Executive Engineer
Executive Engineer Elect. Division PWD B and R Br., Hisar-125001
CONSTRUCTION OF ADMINISTRATIVE BLOCK CIVIL COMPLEX AT BARWALA IN DISTT. HISAR (PDG. FIRE ALARM AND PUBLIC ADDRESS SYSTEM ONLY)
2020_HRY_140030_1
PWD/Elect-GGN/Elect-HSR/100032
Open Tender
Electrical Works
Works
60 days
Hisar
Please refer Tender documents.
2 documents required · 2 mandatory
₹1,000
Yes
Executive Engineer Elect. Division PWD B and R
₹17,800
24 Feb 2021
19 Aug 2020
3 Sept 2020
19 Aug 2020
2 Sept 2020
19 Aug 2020
Amount
S/E of PVC unsheathed copper conductor cable single core 1100 volts grad in pipe of suitable size excluding cost and erection of pipe. (HSR 31.40) Cable size 1.5 sqm(3/0.81 mm)
S/E of PVC conduit pipe ISI marked (Medium) recessed in wall/ ceiling etc. including cost of PVC bends, inspection box and all other material required to complete the job in all respect up to the entire satisfaction of Engineer-in-Charge of the work. (HSR 31.44) b) 25mm dia
SITC of Micro processor based 2 wire fault tolerant, networkable type Fire Alarm / Detection Control Panel (having nos. of loops to suit minimum 20% extra over the nos. of fire detectors. The panel shall be able to give location of all fire / fault conditions of addressable units via the address codes. Further, the panel must be able to automatically switch ON/OFF respective control module when ever any alarm is triggered. The panel shall have rectifier, loop cards, minimum 160 characters LCD unit/ 5.7’’TFT to indicate Fire / Fault Signal with address and analog output, external/inbuilt printer to log all fire or fault events complete in all respects. The Panel Shall be sheet Steel power coated, sealed to IP30. The Panel shall have 20 Zones with individual LED Indicators, expandable to 80 LED Indicators. The Panel shall have 3 Serial Ports. The pane\l shall have a built in power supply and battery charger along with maintenance free 24 AH,2 x 12 volt SMF lead acid batteries capable of running for a minimum of 24 hours with battery charger complete as required. And conforming to BS5839 standards and Duly Approved by EN 54/UL/VDS/ as per specifications complete in all respect up to the entire satisfaction of Engineer-in –charge of work. Make: Bosch FPA 1000 / Cerberus by siements/ Edwards EST3/Honeywell Morley Zxe series.
SITC of addressable multisensor detector with a combination of Optical and Thermal including mounting base, auto addressing feauture as required. Detetctor should have 2 as per NFPA 72 style 7 wiring requirements (one for incoming and one for outgoing line) for maintaining operational availability of all elements in the loop in the event of a short circuit and to meet style 7 requirements. High resistance to electromagnetic effects in accordance with EFSG agreement EFSG/F/97/005 .Detector should monitor Electromagnetic interference and report to the panel - current and average values. EMC safety for detector shall be 50 V/m. Shall be EN54/ VDs/UL certification. (Detectors without Inbuilt Isolators may be considered with an additional Isolator Module after 20 devices) (Makes: Bosch FAP-440-T+FAA-440, Siemens Cerberus OH921+DB-11, Honeywell Morley MI-PTSE+B501, Edwards SIGA PHD + SIGA )
SITC ofaddressable Heat detector with fixed and rate of raise feature including mounting base with LED… etc. complete as required. Each Detector should have 2 as per NFPA 72 style 7 wiring requirements (one for incoming and one for outgoing line) for maintaining operational availability of all elements in the loop in the event of a short circuit and to meet style 7 requirements. High resistance to electromagnetic effects in accordance with EFSG agreement EFSG/F/97/005 .Detector should monitor Electromagnetic interference and report to the panel - current and average values. EMC safety for detector shall be 50 V/m. Shall be EN54/ VDs/UL certification. (Detectors without Inbuilt Isolators may be considered with an additional Isolator Module per detector) (Makes: Bosch FAH-440 + FAA-440 , Siemens Cerberus HI921+DB-11, Honeywell Morley MI-RHSE+B501 , Edwards SIGA DHI + SIGA )
SITC of intelligent analog addressable type Manual Call point having surface or flush mounting option fully compliant to EN54 having rotary decade switches for addressing with back box for mounting as required conforming to BS5839 standards and duly approved by EN54/UL/VDS required to complete the job in all respect upto the entire satisfaction of Engineer-in-Chage of the work. Make Siemens cerberus/ Morely/ Edwards
SITC of addressable Loop powered hooter with strobe complete with mounting base as required conforming to BS5839 standards and duly approved by EN54/UL/VDS required complete the of in all respect upto the entire satisfaction of Engineer - in - charge of work. Make: Bosch/ Morley/ Siemens Cerberus/ Edward
SITC of Glow Type EXIT Sign Board photo luminescent of size 300 mm x 250 mm x 1.5 mm rigid sheet signage containing Zink sulphate as bare chemical class 1 material PSPA fixed on 3mm acrylic sheet on both side showing marking (running man, Arrow and Exit) and hanged with the ceiling with chain and fastener including cost of labour & material required to complete the job in all respect up to the entire satisfaction of Engineer-in-Charge of work. (Make: Glolite / Pearl / PES)
SITC of minimum 1000 Mtr. Range Kheraj / National make SIRON generator provided at the roof of the building with separate Power Supply, relay etc. complete the in all respect up to the entire satisfaction of Engineer-in-Charge of work.
SITC of 9 U rack for switch Mounting with Fan and power Strip, PDU, Hardware Mounting Kit Make: Netrack/Comrack/Vall Rack/ APW.
SITC of Analog Addressable type Active Repeater fire alarm panel with Backlit LCD Display, having controls for reset, mute, Accept, Silence alarms and self test conforming to BS5839 standards and Duly approved by EN54/UN54/VDS with all labour and material required to complete the job in all respect up to the entire satisfaction of Engineer – in Charge of work.(Makes: BOSCH FMR 5000-13, Siemens Fire Finder SSDC, Honeywell Morley , Edwards 3-LCD ANN
Supply & Erection of Fire extinguisher all as Per IS 15683 duly hanged on the wall with necessary hooks to complete the job in all respect upto entire satisfaction of engineer incharge of work . Make: Safex / Minimax / cease fire) ABC Dry power type fire Extinguishers of 5 kg. capacity
Co2 type fire extinguishers of 4 Kg capacity
SITC of fault isolator/base to check short circuit every 20 Deductors
SITC of 6 watt speaker wall mount / ceiling (Bosch / Honeywell/ Henrich )
SITC of 2 core multistrand 1.5 sq mm annealed copper conductor speaker cable in existing pipe/ channel I/C connection etc.Make Finolex/Polycab/ Havell's
SITC of 2 KVA UPS with 2 hour backup on line with Suitables AH batteries. Make: Microtek / Luminous / APC / Elnova )
Vowels Technology and Services
INDIAN SECURITY AND FIRE SAFETY
stage.html
html • 0.05 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .