy>=100 Lm/w (c) Power Factor>=0.95 (d) Protection Class- IP-66
122.2.38:S/I/T/C of Surface mounting CRCA housing 36W LED luminaire with acrylic cover diffuser with following specifications including fixing on existing wall/recess with connections as reqd. (a)Total system wattage = 36 watt +/- 5% (b )Luminous efficacy >=95 lumens /watt. (c)Power factor >=0.95
122.2.39:S/I/T/C of LED Tube type luminaire 20 Watt rating complete with polycarbonate housing batten integrated electronic driver prewired with high efficient LEDs with the following:(a) Total system wattage 20 watt +/- 5%(b )Luminous efficacy lumens/watt >=95 (c)Power Factor >=0.95
122.2.84:Supplying and fixing of full stainless steel body self-contained drinking water cooler with cooling capacity 150ltr per hr, storage capacity 150ltr and suitable for 230V supply as required.
122.2.114:S/I/T/C of stand for split AC
122.2.115:S/I/T/C of 4 KVA Voltage Stabilizer having input voltage 150V-270V and output voltage 195-245V
122.2.117:S/I/T/C of copper pipe for split AC
122.2.118:S/I/T/C of Drain Pipe
122.2.131:Supply, Installation, Testing and Commissioning of 1.5 Ton, 5 Star rated Inverter Split air conditioner with rotary compressor (R32 Refrigerant) having copper condenser complete with outdoor unit as required.
122.2.175:Supply & Installation of wall mounted RO plus UV plus UF water purifier with up to 20 L/hr purification capacity and storage tank up to 09 liter capacity.
122.2.188:S/I/T/C of LED Tube type luminaire 2X20 watt rating box type complete with extruded Al. batten prewired with high efficient LEDs with the following: (A) Total system wattage 40 watt+/- 5% (B) Luminous efficacy lumens/ watt >=95 (C) Power Factor >=0.95.
122.2.242:SITC of window type Air conditioner fitted with rotary compressor of 1.5 Ton capacity, BEE 5 star rating complete as required.
122.1.2:Supply of XLPE insulated PVC sheathed Al. Conductor Armoured Cable 1.1KV grade conforming to IS-7098 of following size:-2C*6 sqmm
OD17061/2023-2024:supply and fabrication of pole protection system made up of 8SWG steel wire mesh of size 25mmX75mm rectangular with 50mmX50mmX6mm MS angle iron for supporting the mesh including MV danger plate and grounding the protection system in suitable quality of CC etc as required
122.2.126:SITC of wall mounted fan 400mm sweep rated voltage 220-230 AC rated frequency 50HZ speed 1280-1350 RPM with desired color
M/S. A.K. Electricals
Bidder Name
M/S. A.K. Electricals
SRI BALAJI ELECTRICALS
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .