Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Tender Value
₹3.6 Cr
EMD Value
₹7.1 L
Closing Date
10 Feb 2025, 5:30 amClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Facilities Management Division, Bangalore
HINDUSTAN AERONAUTICS LIMITED Facilities Management Division, Bangalore
Proposed Construction of Training Centre at Second Floor of Design Building at RWRDC, HAL HC.
18178
TENDER NOTICE/NCP/42/24-25/03
Works
Contract Section Civil-FMD-Bangalore
₹0
₹7.1 L
10 Feb 2025
13 Dec 2024
13 Dec 2024
10 Feb 2025
HINDUSTAN AERONAUTICS LIMITED BANGALORE FACILITIES MANAGEMENT DIVISION
NAME OF THE WORK: Proposed Construction of Training Centre at Second Floor of Design Building at RWRDC, HAL [HC]. CONTRACT NO. HAL/FMD/R-93/24-25
Name of the Contractor :
Sl. No. Specification Quantity Unit Rate in Figs [Excluding GST] Rate in Words Amount
Preamble: (1) The subject work has been called on works contract basis and prevailing GST for same is 18%. Any change in GST +/- during the currency of contract shall be on HAL account. The Tenderer shall abide by prevailing GST act. (2) L1 (lowest quote) will be determined based on the total quoted amount including GST. (3) This BOQ specification has to be read in conjunction with relevant CPWD specifications amended upto date/ detailed technical specification in tender document and tender drawings if any.
Part 'I' - Civil Works
1 Disposal of moorum / building rubbish / malba / similar unserviceable, dismantled or waste material of partitions, ceiling boards, tiles, frames, etc., by mechanical transport including loading, transporting, unloading in all lifts/loads upt 10 km distance from HAL, etc., all complete as directed by Engineer-in-Charge. 98.00 Cu m 0.00
2 Providing and laying cement concrete in retaining walls, return walls, walls (any thickness) including attached pilasters, columns, piers, abutments, pillars, posts, struts, buttresses, string or lacing courses, parapets, coping, bed blocks, anchor blocks, plain window sills, fillets, sunken floor, etc., above plinth level excluding the cost of centering, shuttering and finishing:1:2:4 (1 Cement : 2 coarse sand (zone-III) derived from natural sources : 4 graded stone aggregate 20mm nominal sizederived from natural sources), etc., all complete as directed by Engineer-in-Charge. 42.00 Cu m 0.00
3 Providing and laying in position ready mixed or site batched design mix cement Concrete of M25 grade with minimum cement content of 330 kg /cum for reinforced cement concrete work like, footing, pedestal, columns, beams, lintles, chajjas / canopies, staircases, sills, fins, shelves, flooring, stage, etc., using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland / Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads, etc., all complete as directed by Engineer-in-Charge. Note: 1. Form work and reinforcement steel will be paid separately. 202.00 Cu m 0.00
4 Formwork for Lintel Beams, window sills, etc., by providing timber, wooden planks, runners / M.S. sheets with all supports, struts, braces, wedges, scaffolds, bracings, ladders, gangways, dressing with oil including M.S. bolts nuts and washers, temporary openings, filleting for a stop, chamfered edges, internal / external splayed, rounded angles or grooves for forming throating including making temporary openings in the forms for pouring concrete etc as per drawing., etc., all complete as directed by the Engineer-in-Charge. Note: Formwork material is contractor's own property and shall be removed after completion of work.
a) Foundations, footings, bases of columns, for mass concrete, etc., 8.00 Sq m 0.00
b) For Columns, Pillars, Piers, Abutments, Posts and Struts 332.00 Sq m 0.00
c) Lintels, beams, plinth beams, girders, bressumers and cantilevers 530.00 Sq m 0.00
d) Suspended floors, roofs, landings, balconies and access platform 614.00 Sq m 0.00
e) Vertical and horizontal fins individually or forming box louvers band, facias and eaves boards. 6.00 Sq m 0.00
5 Supplying, straightening, fabricating and fixing Steel reinforcement of HYSD TMT bars of not less than Fe 500 conforming to IS 1786 for all concrete reinforcment members / works including cutting to length, bending to shape required, including cranking, bending spirally for hooping for column, hooking ends and binding with mild steel wire (Annealed) not less than 0.90mm dia or securing with clips, including fixing and bracing, wastage, welding, supporting or otherwise holding firmly in position so that the placing and ramming of concrete will not displace it, etc., complete all as per specifications, drawings and as directed by the Engineer-in-Charge. Note :1. For measurement, the weight of steel sections, plates, reinforcement steel bars, wire fabrics etc., shall be calculated from the tables given in relevant Indian standards or actual whichever is less. Where the weight is not given in Indian standards, it shall be calculated at 7850 kg/m³. No tolerance on account of rolling margin shall be allowed on the nominal weight of steel sections etc. complete as per direction of Engineer-in-Charge. 30.00 M T 0.00
6 Providing and fixing in position 12mm thick bitumen impregnated fiber board conforming to IS: 1838, including cost of primer, sealing depth per compound Grade-A in expansion joints upto depth of 100mm per centimeter length. Both vertically and horizontally, etc., all complete as directed by Engineer-in-Charge. 41.00 R m 0.00
7 Providing and fixing aluminum fluted sheet of 200mm wide covering over expansion joints with iron screws as per site condition, etc., all complete as directed by Engineer-in-Charge. 45.00 R m 0.00
8 Providing and fixing up to floor five level precast cement concrete solid block, including hoisting and setting in position in all heights, curing, leveling, making tooting in each courses, etc., with cement mortar 1:3 (1 cement : 3 coarse sand), cost of required centering, shuttering complete: 4.7.1 1:1½:3 (1 Cement: 1½ coarse sand (zone-III) derived from natural sources : 3 graded stone aggregate 20mm nominal size derived from natural sources), etc., all complete as directed by Engineer-in-Charge. 61.01 Cu m 0.00
9 Providing and fixing Granite stone slab of with 18mm thick, area of slab not less than 0.50Sq m, like Ruby Red / Black / Cherry with gang saw cut, mirror polished, premoulded and prepolished, machine cut for kitchen platforms, vanity counters, window sills, facias and similar locations of required size, approved shade, colour and texture laid over 20mm thick base cement mortar 1:4 (1 cement : 4 coarse sand), joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edges to give high gloss finish, etc., all complete as directed by Engineer-in-Charge. 11.84 Sq m 0.00
10 Providing and fixing Ceramic glazed wall tiles (Light / dark shade) conforming to IS: 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle green, black, in skirting, risers of steps and dados, over 12mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3kg per Sq m, including pointing in white cement mixed with pigment of matching shade of any size as approved, etc., all complete as directed by Engineer-in-Charge. 18.00 Sq m 0.00
11 Providing and fixing expansion hold fasteners on C.C. / R.C.C. / Brick masonry surface backing including drilling necessary holes and the cost of bolt of Wedge expansion type, etc., all complete as directed by Engineer-in-Charge.
a) Fastener with threaded dia 6mm 10.00 Each 0.00
b) Fastener with threaded dia 10mm 25.00 Each 0.00
c) Fastener with threaded dia 12mm 25.00 Each 0.00
12 Designing, fabricating, testing, installing and fixing in position Curtain Wall system comprising of ACP & Tinted glass of approved colour and design with open grooves for linear as well as curvilinear portions of the building, for all heights and all levels etc and with structural sealant, including: (a) Structural analysis & design and preparation of shop drawings for pressure equalisation or rain screen principle as required, proper drainage of water to make it watertight including checking of all the structural and functional design. (b) Providing, fabricating and supplying and fixing panels of aluminium composite panel cladding in pan shape in metalic colour of approved shades made out of 4mm thick aluminium composite panel material consisting of 3mm thick FR grade mineral core sandwiched between two Aluminium sheets (each 0.5mm thick). The aluminium composite panel cladding sheet shall be coil coated, with Kynar 500 based PVDF / Lumiflon based fluoropolymer resin coating of approved colour and shade on face # 1 and polymer (Service) coating on face # 2 as specified using stainless steel screws, nuts, bolts, washers, cleats, weather silicone sealant, backer rods etc and also with 6mm thick high performance glass. (c) The fastening brackets of Aluminium alloy 6005 T5 / MS with Hot Dip Galvanised with serrations and serrated washers to arrest the wind load movement, fasteners, SS 316 Pins and anchor bolts of approved make in SS 316, Nylon separators to prevent bi-metallic contacts, SS bolts with washer of different sizes for structural glazing/ACP Cladding, all complete required to perform as per specification and drawing.
The item includes cost of all material & labour component, the cost of all mock ups at site, cost of all samples of the individual components for testing in an approved laboratory, field tests on the assembled working curtain wall with aluminium composite panel cladding, cleaning and protection of the curtain wall with aluminium composite panel cladding till the handing over of the building for occupation. Base frame work for ACP cladding is payable under the relevant aluminium item. The Contractor shall provide curtain wall with aluminium composite panel cladding, having all the performance characteristics all complete, as per the Architectural drawings, as per item description, as specified, as per the approved shop drawings and as directed by the Engineer-in-Charge. However, for the purpose of payment, only the actual area on the external face of the curtain wall with Aluminum Composite Panel Cladding (including width of groove) shall be measured in sqm up to two decimal places.
a) For ACP sheet Cladding in curtain wall 75.00 Sq m 0.00
b) For Glazing in Curtail wall i.e a Spandrel Glass Panels comprising of 6mm thick heat strengthened monolithic float glass of approved colour and shade with reflective soft coating on surface # 2 of approved colour and shade so as to match the colour and shade of the IGUs in the vision panels, etc., and also having the properties as visible light transmittance (VLT) of 25 to 35 %, Light reflection internal 10 to 15%, light reflection external 10 to 20 %, shading coefficient (0.25- 0.28) and U value of 3.0 to 3.3 W/m2 K, etc., all complete for the required performances as specified, as per the Architectural drawings, as per the approved shop drawings, as specified, and as directed by the Engineer-in-Charge. 75.00 Sq m 0.00
13 Providing and fixing Second Class Teak wood for frames of doors, windows, hand rails, frame work for partitions, wall paneling in, etc., cut to shape and required curvature and preparing the surfaces to receive the polishing fixed in position with hold fast lugs / with dash fasteners of required dia & length / SS Screws at all heights, with necessary moisture content test, etc., all complete as directed by Engineer-in-Charge. 5.00 Cu m 0.00
14 Providing and fixing M.S. grills of required pattern in to openings with rawl plugs / with M.S. flats, square or round bars, etc., including priming coat with approved steel primer, etc., all complete as directed by Engineer-in-Charge. 42.00 Kgs 0.00
15 Providing and fixing 12mm thick commercial ply conforming to IS : 1328 BWR type. plain lining with necessary screws/nuts & bolts / nails, including a coat of approved primer on one face, and fixed on wooden / steel frame work / Plastered surfaces, etc., complete as per direction of Engineer-in-Charge. (Frame work shall be paid for separately) 125.00 Sq m 0.00
16 Providing & Fixing decorative high pressure 1.0mm thick laminated sheet of plain / wood grain in gloss / matt / suede finish to required pattern and combination as per the drawings, etc., on plywood with high density protective surface layer and reverse side of adhesive bonding quality conforming to IS : 2046 Type S, including cost of adhesive of approved quality / brand, etc., all complete as per direction of Engineer-in-Charge. 40.00 Sq m 0.00
17 Providing [40 x 5]mm flat iron hold fast 40cm long including fixing to frame with 10mm diameter bolts, nuts and wooden plugs and embedding in cement concrete block [30 x 10 x 15]cm 1:3:6 mix (1 cement : 3 coarse sand : 6 graded stone aggregate 20mm nominal size), etc., all complete as directed by Engineer-in-Charge. 16.00 Each 0.00
18 Providing and fixing 35mm thick flush door shutters conforming to IS :2202 (Part I) non-decorative type of approved brand / make, core of block board construction with frame of 1st class hard wood & lipping with 2nd class teak wood battens 25mm minimum depth on all edges and well matched commercial 3ply veneering with vertical grains or cross bands including ISI marked Stainless Steel butt hinges with necessary screws and face veneers on both faces of shutters and making rectangular vision panel of 0.10Sq m with 6mm thick clear heat strengthened glass, etc., all complete as directed by Engineer-in-Charge. 27.36 Sq m 0.00
19 Providing and fixing panelling 5.0mm thick glass panes (weight not less than 12.50 Ks/Sq m) or glazing in panelled or glazed shutters 25mm to 40mm thick for doors, windows and clerestory windows / ventilators (Area of opening for panel inserts excluding portion inside grooves or rebates to be measured), etc., all complete as directed by Engineer-in-Charge. 51.68 Sq m 0.00
20 Providing and fixing bright finished brass handles of 125mm size with screws, etc., all complete as directed by Engineer-in-Charge. 16.00 Each 0.00
21 Providing and fixing bright finished brass hanging type floor door stopper with necessary screws, etc., all complete as directed by Engineer-in-Charge. 9.00 Each 0.00
22 Providing and fixing bright finished brass tower bolts of [250 x 10]mm (barrel type) with necessary screws, etc., all complete as directed by Engineer-in-Charge. 16.00 Each 0.00
23 Providing and fixing bright finished brass 100 mm mortice latch and lock with min. 4levers and a pair of lever handles of approved quality with necessary screws, etc., all complete as directed by Engineer-in-Charge. 8.00 Each 0.00
24 Providing and fixing aluminium die cast body tubular type universal hydraulic door closer (having brand logo with ISI, IS : 3564, embossed on the body, door weight upto 35Kgs and door width upto 700mm), with necessary accessories and screws, etc., all complete as directed by Engineer-in-Charge. 9.00 Each 0.00
25 Providing and fixing aluminium sliding door bolts (aldrop) of [250 x 16]mm, ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868), transparent or dyed to required colour or shade, with nuts and screws, etc., all complete as directed by Engineer-in-Charge. 8.00 Each 0.00
26 Providing and fixing 20mm dia chromium plated brass curtain rod / Towel rail of 600mm long having wall thickness of 1.25mm with two chromium plated brass brackets fixed with C.P. brass screws and PVC sleeves etc., wherever necessary, etc., all complete as directed by Engineer-in-Charge. 1.00 Each 0.00
27 Providing and fixing factory made uPVC glazed /Three track three panels sliding window with two glazed and one wire meshed panel with aluminum channel for roller track, wool pile, nylon rollers with SS 304 body using comprising of lead free uPVC multi-chambered frame, sash and mullion extruded profiles duly reinforced having minimum wall thickness of 1.70mm for with minimum frame (98mm x 40mm) & both glazed and fly screen sash of mimimun (30mm x 55mm) with zinc alloy (Zamak) powder coated handle on every glazed panel along with multi-point locking system (Height upto 1.80m) of profiles confirming to EN:12608 in any shape, colour and design duly reinforced with galvanised mild steel section made of required shape & size as per CPWD specification, including uPVC extruded glazing beads, interlocks and inline sash adopter (where ever required) of appropriate dimension, EPDM, gasket, hardware, stainless steel (SS 304 grade) fasteners of minimum 8mm dia with counter sink head, comprising of matching polymide PA6 grade sleeve for fixing frame to finished wall as per IS 1367 :Part 1 to 14 size for plastic packers, plastic caps and necessary stainless steel screws, etc., Profile of frame, sash & mullion (if required) shall be mitred cut and fusion welded / mechanically jointed duly sealed at all corners, including drilling of holes for fixing hardware's and drainage of water, etc. After fixing frame the gap between frame and adjacent finished wall shall be filled with weather proof silicon sealant over backer rod of required size and of approved quality, etc., all complete as per approved drawing & direction of Engineer-in-Charge. Section of steel reinforcement and cross sections of uPVC profiles to be as per design approved by EIC. 50.00 Sq m 0.00
28 Providing and fixing factory made uPVC glazed / Ventilator casement window single panel with or without fixed panel with SS 304 friction hinges as per size and weight of sash, single point locking zinc alloy (zamak) powder coated handle, with using minimum frame of (39mm X 39mm) & sash / mullion of (39mm x 60mm) ( height of the ventilator upto 1.20m) made of required shape & size as per CPWD specification, including uPVC extruded glazing beads, interlocks and inline sash adopter (where ever required) of appropriate dimension, EPDM, gasket, hardware, stainless steel (SS 304 grade) fasteners of minimum 8mm dia with counter sink head, comprising of matching polymide PA6 grade sleeve for fixing frame to finished wall as per IS 1367 :Part 1 to 14 size for plastic packers, plastic caps and necessary stainless steel screws, etc., Profile of frame, sash & mullion (if required) shall be mitred cut and fusion welded / mechanically jointed duly sealed at all corners, including drilling of holes for fixing hardware's and drainage of water, etc., After fixing frame the gap between frame and adjacent finished wall shall be filled with weather proof silicon sealant over backer rod of required size and of approved quality,etc., all complete as per approved drawing & direction of Engineer-in-Charge. Section of steel reinforcement and cross sections of uPVC profiles to be as per design approved by EIC. 2.00 Sq m 0.00
29 Providing and fixing STAINLESS STEEL RAILING ( Grade 304) made of Hollow tubes, channels, plates, etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners, stainless steel bolts, etc., of required size, on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-in-Charge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners, etc.,) 82.00 Kgs 0.00
30 Providing and laying vitrified floor tiles Matt / Antiskid finish of Size [600 X 600]mm as indicated below for Paper Joint in different sizes (Thickness to be sepcified by the manufacturer) with water absorption less than 0.08% and confirming to IS : 15622, of approved make, in all colours and shades, laid on 20mm thick cement mortar 1:4 ( 1 cement: 4 course sand), including grouting the joints with grey cement slurry @ 3.30Kg/Sq m including grouting the joints with white cement and matching pigments, etc., all complete as directed by Engineer-in-Charge. 26.00 Sq m 0.00
31 Providing and laying Double charged Vitrified tiles in floor with different sizes (thickness to be specified by the manufacturer), with water absorption less than 0.08% and conforming to IS:15622, of approved brand & manufacturer, in all colours and shade, laid with cement based high polymer modified quick set tile adhesive (water based) conforming to IS : 15477, in average thickness of 6mm including, pointing and grouting the joints with white cement and matching pigment, etc., all complete as directed by Engineer-in-Charge. 508.00 Sq m 0.00
32 Providing and laying Double Charged Vitrified tiles in different sizes (thickness to be specified by the manufacturer), with water absorption less than 0.08% and conforming to IS: 15622, of approved brand & manufacturer, in all colours and shade, in skirting, riser of steps, laid with cement based high polymer modified quick set tile adhesive (water based) conforming to IS: 15477, in average 6mm thickness, including grouting of joints (Payment for grouting of joints to be made separately), etc., all complete as directed by Engineer-in-Charge. 38.00 Sq m 0.00
33 Providing and laying Polished Granite stone flooring and staircase raiser and steps in colour Black, Cherry / Ruby Red or Equivalent in required design and patterns, in linear as well as curvilinier portions of building as complete as per the architectural drawings / Site condition with 18mm thick stone slab or 20mm (average) thick base of cement mortar 1:4 ( 1 cement : 4 coarse sand) laid and jointed with cement slurry and pointed with white cement slurry admixed with pigment of matching shade including rubbing, curing and polishing, nosing, chamfering and making grooves, etc., complete as per direction of Engineer-in-Charge. 18.00 Sq m 0.00
34 Providing and fixing Single socketed pipes of 110mm diameter unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A of approved brand, on wall face including jointing with seal ring conforming to IS : 5382, leaving 10mm gap for thermal expansion, etc., all complete as directed by Engineer-in-Charge. 74.00 Metre 0.00
35 Providing and fixing Single socketed pipes of 75mm diameter unplasticised Rigid PVC water pipes conforming to IS : 13592 Type A of approved brand, on wall / floor including jointing with seal ring conforming to IS : 5382, leaving 10mm gap for thermal expansion, etc., all complete as directed by Engineer-in-Charge. 12.00 Metre 0.00
36 Plastering to internal brick / block wall with 15mm thick on the rough side of single or half brick wall of cemnet mortor (1:6) including leveling, curing and making the level smooth and at all heights, plaster drip course / groove in plastered surface or moulding to R.C.C. projections and execute the work complete, etc., all complete as directed by Engineer-in-Charge. 674.00 Sq m 0.00
37 Plastering to internal ceiling surface with 12mm thick with cement mortor (1:4) including leveling,curing and making the level smooth and at all heights and execute the work complete, etc., all complete as directed by Engineer-in-Charge. 78.00 Sq m 0.00
38 Plastering to external brick / block wall with 18mm cement plaster in two coats under layer 12mm thick cement plaster on the rough side with cement mortor 1:5 (1 cement : 5 coarse sand) finished with a top layer 6mm thick cement plaster 1:6 (1 cement : 6 fine sand) including leveling, curing and making the level smooth and at all heights, plaster drip course / groove in plastered surface or moulding to R.C.C. projections and execute the work complete, etc., all complete as directed by Engineer-in-Charge. 626.00 Sq m 0.00
39 Providing and applying internal wall and ceiling painting with two coats of premium acrylic emulsion paint of interior grade, having VOC (Volatile Organic Compound) content less than 50grams / litre after applying white cement based putty of average thickness 1mm over the plastered wall / ceiling surface including preparation of the surfces, with a coat of low VOC primer with emery paper to bring to smooth and even including applying additional coats wherever required to achieve even shade and colour of approved brand, etc., all complete as directed by Engineer-in-Charge. 990.00 Sq m 0.00
40 Providing and finishing old walls in two or more coats with Premium Acrylic Smooth exterior paint with Silicone additives of approved brand of required shade @ 1.43 ltr / 10 Sq m over existing cement paint surface after Removing dry or oil bound distemper, water proofing cement paint and the like by scrapping, sand papering and preparing the surface smooth including necessary repairs to scratches, etc., all complete as directed by Engineer-in-Charge. 238.00 Sq m 0.00
41 Providing and Finishing walls with Acrylic Smooth exterior paint of required shade for New work (Two or more coat applied @ 1.67 ltr/10 Sq m over and including priming coat of exterior primer applied @ 2.20 kg/10 Sq m) including scrapping,preparationof surface for completing the work, etc., all complete as directed by Engineer-in-Charge. 626.00 Sq m 0.00
42 Providing and applying synthetic enamel paint of approved brand and manufacture of required colour to give an even shade in One or more coats on old work by cleaning and srcapping to make the surface smooth before appling paint, etc., all complete as directed by Engineer-in-Charge. 28.00 Sq m 0.00
43 Providing and applying synthetic enamel paint in Two or more coats on new work over an under coat of suitable shade with ordinary paint of approved brand and manufacture, etc., all complete as directed by Engineer-in-Charge. 36.00 Sq m 0.00
44 Disconnecting damaged overhead/terrace PVC water storage tank of any size from water supply line and removing from the terrace including shifting at ground level, etc., all complete as directed by Engineer-in-Charge. 1.00 Each 0.00
45 Dismantling 15 to 40mm dia G.I. / CPVC pipe including stacking of dismantled pipes (within 50 metres lead) including making temporary arrangements for continuing ongoing services to toilets, etc., all complete as directed by Engineer-in-Charge. 5.00 R m 0.00
46 Fixing chowkhat in existing opening in brick / RCC wall with dash, fasteners / Chemical fasteners of appropriate size (3 nos on each vertical member of door chowkhat and 2 nos on each vertical member of window chowkhats), including Cost of dash fasteners / chemical fastener, etc., all complete as directed by Engineer-in-Charge. 42.00 Each 0.00
47 Providing and fixing bright finished brass hard drawn hooks (coat hooks) and eyes of 300mm size, etc., all complete as directed by Engineer-in-Charge. 1.00 Each 0.00
48 Repair to plaster of thickness 12mm to 20mm in patches of area lesser than 2.50Sq m including cutting the patch in proper shape, raking out joints and preparing plastering the wall surface with white cement based polymer modified self curing mortar, including disposal of rubbish, without causing hindrance / protecting the existing floor finish work, etc., all complete as directed by Engineer-in-Charge. 54.00 Sq m 0.00
49 Demolishing R.C.C. work by mechanical means and stockpiling at designated locations and disposal of dismantled materials up to a lead of 10 kilometre outside HAL, stacking serviceable and unserviceable material separately including cutting reinforcement bars, after making temporary proetction for existing service lines, etc., all complete as directed by Engineer-in-Charge. 8.00 Cu m 0.00
50 Demolishing brick work with cement mortar manually / by mechanical means, after disconnecting the electrical service and AC lines if any, including stacking of serviceable material and disposal of dismantled materials up to a lead of 10 kilometre outside HAL, etc., all complete as directed by Engineer-in-Charge. 90.00 Cu m 0.00
51 Providing and fixing C.P. brass toilet paper holder of approved brand and fixing with screws, raw plugs, etc., all complete as directed by Engineer-in-Charge. 5.00 Each 0.00
52 Providing and fixing beveled edge mirror of size [600 x 450]mm of superior glass (of approved quality) complete with 6mm thick hard board ground fixed to wooden cleats with C.P. brass screws and washers, etc., all complete as directed by Engineer-in-Charge. 1.00 Each 0.00
53 Providing and fixing Wall hung half pedestal Vitreous China Wash basin size of approx size [630 x 450]mm fixed with with C.I. brackets / rack bolts, single 15mm C.P. brass pillar taps, 32mm C.P. brass waste coupling of standard pattern, P.V.C. waste pipe with waste fittings of 40mm dia and make it function of approved brand / make, including painting of fittings and brackets, cutting and making good the walls wherever required, etc., all complete as directed by Engineer-in-Charge. 3.00 Each 0.00
54 Providing and fixing Stainless Steel A ISI 304 (18/8) Kitchen sink of size [510 x 1040]mm bowl depth 250mm with drain board as per IS:13983 with C.I. brackets and stainless steel plug 40mm, P.V.C. waste pipe with waste fittings of 40mm dia,making it completely operational ,including painting of fittings and brackets, cutting and making good the walls and wherever required, etc., all complete as directed by Engineer-in-Charge. 2.00 Each 0.00
55 Providing and fixing white vitreous china pedestal type water closet (European type W.C. pan) of approved brand with ISI marked white solid plastic seat and lid, 10 litre low level white P.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever), conforming to IS : 7231, with all connecting fittings and fixtures to make it operational completely, including cutting and making good to the walls and floors wherever required, etc., all complete as directed by Engineer-in-Charge. 4.00 Each 0.00
56 Providing and fixing 8mm dia C.P. / S.S. Jet (Health Fuacet) with flexible tube upto 1metre long with S.S. triangular plate on walls / Eureopean type W.C. material of approved make and quality, etc., all complete as directed by Engineer-in-Charge. 6.00 Each 0.00
57 Providing and fixing white colour wall hung vitreous china battery based infrared sensor operated urinal of approx. size [610 x 390 x 370]mm having pre & post flushing with water (250 ml & 500 ml consumption approx.), having water inlet from back side, including fixing to wall with brackets embedded in cement mortar (1:3), connecting the waste pipe/waste coupling to floor trap with all necessary fittings and accessories like 32mm dia semi-rigid PVC waste pipe (concealed in the wall) including PVC waste fittings, clamps, etc., all as per manufacturers, specification and direction of Engineer-in-charge. 5.00 Each 0.00
58 Providing, fixing, testing and commissioning trap (S.S.floor trap) of approved make with 100mm inlet and 75mm outlet of self cleansing design with screwed down or hinged grating with or without vent arm complete, including cost of cutting and making good the walls and floors , connection with PVC soil / waste pipe, necessary 150mm thick cement concrete (1:2:4) for embedding the trap, etc.,all complete as directed by the Engineer-in-Charge. 5.00 Each 0.00
59 Constructing masonry Chamber [60 x 60 x 75]cm inside or outside (or approx. size as per site condition) , in brick work in cement mortar 1:4 (1 cement : 4 coarse sand) for sluice valve, with C.I. surface box 100mm top diameter, 160mm bottom diameter and 180mm deep (inside) with chained lid and RCC top slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size ) , i/c necessary excavation, foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40mm nominal size) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12mm thick, finished with a floating coat of neat cement complete as per standard design : 18.33.1 With common burnt clay F.P.S.(non modular) bricks of class designation 7.5, etc., all complete as directed by Engineer-in-Charge. 1.00 Each 0.00
60 Providing and fixing 15mm nominal bore dia C.P. brass bib cock of approved quality conforming to IS:8931, etc., all complete as directed by Engineer-in-Charge. 7.00 Each 0.00
61 Providing and fixing 15mm nominal bore C.P. brass long nose bib cock of approved quality conforming to IS standards and weighing not less than 810 gms, etc., all complete as directed by Engineer-in-Charge. 7.00 Each 0.00
62 Providing and fixing PTMT soap Dish Holder having length of 138mm, breadth 102mm, height of 75mm with concealed fitting arrangements, weighing not less than 106 gms, etc., all complete as directed by Engineer-in-Charge. 4.00 Each 0.00
63 Providing and fixing Concealed Chlorinated Polyvinyl Chloride (CPVC) pipes of approved brand, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, fixing the pipe with clamps at 1.00m spacing, necessary reducers, tank adaptors, etc., This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints and making good the walls, etc., all complete as directed by Engineer-in-Charge.
a) 15mm dia 15.00 R m 0.00
b) 20mm dia 20.00 R m 0.00
c) 25mm dia 20.00 R m 0.00
d) 32mm dia 10.00 R m 0.00
e) 40mm dia 15.00 R m 0.00
64 Providing and placing 2000Litres capacity polyethylene water storage tank, IS : 12701 marked on terrace (at all floor levels), with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow valve / control valves, pipes, etc., all complete as directed by Engineer-in-Charge. 1.00 Each 0.00
65 Providing and fixing PTMT extension nipple of minimum 25mm nominal bore for water tank pipe, fittings of approved quality and colour, etc., all complete as directed by Engineer-in-Charge. 2.00 Each 0.00
66 Dismantling of old S.W. pipes including breaking of joints and bed concrete stacking of useful materials near the site within 50m lead and disposal of unserviceable materials into municipal dumps and making temporary arrangements to protect / countinue ongoing service lines of other floors, etc., all complete as directed by Engineer-in-Charge.
a) 100mm diameter 40.00 R m 0.00
b) 150mm diameter 50.00 R m 0.00
67 Supply and Making connection of drain pipes of 100 to 250mm diamete or sewer line with existing manhole including breaking / cutting into and making good the walls, floors with cement concrete 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size) cement plastered on both sides with C.M 1:3 ( 1 cement : 3 caorse sand ), finished with a floating coat of neat cement and making necessary channels for the drain etc all complete as directed by the Engineer-in-Charge. 1.00 Each 0.00
68 Providing and fixing powder coated aluminium (minimum thickness of powder coating 50 micron) work for doors, windows, ventilators,and partitions with extruded built up standard tubular sections/appropriate Z sections and other sections of approved make conforming to IS: 733 and IS: 1285, including cleat angle, Aluminium snap beading for glazing / paneling, C.P.brass / stainless steel screws, filling up the gaps at junctions, with dash fasteners and EPDM rubber/neoprene gasket, etc., all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately) 1000.00 Kgs 0.00
69 Providing and fixing glazing in aluminium / UPVC door, window, ventilator shutters and partitions, etc., With float glass panes of 5mm thickness (weight not less than 12.50 kg/Sq m) along with EPDM rubber/ neoprenegasket/sealant of 5mm depth, etc., all complete as per the architectural drawings and the directions of Engineer-in-Charge. 76.00 Sq m 0.00
70 Providing and fixing double glazed hermetically sealed glazing in aluminium windows, ventilators and partitions / panes, etc., with 6mm thick clear float glass both side, having 12mm air gap, including providing EPDM gasket, perforated aluminium spacers, desiccants, sealant (Both primary and secondary sealant), etc., as per specifications, drawings and direction of Engineer-in-Charge. 108.00 Sq m 0.00
71 Providing and laying integral cement based water proofing treatment with average thickness of 120mm and minimum thickness at khurra as 65mm including preparation of surface as required for treatment of roofs,balconies, terraces etc consisting of following operations: (a) Applying a slurry coat of neat cement using 2.75 kg/Sq m of cement admixed with water proofing compound conforming to IS. 2645 and approved by Engineer-in-charge over the RCC slab including adjoining walls upto 300mm height including cleaning the surface before treatment. (b) Laying brick bats with mortar using broken bricks/brick bats 25mm to 115mm size with 50% of cement mortar 1:5 (1cement : 5 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer in-charge over 20mm thick layer of cement mortar of mix 1:5 (1 cement :5 coarse sand ) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer in-charge to required slope and treating similarly the adjoining walls upto 300mm height including rounding of junctions of walls and slabs. 519.56 Sq m 0.00
(c) After two days of proper curing applying a second coat of cement slurry using 2.75 kg / Sq m of cement admixed with water proofing compound conforming to IS : 2645 as per EIC. (d) Finishing the surface with 20mm thick jointless cement mortar of mix 1:4 (1 cement :4 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-Charge including laying glass fibre cloth of approved quality in top layer of plaster and finally finishing the surface with trowel with neat cement slurry and making pattern of [300 x 300]mm square 3mm deep. (e) The whole terrace so finished shall be flooded with water for a minimum period of two weeks for curing and for final test.“All above operations to be done in order and as directed and specified by the Engineer-in-Charge. Note: A performance guarantee bond for 5 years on non-judicial stamp paper of Rs. 500/- shall be given by the contractor. The 10% of completed value of this item shall be dedcuted as defect liability deposit and the same shall be returned after sucessful completion of 5 years from the date of completion of contract / project as a whole.
72 Providing and fixing mineral fibre false ceiling tiles (of approved brand/make) with 16mm thick beveled tegular edge with (NRC 0.55 to 0.60) at all heights of size [595 X 595]mm of approved texture, design and pattern. The tiles should have Humidity Resistance (RH) of 99%, Light Reflectance ≥ 85%,Thermal Conductivity k = 0.052 - 0.057 w/m K, Fire Performance as per (BS 476 pt - 6 &7)in true horizontal level suspended on interlocking T-Grid of hot dipped all round galvanized iron section of 0.33mm thick (galvanized @120 gsm) comprising of main T runners of [15 x 32]mm of length 3000mm, cross T of size [15 x 32]mm of length 1200mm and secondary intermediate cross T of size 15x32 mm of length 600mm to form grid module of size [600 x 600]mm suspended from ceiling using galvanized mild steel item (galvanised@80gsm) 50mm long 8mm outer diameter M-6 dash fasteners, 6mm diameter fully threaded hanger rod up to 1000mm length and L-shape level adjuster of size [85 x 25 x 2]mm, spaced at 1200mm centre to centre along main ‘T’. The system should rest on periphery walls /partitions with the help of GI perimeter wall angle of size [24 x 24 X 3000]mm made of 0.40mm thick sheet, to be fixed to the wall with help of plastic rawl plug at 450mm centre to centre & 40mm long dry wall S.S. screws. The exposed bottom portion of all T-sections used in false ceiling support system shall be pre-painted with polyester baked paint, for all heights. The work shall be carried out as per specifications, drawings and as per directions of the Engineer-in-Charge. 610.00 Sq m 0.00
73 Supply and fixing of roller blinds consisiting of control unit idler, head of rail, roller tube, bottom rail operating chain, bracket and clamps / nuts / bolts of approved colour/pattern including necessary supporting hangar holders /screws, etc., all complete as directed by Engineer-in-Charge 60.48 Sq m 0.00
Sub-Total of Part 'I' - Civil (Excluding GST) 0.00
Part 'II A' - ELECTRICAL, VOICE & DATA WORKS
LED Light fixtures
1 Supply, fixing in flush with the false ceiling including suitable fixing arrangment using Chain links, testing & commissioning of recess mounting type square LED lighting fixture of wattage not exceeding 32watt made out of white powder coated aluminium housing, front frame with translucent /polycarbonate cover including control gear. The luminaire should have Lumen efficacy ≥125 lm/watt and lumen output not less than 4000 lumens with PF >0.9 and Colour temperature shall be ≥6500K operating on single phase 230V voltage 50 Hz AC supply with voltage range 140-270V, DALI dimmable driver including necessary interconnections and other standard accessories complete in all respects and as directed by Engineer incharge. LED used in the lighting fixtures should be one of the approved make. LM79 certification for luminaires & LM80 certificate for LED shall be produced.The LED Light fixture shall be of PHILIPS Model No:RC600B M LED40S PSD Philips DALI Dimmable/Equivalent model in other approved makes luminaries which meets the above technical specification. LED used in the luminaire should be one of approved make as per approved make list of HAL. 54.00 Nos 0.00
2 Supply and fixing on existing wall / ceiling, testing & commissioning of recess mounting , type round LED lighting fixture of wattage not exceeding minimum 18W LED downlights Luminaries with minimum lumens output Efficacy of minimum100 lm/W., comprising of white powder coated CRCA sheet steel housing, operating on single phase 230V 50Hz AC supply,DALI dimmable driver, including necessary interconnections and other standard accessories complete in all respects and as directed by Engineer incharge. LED used in the lighting fixtures should be one of the approved make. LM79 certification for luminaires & LM80 certificate for LED shall be produced. The LED light fixtures shall be of PHILIPS Model No:DN296B LED20S-6500 PSD WH Philips DALI Dimmable/Equivalent model of approved make luminaries which meets the above technical specification. complete in all respect and as directed by Engineer-in-charge. 46.00 Nos 0.00
3 Supply and fixing on ceiling as per site requirement testing & commissioning of Surface mounted LED downlighter with PDC aluminium housing and high translucent frosted plastic diffucer makes it a robust luminaire, wattage not less than 18W LED lighting fixture, lumens efficiency ≥ 100lm/w at luminaire level, effficent heat sink, operating on single phase 230V voltage 50 Hz AC supply with voltage range 140-270V. 79 certification for luminare & LM80 certificate for LED shall be produced. including control gear, power factor of control gear shall be >0.90. Crompton model no:LCDSPLN-S-18-CDL Equivalent model in other approved makes luminaries which meets the above technical specification. LED used in the luminaire should be one of approved make as per approved make list of HAL. 7.00 Nos 0.00
4 Supply, installation, testing and commissioning of DALI Dimming energy-efficient network lighting control solutions consist in built DALI power supply and driver power managetment, Ethernet port for network communication, isolated Remote Device Management(RDM) enabled DmX splitter unit use to connect lighting console to dimmers . Make Philips model no:Dynalite DDBC320 DALI or Equivalent model in other approved light fixtures makes which meets the above technical specification and as directed by EIC. 1.00 Nos 0.00
5 Supply, installation, testing and commissioning of Key-Pad interface module to connect any Antumbra panel with Dynalite system of phillips or other similar system other light fxitures having features like field effect technology,programmed to perform a wide variety of local and site-wide control functions with Rs 485 port, internal light sensor measures ambient light. Easy access key pads of Philips model : PAXBPE-WW-X + DACM-Dynet or Equivalent model in other approved make light fixtures which meets the above technical specification and as directed by EIC including necessary interconnection between DALI controller etc. 2.00 Nos 0.00
6 Supply, installation, testing and commissioning of Network Power Supply unit to supply regulatted power supply designed to supplement the Dynet network DC supply or other network DC supply of other lighting approved make,DIN rail mountable installed in suitable distribution board enclouser includign enclouser ,self resetting overload protection,short circuit proof,automatic thermal shutdown. Model : DDNP1501 of Philips or Equivalent model in other approved light fixtures makes which meets the above technical specification including interconnection with keppad and DALI controller complete in all respect and as directed by EIC. 1.00 Nos 0.00
7 Supply, installation, testing and commissioning of multifunction Low profile recessed 360° ceiling sensor that combines motion detection (PIR) and ambient light level detection (PE) in one device,powered and communicates to the networked control system via a DALI bus.detection of motion within a scanned area triggers a programmed lighting action,Daylight harvesting mode, ,Delivers automatic energy savings,Enables sign-on identification to the networked system.Philips model no:DUS360CR-D / Equivalent model in other approved makes luminaries which meets the above technical specification. LED used in the luminaire should be one of approved make as per approved make list of HAL. 11.00 Nos 0.00
8 Supply and fixing on ceiling as per site requirement testing & commissioning of Two-way Wall Washer LED light with wattage not less than 10W LED lighting fixture, lumens efficiency ≥ 85lm/w at luminaire level, effficent heat sink, operating on single phase 230V voltage 50 Hz AC supply with voltage range 140-270V. LM79 certification for luminare & LM80 certificate for LED shall be produced. including control gear, power factor of control gear shall be >0.90. Philips model no:582009/ Equivalent model in other approved makes luminaries which meets the above technical specification. LED used in the luminaire should be one of approved make as per approved make list of HAL. 6.00 Nos 0.00
9 Supply, fixing directly to the ceiling/wall/Floor using suitable mounting arrangements testing & commissioning of 28W, 2400 Lumens for 5 meter having reliable performance and anti-dust LED strips with professional design for Decorative lighting applications(Cove lighting) and Colour temperature shall be =>3000K, operating on single phase 230V voltage 50 Hz AC supply with voltage range 140-270V including necessary interconnections between driver and lighting fixtures complete in all respect and as directed by EIC. The lighting fixture shall be model no: Philips Linea Bright Cove light or Equivalent make in other approved makes. (Note: Driver will be measured separatley) 300.00 mtrs 0.00
10 Supply, fixing , testing & commissioning of 28wattage Driver for LED cove lighting using suitable mounting arrangements for abvove cove light strip.(one driver for every 5mtr lighting strip to used. However, wherever, small er length of cove ligtign stip is used as per design, in these cases addtional driver can be used.) 70.00 Nos 0.00
11 Supply & fixing on existing MS hook 1200mm sweep,Five star rated with brushless direct current motor(BLDC) Ceiling fans complete with blades, down rods, and accessories, 230V single phase 50Hz AC supply. Minimum air delivery 210cu.m/min with service value 6.00 BEE , erected in position with necessary flexible copper leads of required colour and with canopy, down rod 300mm to 600mm length as per site requirement , necessary rubber bushings, clamps nuts,bolts etc., complete in all respects and as directed by Engineer-in-charge. 4.00 Nos 0.00
12 Supply, installation, testing & commissioning of 300mm dia 900 rpm heavy duty exhaust fan of any approved make with louvers, connecting cord with 6A, 3 pin plug top and with all necessary accessories, including making wall openings and replastering to smooth finish with matching paint etc., complete in all respects and as directed by Engineer-in-charge. 2.00 Nos 0.00
13 Supply, fixing, testing & commissioning of the following factory built powder coated Double door MCB/MCCB DB of any approved make fabricated out of M.S. sheet steel enclosure & necessary cutouts for operating the MCB knobs & comprising of 200 amps tinned copper busbars & earthing bus with tapped holes including internal wiring with stranded copper PVC wires or suitable size copper strips etc. & fixing the DB in flush with wall/ on wall as per site requirement with necessary M.S. angle supports, chipping the wall and replastering to smooth finish etc., wherever required as per site condition, complete in all respects, as directed by Engineer-in-charge and comprising the following as detailed below:
a) 6 way (4 + 18), Double door Horizontal MCB DB 5.00 Nos 0.00
b) 8 way (4 + 24), Double door Horizontal MCB DB 1.00 Nos 0.00
c) 6 way VTPN, MCCB DB IP 54 - Metal Door VTPN MCCB DB 1.00 Nos 0.00
d) 125 A, 415V 36KA, FP MCCB TM based 1.00 Nos 0.00
e) 63A, 415V 10KA TP MCB 4.00 Nos 0.00
f) 63 amps. ratings, 4P MCB, "C" curve, 10 KA breaking capacity. 6.00 Nos 0.00
g) 32 amps. ratings, 4P MCB, "C" curve, 10 KA breaking capacity. 2.00 Nos 0.00
h) 6-32 amps. ratings, SP MCB, "C" curve, 10 KA breaking capacity. 117.00 Nos 0.00
Lighting Point wiring
14 Wiring for light point / fan point / exhaust fan point/call bell point from nearest switch box with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, fan regulator, modular plate, suitable GI box and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required. (as per detailed CPWD specifications for Group C wiring)
a) Wiring to single light point controlled by 1 No 6A, 250V gr. flush type modular SP switch complete in all respects. 11.00 Pts 0.00
b) Wiring to two light point controlled by 1 No 6A, 250V gr. flush type modular SP switch complete in all respects. 28.00 Pts 0.00
c) Wiring to three light point controlled by 1 No 6A, 250V gr. flush modular type SP switch complete in all respects. 20.00 Pts 0.00
d) Wiring to fan point controlled by 1 No. 6A, 250V gr. flush type modular SP switch including providing 1No box type MS Fan hook in ceiling whereever required, 2 module type electronic five stepped speed regulator etc., complete in all respects. 4.00 Pts 0.00
e) Wiring to exhaust/wall mounting fan point using 6A, 250V gr. flush type modular SP switch housed along with other lighting switches/separate switch box if required and 3pin 6A, 250V gr. modular type socket housed near the exhaust fan complete in all respects. 2.00 Pts 0.00
Wiring for Power Points(6A & 16A power sockets)
15 Wiring for circuit/submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required
a) 3 x 2.5 sq. mm (For lighting ckt from DB to Switch box, For 6A power Points) 1700.00 Mtrs 0.00
b) 3 x 4 sq. mm(For 16A power points) 600.00 Mtrs 0.00
16 Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.
a) 6A Switch 187.00 Nos 0.00
b) 16A Switch 26.00 Nos 0.00
c) 3 pin 6A Socket outlet 374.00 Nos 0.00
d) 3 pin 16A Socket outlet 26.00 Nos 0.00
17 Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.
a) 2 Module 250.00 Nos 0.00
b) 3 Module 40.00 Nos 0.00
c) 4 Module 30.00 Nos 0.00
d) 6 Module 190.00 Nos 0.00
e) 8 Module 5.00 Nos 0.00
f) 12 Module 3.00 Nos 0.00
18 Supplying and fixing of follwing size GI box in flush with wall including cutting the wall and making good finish with same.
a) 2 Module 50.00 Nos 0.00
b) 3 Module 40.00 Nos 0.00
c) 4 Module 15.00 Nos 0.00
d) 6 Module 30.00 Nos 0.00
e) 8 Module 5.00 Nos 0.00
f) 12 Module 3.00 Nos 0.00
19 Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.
a) 20MM PVC Conduit 800.00 Mtrs 0.00
b) 25MM PVC Conduit 1500.00 Mtrs 0.00
c) 32MM PVC Conduit 500.00 Mtrs 0.00
a) Supplying and fixing of Telephone socket outlet on the existing modular plate & switch box including connections but excluding modular plate & box etc. as required. 10.00 Nos 0.00
b) Supply & drawing of 0.5 mm dia copper conductor PVC insulated 4 pair colour coded and twisted unarmoured telecommunication cables in the existing PVC conduit as per standard practice including necessary inter connections & end terminations. 500.00 Mtrs 0.00
c) Supply, laying in the already excavated cable trench/existing duct/fixing on wall/cable tray/iron structure using suitable clamps etc./ encasing in pipe, testing and commissioning of 20 pair jelly filled armoured copper conductor of 0.5mm dia polyethylene insulated cover, twisted into pairs, colour coded, pairs laid up, fully filled with petroleum jelly as a moisture barrier, core wrapped with non-hygroscopic polyester tape to contain the jelly, covered with aluminium poly-laminates screen, polyethylene sheath extruded over aluminium screen, polyethylene tape over the above sheath, armoured with galvanised steel tape and outer polyethylene sheath underground telecommunication cable including both end terminations on the existing krone type junction box complete in all respects. 50.00 Mtrs 0.00
d) Supply & fixing on wall/grouted to floor upto 1200mm above ground level as per site requirement using suitable size MS angle iron frame work finished with two coats of enamel spray paint over a good primer & providing 50 pair krone type telephone connector junction box including krone connector with necessary mounting frame housed in suitable size FRP box with hinged lockable cover complete in all respects. 2.00 Nos 0.00
21 Supply & fixing of 1no of 1 Module RJ-45 sockets for one number of Data points on the existing modular plate & switch box including connections but excluding modular plate & box etc. as required. 181.00 Nos 0.00
22 Supply and drawing in the existing PVC conduits / wall / above false ceiling, Cat 6 UTP 4-Pair cable including necessary interconnections complete for LAN & Internet point as directed by Engineer-in-charge. 14000.00 Mtrs 0.00
23 Supply, installation, testing & commissioning of Following LT Panels( In door-PTTA).
Design, fabrication, supply, installation, testing and commissioning of cubicle type Indoor LT Panel with front lockable door arrangement, suitable to be mounted on the existing brick pedestal/cable duct using M.S channel frame work, with cable entry from bottom/top with removable gland plates with required knock-outs, panel fabricated out of CRCA sheet steel folded and braced as necessary to provide a rigid support for all components, totally enclosed, dust and vermin proof and degree of protection shall not be less than IP-54, multi-tier cubicle type formation with front hinged lockable doors for the individual feeders/ compartments, preparation of surface and treatment by seven tank process, powder coated with approved colour for not less than 50 microns and all doors and covers shall be fully gasketed using good quality EPDM gasket and/or rubber strips and ensure good lockable, durable door opening & closing mechanism, suitable meshed ventilator louvers with suitable cover,canopy type covering and Aluminium bus bars for three phases and neutral, bus bar insulators, heat shrinkable PVC sleeves etc., with necessary interconnections as specified in Technical specifications for electrical & mechanical works, comprising of following switchgear and accessories complete in all respects and as directed by Engineer-in-charge.
1) Current density shall not exceed 0.8A/sq.mm for Aluminium bus bars in LT Panel
2)The operating height of the Panel shall not exceed 2.1 mtr. from FFL.
23.1 Add-ON panel @ NDB Substation( In door-PTTA). 1.00 Nos 0.00
i) 1No - 250A 415V gr. 25KA, TP+NL MCCB TM based
ii) 2Nos-400A 415V gr. 36KA, TP+NL MCCB MP based
iii) The above Add-on outgoing LT panel to be coupled with existing (PTTA) LT Panel as per SLD at New design building Substation including suitable adopter box if any required, busbars extension matching to exisitng panel busbar etc., complete as per site condition and as directed by EIC.
23.2 New Design Building @ Second floor ( In door-PTTA) LT panel. 1.00 Nos 0.00
i) 1No - 400A, 415V gr. 36KA, Four Pole MCCB MP based
ii) Lot - 500A TP + 250 N, 415V, short circuit rated 36KA for 1sec, Aluminium bus bars with busbar insulators, heat shrinkable PVC sleeves etc.
iii) 1No- Multi function meter (MFM/MDM) suitable for 3ph, 4 wire, 240V(L-N), 5A, CL-1, RS 485 Port Digital MFM/MDM of EM6400NG of Schneider or any equivalent make meeting technical specification of above MFM complete in all respect.
iv) 1Set of - 400/5A current transformers of class 1 and 15VA burden for metering.
v) 1No- (0-500V) range 96x96mm flush type voltmeter with RYB selector switch
vi) 1No 16A 415V gr TP 50KA MPCB of for tapping power for metering and control circuit
vii) 1Set - RYB indicating lamps of LED module with 6A SP MCB.
viii) 1Set- 6A, MCB for the protection of measuring instruments.
i) 2 Nos - 250A 415V gr. 25KA TP+NL MCCB ,TM based
ii) 4 Nos - 125A 415V gr. 25KA TP+NL MCCB,TM based
iii) 8Nos - 63A 415V gr. 25KA TP+NL MCCB,TM based
iv) 6 Nos - 63A 415V gr. 10KA MCB
v) 1 Nos - 63A, 415V gr. 25KA TP+NL MCCB with VFD for AHU motor including built in PID controllers suitable for up to 18.5kW motors or as required for AHU motor complete as per technical specification and as directed by EIC.
23 Supply & laying in the already excavated cable trench/cable tray/fixing on wall/duct wall with necessary M.S clamps / encasing in pipes etc., testing & commissioning of following size XLPE insulated Aluminium (Al) conductor 1100V gr., earthed Armoured (Arm) U.G cables as directed and as per technical specification and as detailed below. (Note:- Excavation, sand & Brick Protection, concrete cutting, reconcreting, casing pipes will be measured separately.)
a) Supplying of 3.5CX 185 Sqmm LT Aluminium Armoured conductor 200.00 Mtrs 0.00
b) 3.5 CX 70 Sqmm Aluminium armoured conductor. 30.00 Mtrs 0.00
c) Supply of 3.5 CX 25 Sqmm Aluminium armoured conductor 180.00 Mtrs 0.00
d) 4 CX 16 Sqmm Aluminium armoured conductor. 80.00 Mtrs 0.00
24 Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required
a) Supplying of3.5CX 185 Sqmm LT Aluminium Armoured conductor 4.00 Nos 0.00
b) Supply of 3.5 CX 70 Sqmm Aluminium armoured conductor 2.00 Nos 0.00
c) Supply of 3.5 CX 25 Sqmm Aluminium armoured conductor 18.00 Nos 0.00
d) Supply of 4CX 16 Sqmm Aluminium armoured conductor 6.00 Nos 0.00
25 Supply and laying of 160 mm dia, PN8 HDPE pipe of confirming to IS 4984:19955 in the excavated trench/duct/at road crossings for encasing cables , including welding of pipes by heating complete in all respect as directed by Engineer-in-charge. 20.00 Mtrs 0.00
26 Supply and embedding in floor GI floor mounting box(300x300mmx50mm) for accomodate power socket, telephone & Lan points including fixing hardwares with hinged lockable cover with gasket etc., complete in all respects and as directed by Engineer-in-charge. 2.00 Nos 0.00
27 Supply and fixing on wall/ partition wall using necessary mounting arrangements for 105mmx50mm size DLP-PVC adaptable trunking system with separation partition for laying power and Data/Telephone cables/wires with full top cover, necessary accessoires such as end caps, flat angle, T joints, external/internal angle, flat junction, Body joint, cover joint, required cabling accessories etc., complete in all respects as directed by Engineer-in-charge. 100.00 Mtrs 0.00
28 Supplying and fixing of Hot dip galvanised Perforated type cable tray of following sizes, steel: As per IS:2062 / 1079, Galvanising : As per IS: 2629 / 4759 including all accessories like base slotted angle , horizontal elbow, horizontal tee, horizontal cross, horizontal reducer, vertical elbow up, inside, vertical elbow down, outside, coupler plate, fasteners etc.
a) 100 mm Width X 50 mm Depth X 1.6 mm Thickness 100.00 Mtrs 0.00
b) 300 mm Width X 50 mm Depth X 1.6 mm Thickness 100.00 Mtrs 0.00
a) Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. 2.00 Nos 0.00
b) Supplying & laying 25 mm X 5 mm GI strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of GI nut bolt & spring washer spaced at 50mm) 80.00 Mtrs 0.00
c) Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required. 120.00 Mtrs 0.00
30 Earth work in excavation by mechanical means (Hydraulic excavator)/manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan). Including dressing of sides and ramming of bottoms, for all lift, including getting out the excavated soil & refilling the same soil and disposal of surplus excavated soil as directed, with in a lead of 50m. 10.00 Cu.Mtrs 0.00
31 Concrete cutting/Chipping/Bitumen Road the existing 1:2:4 cement concrete road /pavements / flooring / rock/stone etc., including removing debris from the work site and depositing in the place as directed by EIC. 5.00 Cu.Mtrs 0.00
32 Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement-All work up to plinth level:
a) 1:2:4 (1 cementy: 2 coarse sand (zone-III)derived from natural sources : 4 graded stone aggregate 20 mm nominal size derived from natural sources) 5.00 Cu.Mtrs 0.00
a) Supply, fixing and programming of Managed Layer 2 network switch with 48 ports, RJ-45 autosensing 10/100/1000 ports, 4 SFP+ ports complete in all respects as per the details broughtout in technical specifications and as directed by Engineer-in-charge. Approved Make : Cisco/ HP/ Juniper/ Dlink / Netgear/ Extreme/ Allied Telesis 4.00 Nos 0.00
b) Supply, Installation,Testing and Commissioning of Minimum 1G SFP Transreciver for Fiber uplinks ( Transreciver as to be same OEM of switch only) Complete in all respects as directed by Engineer-in-charge. 4.00 Nos 0.00
c) Supply and fixing of Fiber Optic Patch Cord (LC-LC) SM Type - 1 meter, complete in all respects and as directed by Engineer-in-charge. Approved Make:COMMSCOPE TYCO/ PANDUIT/ MOLEX 2.00 Nos 0.00
d) Supply and fixing of Fiber Optic Patch Cord (LC-LC) SM Type - 3 meter, complete in all respects and as directed by Engineer-in-charge. Approved Make:COMMSCOPE TYCO/ PANDUIT/ MOLEX 2.00 Nos 0.00
e) Supply, fixing and programming of Managed Layer 2 network switch with 24 ports, RJ-45 autosensing 10/100/1000 ports, 4 SFP+ ports complete in all respects as per the details broughtout in technical specifications and as directed by Engineer-in-charge. Approved Make : Cisco/ HP/ Juniper/ Dlink / Netgear/ Extreme/ Allied Telesis 1.00 No 0.00
f) Supply and laying in the already excavated cable trench/existing duct/fixing on wall/cable tray/ iron supports/HDPE pipe, of 12 core Single Mode armoured, loose-tube, Gel-filled, 9/125 micron Fiber Optic cable, including OTDR testing for OFC cable complete in all respects as per technical specification and as directed by Engineer-in-charge. Approved Make:COMMSCOPE TYCO/ PANDUIT/ MOLEX 300.00 Mtrs 0.00
g) Supply and fixing of 24 Port LIU fiber LC style singlemode, 19-inch Rack mount Patch panel with adapter plates, fiber pig tails, Fully loaded including splicing. complete in all respects and as directed by Engineer-in-charge. Approved Make:COMMSCOPE TYCO/ PANDUIT/ MOLEX 1.00 No 0.00
h) Supply and fixing of fully Loaded, 24 Port CAT6 UTP Jack Panel, including termination of CAT 6 cables in Jack panel, labelling complete in all respects as per technical specification and as directed by Engineer-in-charge. Approved Make: COMMSCOPE TYCO/ PANDUIT/ MOLEX 8.00 Nos 0.00
i) Supply, fixing and labelling of Cat 6 UTP 4-Pair 1Meter length Patch cord, complete in all respects as per technical specification. Approved Make: COMMSCOPE TYCO/ PANDUIT/ MOLEX 181.00 Nos 0.00
j) Supply, fixing and labelling of Cat 6 UTP 4-Pair 2Meter length Patch cord, complete in all respects as per technical specification. Approved Make: COMMSCOPE TYCO/ PANDUIT/ MOLEX 181.00 Nos 0.00
k) Supply and fixing of floor mounted 42U Network Rack with load capacity of 750kgs or more, Zero U standard Vertical rack mount power distribution unit with 10 Nos. Indian 5/15A Round 3 Pin, 230 V AC sockets, 4nos of fans, 25x3mm earthing tinned copper bus bar, 3point lock, hardware etc. with all standard Accessories, complete in all respects as per technical specification and as directed by Engineer-in-charge. Approved Make:APC/VALRACK/NETRACK/RITTAL 1.00 No 0.00
l) supply and fixing of 50x50mm PVC Raceway with cover including fixing accessories, complete in all respects as directed by Engineer-in-charge. 200.00 Nos 0.00
m) supply and fixing of 100x100mm PVC Raceway with cover including fixing accessories, complete in all respects as directed by Engineer-in-charge. 100.00 Nos 0.00
Sub-Total of Part 'II A' - ELECTRICAL, VOICE & DATA WORKS (Excluding GST) 0.00
Part 'II B' - FIRE DETECTION AND ALARM SYSTEM
34 FIRE DETECTION AND ALARM SYSTEM
Supplying, installation, testing and commissioning of micro processor based intelligent addressable main fire alarm panel, central processing unit with the following loop modules and capable of supporting not less than 240 devices (including detectors) and minimum 120 detectors per loop and loop length up to 2 km, network communication card, minimum 320 character graphics/ LCD display with touch screen or other keypad and minimum 4000 events history log in the non volatile memory (EPROM), power supply unit (230 ± 5% V, 50 hz), 48 hrs back-up with 24 volt sealed maintenance free batteries with automatic charger. The panel shall have facility to connect printer to printout log and facility to have seamless integration with analog/digital voice evacuation system (which is part of the schedule of work under SH: PA System) and shall be complete with all accessories. The panel shall be compatible for IBMS system with open protocol BACnet/ Modbus over IP complete as per specifications.
a) Two Loop Panel. 1.00 No 0.00
b) Supplying,installation,testing & commissioning of intelligent adressable thermal detector with rate of rise cum fixed tempreature thermistor complete with base as required. 2.00 Nos 0.00
c) Supplying,installation,testing & commissioning of response indicator on surface/recessed MS Box having two LED, metallic cover complete with all connections etc as required. 10.00 Nos 0.00
d) Supplying, installation, testing & commissioning of intelligent analog addressable photothermal detector complete with mounting base complete as required. 20.00 Nos 0.00
e) Supplying, installation, testing & commissioning of manual call boxes of MS construction in surface/recess with stainless steel chain & hammer assembly complete with glass and push button etc.as required 2.00 Nos 0.00
f) Supplying, installation, testing & commissioning of addressable horn cum strobe complete as required. 2.00 Nos 0.00
35 Supply, installation, integrating with the existing main FACP, testing & Commissioning of Auto dialler with addressable control module connected to main control panel including connected cabling/wiring complete in all respects, as per technical specification. 1.00 No 0.00
36 Supply, laying and fixing directly to the ceiling/on wall / above false ceiling etc, testing & commissioning of 2 Core X1.5 sqmm copper XLPE insulated FRLS with ISI mark armoured RED colour LT cable along with required accessories, terminations glands, as directed by EIC to complete the installation as per the technical specification. 400.00 Mtrs 0.00
Sub-Total of Part 'II B' - FIRE DETECTION AND ALARM SYSTEM (Excluding GST) 0.00
Part 'II C' - Solar WORKS
1 Supply Installation and Commissioning of on- grid solar power plant for 75kWP 1.00 Set 0.00
SOLAR PV PANELS, INVERTERS AND ITS ACCESSORIES
Supply, Fixing, Testing & Commissioning of 75 kWp Grid Tied Solar Rooftop Power Plant consists of Solar Photo Voltaic array, power conditioning unit(PCU), consisting of Maximum Power Point Tracker (MPPT), inverter, controls, protections and switches. PV Array is mounted on suitable structure. Grid tied SPV system is without battery and should be designed with necessary features to supplement the grid power during day time. Components and parts used in the SPV power plants including the PV modules, metallic structures, interconnecting cables, junction box, switches, PCU's, earthing etc., complete in all respects and as detailed as below:-
a) Supply, installation, testing and commissioning of Solar PhotoVoltaic modules of minimum 535Wp or above rating consisting with 144 half-cut cells configration, with MONO crystalline silicon solar cells meeting IEC 61215 (revised) / IS 14286 / IEC 61646 standards. PV modules must qualify to IS/IEC61701 also PV modules used must qualify to the latest edition of IEC PV module qualification test or equivalent BIS standards. In addition, the modules must confirm to IEC 61730-1 & IEC 61730-2 with minimum efficiency of 20% with all accessories as per the tender specification, module shall have positive tolerance of 0 to 4% and negative temperature coefficient of power for the modules shall be less than or equal to 0.45% per deg. C.
Supply, fabrication, erection of Mounting structures for panels with Hot dip galvanized GI rectangular Tubes. The Mounting structure should have suitable size GI angle section for routing DC cables between Modules and Modules to cable trays, including necessary clamps, welding, nuts, bolts, etc as per IS 4756. Mounting structure suitable for RCC roof Top Hot Dip Galvanized (HDG) With Minimum Lower Height of 1 Meter, RCC Low balast, and Adhesive clamping and mounting structure shall be fabricated as per technical specification.
Supply, fabrication, erection of Mounting structures for panels with Hot dip galvanized GI rectangular Tubes. The Mounting structure should have 40mm GI angle section for routing DC cables between Modules and Modules to cable trays, including necessary clamps, welding, nuts, bolts, etc as per IS 4756. Mounting structure shall be fabricated for group of panels as per technical specification. Civil works for the foundation is also included and it has to be carried out as per the detailed specifications are mentioned in the technical specification.
Supply & laying/drawing of following DC Cables.
Supply, laying, testing and commissioning of Cables of appropriate sizes shall meet IEC 60227/IS 694, IEC 60502/IS1554 standards, voltage rating of 660/1100V cables from Modules to String Combiner / Monitoring Box/inverter, UV Protected Cable. Scope includes suitable size PVC pipe for cable protection. The item includes all necessary accessories clamp, ties etc as required complete as per technical specification.
Supply, fabricating, installing of 300x50x2mm size perforated GI cable Trays with out cover including horizontal and vertical bends, reducers, tees, cross members and other accessories as required and duly suspended from the ceiling/fixing to the wall/RCC beam/iron structures including suitable size M.S. angle supports and necessary fixing hardware as required and as per site requirements.
Supply and fixing/connecting of MC4 Connector suitable for 1C 4 Sqmm DC Cable at String side
Supply and fixing/connecting of MC4 Connector suitable for 1C 4 Sqmm DC Cable at Inverter Input side
Supply and fixing of Lightning arrestors(LA) spike.
Supply, providing and Fixing Cast Iron Pipe earth station confirming to IS 3043 complete with 2750mm long, 100 mm Inner Dia(ID),13mm thickness CI Pipe, with 2 part clamp made out of G I flat 50 x 6 mm continuously welded around the pipe using cast iron welding electrodes as per drawing. The cost also includes excavation for earth pit, providing & laying homogenous mixture of charcoal lumps, salt & sand all around the pipe as per specification, supplying and fixing of RCC Collar of size 450 mm dia, 450 mm height and 50 mm thick over Cement concrete base of minimum size 150mm width & 100mm thick all around below collar shall be provided using 1:2:6 CC after necessary excavation, refilling of soil, consolidating, ramming, leveling of soil etc., supplying & fixing the label board(MS Plate of size 300mmx200mmX2mm) welding to the electrode complete as per specification, std drawing, instructions of EIC.
Supply, fixing & connecting the 25x3mm(75 sqmm) size G.I strip on wall / clamping to the existing duct wall / fixing on cable tray/ laying 2 ft. below the ground level including concrete cutting, reconcreting, excavation, refilling, consolidation & levelling of soil after laying for interconnection between the earth pits & panels, DB's as directed by Engineer-in-charge.
Supply and fixing on the wall/tray 4 Sqmm copper un armoured cable complete with necessary interconnections using suitable lugs, bolts & nuts to effect proper earth continuity as per standard practice.
Remote monitoring system with WMS for Data Accusation
All other accessories for complete functioning of solar PV power plant consisting of AC and DC cables and its terminations, , cable trays, lightning arrestor and earting for LA and power plant including required GI strip,etc complete in all respect and as required for plant as per the specification given for individual items under section-1. Note: The LT cable from ACDB at roof top to HAL distribution board will be measured separately.
b) Supply, Installation, Testing and Commissioning of Grid Tied solar string inverter of 75kVA rating , IP 66 rated, outdoor, and IP 20 for indoor unit the output should be three Phase 415V, 50Hz, true sinewave inverter system, with Maximum Power Point Tracker charge controller.Inverter should have MPPTs as per OEM design and site requirement for extracting more output.. Minimum protection required shall be over voltage/surge, over load, short circuit and anti- islanding protection. Earthing shall be provided as per IEC standards. IGBT / MOSFET switching and microprocessor / DSP type controller with true sine wave output. Unity Power factor(75kVA=75kW). Accuracy of AC voltage control = +/-3%. Accuracy of AC frequency control = +/-1%. Frequency = 50Hz. Intelligent interface with LED/LCD display(Bluetooth/Wifi interface is also acceptable). Total Harmonic Distortion <3%, the minimum inverter effciency should be >95% and P.F of >0.9. The inverter should have all specification, protections, operational modes, etc as detailed in techinical specification. The inverter should have in-built Type Surge protection device on AC and DC side.The item includes all necessary accessories like supports, canopy etc,.
c) Supply, fabrication, fixing & grouting of MS angle frame work/Mounting stand with Canopy arrangement for the Inverter erection.
d) Supply and Erection of DATA Monitoring System with Display monitor as per IEC standard.
e) Supply, installation, testing and commissioning of AC Distribution panel board suitable for 415V, 50 Hz, outdoor type with IP55, metal clad, totally enclosed, rigid, floor or wall mounted, air insulated cubical type. Class I+II surge Protective Device with CT & Multifunction Meter, incoming MCCB & Outgoing MCCB. DCDBs, cabling from AC Isolation boxes to inverter, array junction boxes etc., complte in all respects inline with detailed specificaiton.
All other accessories for complete functioning of solar PV power plant.
Sub-Total of Part 'II C' - Solar WORKS (Excluding GST) 0.00
Part 'II D' - Air-conditioning works
Air-conditioning works
1 Design, Supply, installation, testing and commissioning of the minimum 48 HP capacity (Combination of two modules) of Air-cooled VRF/VRV (Variable Refrigerant Flow/Variable Refrigerant volume ) modular type Outdoor unit mounted on suitable MS frame for connecting existing DX type VRV/VRF-AHUs with multiple variable speed, energy efficient inverter driven Scroll/rotary compressors as per specifications complete with suitable capacity drive motors, air-cooled condenser, including first charge of refrigerant gas R410A/R407C/R-32, oil separator with all accessories and safety devices as per OEM standards, high-low pressure cut-off, ODU vibration isolators, MS frame stand. ODU unit shall be suitable for operating on 3 phase, 380-415V, 50Hz power supply with all associated electrical works including, power cabling to nearest power point & microprocessor control panel, starter controls for all compressors and condenser fan motors along with internal control and power wiring, cooling coil with internally interconnected refrigerant pipes, Y joints/ refnet joints, for interconnecting various capacity following modules (to make unit of above HP), charging port and the entire unit shall be with weather resistant powder coating paint for continuous outdoor operation. The scope includes power & control cabling between AHU and outdoor units along with all associated accessories. The scope also includes supply, installation, testing & commissioning of OEM Standard VRV/VRF- AHU connectivity kit for below mentioned Dx-AHU's, including compatible Electronic type expansion valves and display unit with provision to set desired temperature etc, Temperature display unit shall be connected to the corded remote control display unit fixed inside the training hall area at suitable location including required control wiring complete in all respects as per technical specification and as instructed by Engineer-In-charge. 1.00 Set 0.00
2 AHU: Design, Supply, loading, transportation, unloading, installation, commissioning and testing of floor mounting DX type, VRV/VRF compatible minimum 15000CFM (with suitable cooling coil load) capacities Air Handling Unit (AHU) made of 45 mm thick (±2mm), 40kg/cu.m(±2kgs)density PUF insulated double skinned air handling unit of sectionalised sheet steel construction with outer sheet of panels shall be made of pre-plasticised GI sheet of 0.6 mm thick and inner sheet of 0.6 mm plain 304 grade stainless steel sheet. The entire unit shall be fitted with double skin panels with frame work of thermal-break profile complete. AHU is complete with filter section, minimum 4 rows deep Dx-VRV/VRF copper cooling coils or suitable configuration to match with the outdoor unit selection (Number of rows of cooling coil shall be as per OEM design to meet the specification) & aluminium fins, construction including necessary refnet joints to connect Dx cooling coils, Fan section with belt driven DIDW backward coverd fan mounted on spring vibration isolators, Fan-motor assembly (as a whole) shall be statically & dynamically balanced, double hinged type/suitable type access doors for both motor and filters as per site requirement, cabin light fixure with door interlocking limit switch, Drain pan made out of SS 304 18G stainless steel duly insulated, including pressure testing, vaccumising of refrigerant piping complete. The coil size shall be selected for a maximum face velocity of 500 feet/minute and 50mm WC external static pressure or as required to overcome pressure drop in the systems. Motor shall be with TEFC Squirrel Cage IP 55 Protected 1.00 No 0.00
VFD Compatible induction motor minimum IE - 2 class efficiency suitable for 415 +/- 10% volts, 50 cycles, 3 phase power supply. The AHU shall be supplied with filter section to accomodate Fine filters from 99% down to 3.0 microns and Pre filter from 90% down to 10.0 microns. The AHU's shall also contain Magnehelic gauges with necessary interconnection and required Temperature sensors and display unit with provision to set desired temperature etc. AHU noise level shall be as per OEM standard (Scope of work include SITC of filters and its section as detailed above). The entire AHU shall be mounted on vibration isolation rubber pads such that no vibration is transimitted to the structure.
3 Design, Supply, erection, testing and commissioning of minimum 14HP capacity Air-cooled variable refrigerant volume/variable refrigerant flow(VRV/VRF) modular type Outdoor unit mounted on suitable MS angle frame for connecting multiple indoor units of different capacities including suitable size communication copper control wiring up to each indoor units, energy efficient inverter driven rotary/ Scroll compressors of EER(W/W) not less than 3.26, 3 phase, 380-415 V, 50Hz AC power supply input including microprocessor control panel, starter controls for all compressors and condenser fan motors along with internal control and power wiring, cooling coil with internally interconnected refrigerant pipes, charging port and the entire unit shall be with weather resistant powder coating paint for withstanding all ambient conditions for continuous outdoor operation, all other required accessories, & hardware’s, full charge of eco friendly R 410A/R407 /R32 Refrigerant, safety devices and all other standard accessories etc., The scope includes power & copper control cabling between IDU and ODU along with all associated accessories, complete in all respect as per technical specification and as instructed by the Engineer-in-charge. MS frame work for mounting unit will be included in the scope. Note: 1)Power supply to 14HP unit will be provided near ODU to tap power supply. 1.00 Set 0.00
4 Design, Supply, erection, testing and commissioning of minimum 2.0TR capacity, Four directional/ Rounded air flow Cassette type Indoor Air Conditioning Units suitable for mounting inside false ceiling, each comprising of cooling coil, blower with multi speed motor, electronic expansion valve, supply & return air grilles, filter, insulated connection of refrigerant circuit, provision for fresh air intake, condensate water drain pump with electronic level sensor, including suitable size LT copper cable connecting to the nearest existing plug & socket, necessary mounting arrangement for suspending the unit from ceiling etc. All the indoor units shall be compatible to work with VRV / VRF type above condensing unit. Scope includes Remote controller (Cordless) for each following units including batteries and necessary cutting of existing false ceiling Note: Power supply to individual indoor unit will be provided near to IDU to tap power supply. 5.00 Nos 0.00
5 Design, Supply, erection, testing and commissioning of suitable size hard/soft refrigerant copper pipe as required with required pipe fittings and accesories like bends,Tees, reducers, Y-Joints/Refnets, suction filters, filter drier and couplings by good quality pipe joints which laid between ODU and IDU (AHU/Cassette). The Minimum copper pipe gauge shall be as per the gauges indicated by manufacturer. The Pipe sizes to be used as per OEM design recommendation. The Refrigerant pipe shall be insulated with Class O nitirle rubber of 19 mm thick for Gas line and 19 mm thick for liquid line. The piping shall be laid on walls / roof / ceiling well supported at specific intervals with metallic support, Cable tray with cover and required hardwares etc., for fixing copper pipes. All the necessary accessories, jointing / brazing etc shall be carried out as required..The pressure testing of refrigerant piping has to be done as per manufacturer design recommendation. All the copper fittings shall be suitable for R 410 A/R 407/R-32 refrigerant. Refer IDU/ODU layout tender drawing . Make: Mandev/Piyush/Totaline 60.00 R.Mtrs 0.00
6 Design,supply,Installation testing & commissioning of suitable sizes as per OEM recommonadation not less than 2mm thick CPVC drain water / fresh air arrangement pipe including U-traps, vlaves for AHU drain,reducer, bends, collars & elbow etc, all complete and duly insulated with 9 mm thick tubular insulation of closed cell elastomeric nitrile rubber as required.The PVC drain water pipe/fresh air pipe shall be complete with fittings, accessories and duly insulated using bends, elbows, tees, wall sleeves, hangers, supports, anchors etc.(Note:.1 Pipe used for fresh air intake to IDU shalll be coverd with mesh. 2. Necessary wall openings and closing the same using cement mortar and matching paint finish after taking out pipes is included in the scope of work. ) Make: Supreme/Finolex/Hycount/Saroplast 20.00 R.Mtrs 0.00
7 DUCTING : Design, supply, installation & testing and commissioning of factory fabricated GSS ducting as per IS 655 with zinc coating of minimum class VIII ie. 120GSM total on both sides as per IS 277 complete with suspenders of MS rods / wall MS brackets, cradles, angle iron supports, bolts and nuts, gaskets, stiffeners, canvas connections, fixing of anchor grip bolts, zinc chromate painted angle iron flanges/Transverse duct connectors, chipping and plastering of opening made for duct supports, outside air intakes complete with bird screen, damper,collar, bowl, rough filters etc., complete as per specifications and as directed by Engineer-in-charge.: Note:1. Scope includes cutting and closing of wall/wall GI sheet with suitable sealant. 2. Duct support shall be measured separately.
a 24 Gauage 80.00 Sq.mtrs 0.00
b 22 Gauge 120.00 Sq.Mtrs 0.00
c 20 Gauge 50.00 Sq.Mtrs 0.00
d 18 Gauge 20.00 Sq.Mtrs 0.00
8 Supply, installtion of Fresh air intake louvers made of extruded aluminium with bird/insect screen provided with intake louvers. The lowest louvers of the assembly shall extend out slightly to facilitate disposal of rain water without falling on the door / wall on which it is mounted and complete with all aluminium construction volume control dampers. 0.50 Sq.Mtrs 0.00
9 Supply, installing and testing of Factory fabricated GI Volume Control damper(Manual)made of GI sheet construction 16G GI blade, 16G GI frame, lever mechanism comprising of Steel spindles, blade linkages with suitable handle operation including status indicator for main and branch duct, ON/OFF indicators for dampers complete in all respect and as directed by Engineer-in-charge. 1.50 Sq.Mtrs 0.00
10 Supply,installation,testing and commissioning 150mm depth fire dampers fabricated out of minimum 16 gauge GI sheet construction and 18 gauge GI blades complete with chrom plated spindle, self lubricating bushes with 90-120Minutes fire rating as per UL 555 with 600mm extended sleeves as applicable with fusible link, complete in all respect. 1.50 Sq.Mtrs 0.00
11 Ducting Acoustic Insulation: Supply & Installation of Acoustic insulation for Supply air ducts with 15 mm thick open cell nitrile rubber with OEM recommended adhesive and density 140 kg / cum having open cell foam structure of Class 1 fire category as per technical specification. 80.00 Sq.Mtrs 0.00
12 Supply, Installation & Testing of Thermal Insulation for Supply air ducts with 13mm thick Class-O, Close cell elastomeric nitrile insulation with suitable OEM recommended adhesive and density not less than 50kg/cum. Joints shall be overlapped and joints sealed with 75 mm wide aluminium foil self adhesive tape/suitable tape as per technical specification, complete in all respect and as per standard practice. 190.00 Sq.mtrs 0.00
13 Supply and Fixing of Underdeck insulation for AHU room and second floor roof using 13mm thick Closed cell chemically cross linked polyethelene foam density of 30 kg/cum insulation material with one side factory laminated aluminium sheet to fix the insulation on the ceiling with additional support of GI frame/strip works for entire insulated area using GI washers and tie wires on perlins including all accesseries and required hardware as per site requirement and as directed by Engineer in charge. Note : Contractor should make sure that there should not be any sag after fixing the insulation. 410.00 Sq.mtrs 0.00
14 Supply, Fixing of Acoustic insulation for AHU room on the existing wall using 25 mm thick nitrile rubber open cell insulation with OEM recommended adhesive and density 140kg/cum having open cell foam structure of class 1 fire category provided in the suitable GI frame work as per site requirement. Complete in all respect as directed by Engineer in Charge. Note : Contractor should make sure that there should not be any sag/gap between wall & insulation after fixing the insulation. Scope includes repair of existing wall acoustic as is basis as per site requirement. 80.00 Sq.mtrs 0.00
15 Supplying, fixing, testing & commissioning of supply air diffusers of powder coated 4 way deflection with aluminium volume control dampers with removable core suitable for fixing on existing false ceiling grid including necessary supports, suitable size GI collar duct complete in all respects as per technical specifications. (Note: Measurement will be taken for neck size) 10.00 Sq.mtrs 0.00
16 Supplying, fixing, testing & commissioning of Return air diffusers of powder coated 4 way deflection without volume control dampers suitable for fixing on existing false ceiling grid complete in all respects as per the technical specifications. (Note: Measurement will be taken for neck size) 10.00 Sq.mtrs 0.00
17 Supply , installtion & testing GI butterfly Circular duct dampers of size 250 to 375mm dia (as per site requirement) complete in all respect as per standard practice. 42.00 Nos 0.00
18 Supply , installtion & testing of spill air mixing boxes made out of GI sheet with 250-375mm dia round inlet and outlet to connect to the above SA diffuser including necessary supports, complete in all respect as per standard practice. 42.00 Nos 0.00
19 Supply , installtion & testing 250 to 375mm suitable dia preinsulated flexible ducts with 25mm thick glass wool insulation covered with aluminum foil suitable for connecting branch ducts with the diffuser boxes including with circular clip complete in all respect and as per standard practice. Make: ATCO/Seven Star/Supaflex 50.00 R.mtrs 0.00
20 Supply & installation of flexible connections constructed of fire resistance flexible double canvas sleeve as per required size suitable for AHU mouth with zip for measurement of CFM etc. Complete in all repsect and as directed by EIC. 1.00 No 0.00
21 Supply, fabrication, fixing/welding to the existing steel struss/wall/ steel columns/ceiling suitable size M.S sections, angles/flats with supports, suspenders etc., as per site requirement including necessary fixing hardwares, clamps etc., and painted with 2 coats of enamel paint over a coat of good primer complete in all respects and as directed by Engineer-in-charge for making duct supports etc. 120.00 Kgs 0.00
Sub-Total of Part 'II D' - Air-conditioning works (Excluding GST) 0.00
Total of Part 'I' + 'II A' +'II B' + 'II C' + 'IID' (Excluding GST) 0.00
Add 18% GST 0.00
Grand Total (Including GST) 0.00
HINDUSTAN AERONAUTICS LIMITED
Facilities Management Division
Pre-Qulification Profile (To Be uploaded along with Part A)
Tender Ref No. or Contract No.: HAL/FMD/C-93/24-25
Name of Work: Proposed Construction of Training Centre at Second Floor of Design Building at RWRDC, HAL [HC].
Estimated Amount in Lakhs.: 355.7
Tender Notice Date:(DD/MM/YYYY) 18.11.2024 Can we give in DD/MM/YYYY
Complition Period(In months) 12
PROVISIONAL GST ID NO. for HAL 29AAACH3641R1Z3 Kindly mention at Col I J &K as " Any Other related Information"
Sl.No Description Details Enclosed / Not Enclosed Any Other Related Information Remarks
1 Name of the Individual / Firm / Company: * Mandatory Pls enter name
2 Type of ownership Related Document to be Uploaded to eProcurement Portal
3 Year of Estblishment of Company/Business
4 If Other, please specify
5 Details of Constitution or Legal Status such as certificate of incorporation, shops and establishments, etc., If not enclosed reasons be to recorded here
6 Address for correspondence:
8 PAN no and Name of Holder
9 PF number (If any)
11 (a) Service Tax Registration No
11 (b) Goods and Service Tax ID No.
12 Contact details
Contact person name Pls
Ph. No. with STD code
FAX No. with STD code 5 6
13 Registered Contractor
If Registered Contractor with HAL Yes/ No Pls Enter Related Document to be Uploaded to eProcurement Portal * Category: A = Above 25 Crores B = 15Crore to 25 Crores C = 5Crore to 15 Crores D = 1 Crore to 5 Crores E = Lessthan 100 Lakhs to 75 Lakhs F = 75 Lakhs to 50 Lakhs 0 7 .A1 1
Name of Organisation 199999 7 A 2
Category and Registration No. 200000 6 B 3
PEMD Amount ( If paid ) 499999 6 C 4
not required Need to Fill Column 19 no comparision 500000 5 D 5
14 I.T Returns for past 03 years 999999 5 E 6
2024-25 Pls Select 'Yes','No' for IT Returns for all the 3 years 2499999 4
15 Maximum value of works excuted during the followinf 5 years. . (In Lakhs)
2019 - 2020 Pls enter Finiancial Turnover in Rupees for all the years NOTE: The value of max work to be supported with the details of Works executed for each year including name of the organisation with period of execution. Here last 3 years cells to be considered to Check Annual Turn Over for 30 % value of Estimation given above 1 6.00 7.00 0 0
Avg Annual Turnover criteria is not met
16 DETAIL OF WORK ON HAND UPTO N-Months (N-contract period) [For Bid capacity calculation] NOTE : PROVISION for 10 works are given. If more, a separate similar sheet to be made showing all the works with all details as per this FORMAT and same to Uploaded. However, 9 works details to be provided and balance work value of other works to be added and to be provided in 10th row as OTHER works.
Sl.No(work No) Name of Organization with address Name of the work on hand Amount of Contract Rs (in Lakhs) Period of CONTRACT in months Date of Commencement of work as Work Order in dd/mm/yyyy Probable date of Completion as Agreed Actual progress achieved till date of Tender Notification Rs (in Lakhs) Balance value of work on hand [Col.(3)-Col.(7)] Rs (in Lakhs) Remarks If Any 0.00
8 0.00 Max Turn Over 07-08 8500000
9 0.00 Current Level to be brought by adding 10% for every year 10-11 8500000 X 1.1 X 1.1 X 1.1
10 0.00 Turn Over to considered A 11313500
0.00 Balance Work On Hand 207452000
Bid Capacity 0.00 Bid Capacity Criteria is not Met this shouldf be hidden while uploading
17 Work Schedule for completion of works with in stipulated time [Please enclose action plan / bar chart as to indicate the completion of work, within the scheduled time (contract period)] Bid Capacity (2 X A X N) - B
Related Document to be Uploaded -162198000
18 Quantity of work Excuted during the last three years
Earthwork [in Cum]
Concrete work [in Cum]
Reinforcement steel [in MT]
Any other quantity of items tenderer would like to mention
19 Bank(s) details: [Copy of the cheque leaf to be uploaded]
19a Bank Account No. Related Document to be Uploaded to eProcurement Portal (Note Canceled cheque leaf to be uploaded)
Name of the Bank
Type of Account
19b Bank Statement for past three month
19c Latest Over draft Facilties with Bank enter Name of Bank, Date of Issue and Value of Over Draft
20 Latest Bankers Solvency Certificate from Nationalized/ scheduled Bank issued NOT before 12 months from the date of Tender Notice. SOLVENCY solvency cal
Name of Bank & Branch Pls Related Document to be Uploaded to eProcurement Portal 18.11.2024 1-Jul 0 40000
Date of Issue(dd-mm-yyyy) #VALUE! 200000 40000
Value Rs. In Lakhs 200001 150000
Solvency value is as per NIT
21 Experience of having successfully completed similar works during last 7 years ending last day of previous month. [Work experience certificates / Completion certificates should be uploaded for verification]. [Latest work experience certificate may be uploaded] (i) THREE similar completed works each costing not less than the amount equal to 40% of the estimated cost. (ii) TWO similar completed works each costing not less than the amount equal to 50% of the estimated cost. (iii) ONE similar completed work each costing not less than the amount equal to 80% of the estimated cost. [Amount put to the Tender] 40000 500001 250000
Completed similar works during last 7 years You are Not Eligible Pls Select Works Completed during last 7 years 1000000 250000
Work NoI Type of Work [ Incase of private works the same shall be supported with TDS certificate] Related Document to be Uploaded to eProcurement Portal 1000001 500000
Name of The organisation
Brief Description of Work: 2000000 500000
Completed value of Work in Rs. Lakh: 2000001 1000000
Date of Commencement of Work [DD/MM/YYYY]: 4000000 1000000
Date of Actual Completion of Work[DD/MM/YYYY]: 4000001 2000000
Work No II Type of Work [ Incase of private works the same shall be supported with TDS certificate] Related Document to be Uploaded to eProcurement Portal 10000000 2000000
Name of The organisation
Brief Description of Work
Completed value of Work in Rs. Lakh:
Date of Commencement of Work [DD/MM/YYYY]:
Date of Actual Completion of Work[DD/MM/YYYY]: work done
Work No III Type of Work and Organisation name [ Incase of private works the same shall be supported with TDS certificate] Related Document to be Uploaded to eProcurement Portal 18.11.2024 2555
Name of The organisation
Brief Description of Work: #VALUE!
Completed value of Work in Rs. Lakh:
Date of Commencement of Work [DD/MM/YYYY]:
Date of Actual Completion of Work[DD/MM/YYYY]:
Work Competion is NOT with in 7 years
Valid Class I Electrical Licence [or] Undertaking for engaging Electrical Contractor possessing valid Class I Electrical Licence Please Enter Electricial Licence No Electricial Licence valid upto Related Document to be Uploaded to eProcurement Portal
22 DEAILS OF TECHNICAL PERSONNEL AVAILABLE( if space provided is insufficant separate sheet to be uploaded with the same format as below)
Sl.No Name of members or technical personllel avalable in the organization Qualification of similar nature number of years of experience
23 DETAILS OF MACHINERY AVAILABLE
Sl.No Name of Mechinery No Make Year of Manufacture
1 Concrete Mixers - Type etc
2 Vibrators - Diesel - Electrical
3 Weiding equipment's
4 a) Rectifiers
5 b) Welding Generators
6 Erection equipment's
10 Water Lifting motor pumps
13 Drilling Equipment's
16 Stone crushers
17 Bitumen hot mixture plant
18 Bitume boiler
20 Batching plants
21 Vibratory rollers
23 Cranes-Details
24 Concrete pumps
26 Rock breakers
27 Transit mixers
29 Weight batches
24 Details of person holding the power of Attorney (If different from contact person)
Name Related Document to be Uploaded to eProcurement Portal
Ph. No. with STD code
FAX No. with STD code
I/We declare and confirm that - 1. All information and attachments submitted in this application are true and correct. 2. I/We are aware that any false information provided herein will result in the rejection of my application and suspension of any registrations granted. 3. I/We shall not make refund claims of expenditure incurred in processing this application. Pls enter
26 Tender Document Cost and EMD details
Descipttion Enclosed / Not enclosed Valid upto [in case of BG] Related Document to be Uploaded to eProcurement Portal
Tender cost Enclosed
27 Average annual financial turn over during the last 3 years, ending 31st March 2024 [ should not be less than 30% of amount put to tender] and details for last 5 years to be provided to assess the bid capacity. The values provided to be supported by uploading Balance Sheet along with Profit & loss account statement. . (In Lakhs)
2023-24 Pls Select 'Yes','No' for Annual financial turn over for all the 3 years
Average 0.00 FALSE
Balance sheet and Profit & loss statement for last 05 years
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
raw.json
RAW_JSON
TN42.pdf
TENDER_DOCUMENT • 1.11 MB
93Undertaking2.pdf
TENDER_DOCUMENT • 0.57 MB
ACdrawing02.pdf
TENDER_DOCUMENT • 0.58 MB
93PBF.xlsm
TENDER_DOCUMENT • 0.14 MB
AMD.pdf
TENDER_DOCUMENT • 0.21 MB
FINALELECTRICALDRAWING.pdf
TENDER_DOCUMENT • 0.36 MB
93PB.pdf
TENDER_DOCUMENT • 0.66 MB
Electricaldrawing01.pdf
TENDER_DOCUMENT • 0.26 MB
Electricaldrawing02.pdf
TENDER_DOCUMENT • 0.47 MB
SLD1.pdf
TENDER_DOCUMENT • 0.11 MB
SLD2.pdf
TENDER_DOCUMENT • 0.02 MB
93TBF.pdf
TENDER_DOCUMENT • 6.15 MB
93PQ.pdf
TENDER_DOCUMENT • 0.20 MB
TenderDrawing.pdf
TENDER_DOCUMENT • 0.58 MB
93ECSForm.pdf
TENDER_DOCUMENT • 0.48 MB
ACdrawing01.pdf
TENDER_DOCUMENT • 0.56 MB
93PQF.xlsm
TENDER_DOCUMENT • 0.04 MB
93Checklist.pdf
TENDER_DOCUMENT • 0.19 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .