Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹21.7 LAccepted-AOC 58 CHANDRALOK BUILDING MAYO HOSPITAL ROAD NAGPUR 440 018 | NAGPUR | MAHARASHTRA | 440018 | L1 | Accepted-AOC Lowest | |
| 2 | L2₹23.3 L+₹1.4 L (6.38%)Rejected-Finance | L2 | Rejected-Finance Not Lowest | |
| 3 | L3₹24.9 L+₹3.0 L (13.7%)Rejected-Finance 58 CHANDRALOK BLDG MAYO HOSPITAL ROAD NAGPUR 440018 | NAGPUR | NAGPUR | MAHARASHTRA | 440018 | L3 | Rejected-Finance Not Lowest |
Tender Value
₹27.2 L
EMD Value
₹54,360
Closing Date
1 May 2025, 6:00 pmClosed
Garrison Engineer
Military Engineer Services, Garrison Engineer, Kamptee 441001
MAINT AND REPLACEMENT OF LT PANEL, REPAIR . REPLAEMENT TO LT UG CABLE, MAINT OF STREET LIGHT / FOOD LIGHT / SOLAR LIGHT ALONGWITH TIMER, MCCBS, MAINT OF RCC / STEEL POLES, PAINTING OF LT --- R LINE AND CERTAIN LOCATIONS UNDER GE KAMPTEE
2025_MES_703473_1
8756/E8
Open Tender
Civil Works
Item Rate
180 days
Kamptee
All as per tender douments
8 documents required · 8 mandatory
₹500
GE Kamptee
₹54,360
Yes
23 May 2025
3 Apr 2025
3 May 2025
3 Apr 2025
1 May 2025
17 Apr 2025
Amount
Taking down the unserviceable LT cable of any size from tranches/ walls /floor etc complete all as specified and as directed. Note :- laying of cable route is same as old cable route .
Supply and laying in trenches or fixing in walls / poles or drawing through pipe XLPE insulated, screened, PVC bedded, galvanised steel strip, electric armoured power cables (heavy duty) with aluminium conductor, 1100 volts, grade cross sectional area 95 Sqmm, 3.5 core including testing after laid and jointed all as specified and as directed Make :- KEI/ Polycab/Havells/Finolex Note:- Excavation and earth work, cable protection shall be measured and paid separetely.
All as per item No. 2 but cable size 70 Sqmm 3.5 core all as specified and as directed.
All as per item No. 2 but cable size 16 Sqmm 4 core all as specified and as directed.
All as per item No. 2 but cable size 10 Sqmm 4 core all as specified and as directed.
Excavation in trenches in soft/loose of soil not exceeding 1.5 meter wide and not exceeding 1.5M in depth for laying of Cables, poles, stay and getting out of excavated material complete all as specified and directed.
Returning, filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25cm thick each, excavated soil in trenches after the cables have been laid and tested complete all as specified and directed.
Removal of surplus soil to a distance not exc. 50m and deposited where directed at a level not exc. 1.5 m above the starting point all as specified and as directed .
Supply and fix in repair Double wall Corrugated High Density Polymer Ethyl (HDPE) pipe For laying of Electric cable of size 90 mm outer diameter and 75 mm inner Diameter with IS 16285 (part 2):2001 laid in trenches, wall, floor, pole including bends, sockets and other connected accessories complete all as specified and directed. Make:- Tirupati / Ketron
Supply and fix in repair Double wall Corrugated High Density Polymer Ethyl (HDPE) pipe For laying of Electric cable of size 63 mm outer diameter and 51 mm inner Diameter with IS 16285 (part 2):2001 laid in trenches, wall, floor, pole including bends, sockets and other connected accessories complete all as specified and directed. Make:- Tirupati / Ketron
Supply and fix in repair Double wall Corrugated High Density Polymer Ethyl (HDPE) pipe For laying of Electric cable of size 50 mm outer diameter and 38 mm inner Diameter with IS 16285 (part 2):2001 laid in trenches, wall, floor, pole including bends, sockets and other connected accessories complete all as specified and directed Make:- Tirupati / Ketron
Material and labour for testing the cables with high voltage DC testing machine and locating the fault in the cables by fault locating machine to pin point exact position of fault, disconnecting faulty 1100 Volt LT cables of different sizes from both ends, removal of Fault, Re-connections and testing of cables after removal of fault complete all as specified and directed. Notes : (i) All T&P and other accessories required for checking and finding of fault in cable shall be provided by the Contractor (ii) Charges/rent of the fault locating mobile machine, operator, engineer, electricians etc shall be deemed to included rate quoted by Contractor. (iii) Checking and finding fault upto 05 places of same route of the cable will be considered as one Job.
Supply and fix in repair Heat shrinkable straight through cable jointing kit for 1100 Volts grade cable joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 120 Sqmm to 240 Sqmm. Note :- Any Excavation and earth work, Returning and filling, Removing involved shall be measured and paid separately. Make :- Densons / M-Seal / Raychems
All as per item No. 13 but cable size 70 Sqmm to 95 Sqmm all complete as specified and directed.
All as per item No. 13 but cable size 10 Sqmm to 50 Sqmm all complete as specified and directed.
Supply and fix in repair LED street light luminaires of capacity 60 watts with pressure die cast aluminium housing heat resistance toughened glass, IP 66 protection and efficacy minimum 120 Lumen per watt, complete with driver, including three core copper flexible wire of size 0.75 Sqmm for connection from street light fitting to OH line or junction box, fixing accessories and complete all as specified and directed by Engr -in- charge. Make :- Bajaj / Philips / Crompton / Havells
S&F in repair LED driver for 60W LED street light fittings complete all as specified and as directed. Make :- Bajaj / Philips / Crompton / Havells or other OEM approved make.
S&F in repair LED driver for 45W LED street light fittings complete all as specified and as directed. Make :- Bajaj / Philips / Crompton / Havells or other OEM approved make.
Supply and fixing in replacement LED flood light 200 watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp complete, including three core copper flexible wire of size 1.50 Sqmm for connection from street light fitting to OH line or junction box, with taking down old unserviceable flood light complete all as specified and directed by Engineer -in -charge. Make :- Bajaj / Philips / Crompton / Havells
Supply and fixing in replacement LED flood light 100 watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp complete, including three core copper flexible wire of size 1.50 Sqmm for connection from street light fitting to OH line or junction box, with taking down old unserviceable flood light complete all as specified and directed by Engineer -in -charge. Make :- Bajaj / Philips / Crompton / Havells
Supply and fix in repairs thermoplastic cable entry junction boxes of size 250 x 220 x 135 mm and IP-65 protection level with metric knock out fixed on poles with MS clamps, nuts, bolts and washers including MCB SPN, 5-32 amps, 'C' series, breaking capacity 10 KA, 'C' curve 240 volts, 50Hz including necessary incoming and outgoing electric connection with suitable size of copper lugs etc., separate (detachable) gland plate, bakelite connector 4 way 20 amp, dust and vermin proof, front door opening with hinges and locking arrangement, complete all as specified and as directed. Make:- Sintex/Hensel or equivalent
Supply and fix in repair bracket for street light fittings made out of 32 mm dia GI pipe of light grade 1.5 m long each bent to shape & size required & fixed to pole with and including flat iron clamps 02 Nos made out of 30 x 5 mm flat iron including GI Nuts, bolts and washers and painting of clamps and street light brackets with two coat of aluminium paint over a coat of red oxide primer and fittings bracket to street light fitting including taking down old unserviceable bracket of any shape and size all as specified and as directed.
S&F in renewal MCCB 63 Amps, 4 Pole, 415V, 50 Hz, Adjustable type, with breaking capacity 16 KA, Ics=100% of Icu, including taking down of old unserviceable MCCBs complete all as specified and directed. Make : Legrand / L & T / ABB
S&F in renewal MCCB 100 Amps, 4 Pole, 415V, 50 Hz, Adjustable type, with breaking capacity 25 KA, Ics=100% of Icu, including taking down of old unserviceable MCCBs complete all as specified and directed. Make : Legrand / L & T / ABB
S&F in renewal MCCB 125 Amps, 4 Pole, 415V, 50 Hz, Adjustable type, with breaking capacity 25 KA, Ics=100% of Icu, including taking down of old unserviceable MCCBs complete all as specified and directed. Make : Legrand / L & T / ABB
S&F in renewal MCCB 160 Amps, 4 Pole, 415V, 50 Hz, microprocessor release based type, with breaking capacity 36 KA, Ics=100% of Icu, including taking down of old unserviceable MCCBs complete all as specified and directed. Make : Legrand / L & T / ABB
S&F in renewal MCCB 200 Amps, 4 Pole, 415V, 50 Hz, microprocessor release based type, with breaking capacity 36 KA, Ics=100% of Icu, including taking down of old unserviceable MCCBs complete all as specified and directed. Make : Legrand / L & T / ABB
S&F in renewal MCCB 250 Amps, 4 Pole, 415V, 50 Hz, microprocessor release based type, with breaking capacity 36 KA, Ics=100% of Icu, including taking down of old unserviceable MCCBs complete all as specified and directed. Make : Legrand / L & T / ABB
S&F in renewal MCCB 320 Amps, 4 Pole, 415V, 50 Hz, microprocessor release based type, with breaking capacity 36 KA, Ics=100% of Icu, including taking down of old unserviceable MCCBs complete all as specified and directed. Make : Legrand / L & T / ABB
S&F in renewal MCCB 400 Amps, 4 Pole, 415V, 50 Hz, microprocessor release based type, with breaking capacity 36 KA, Ics=100% of Icu, including taking down of old unserviceable MCCBs complete all as specified and directed. Make : Legrand / L & T / ABB
Supply, erecting & fixing in replacement of steel tubular swaged pole complete with base plate, pole cap, nut bolt washer etc type 410 SP-31 (9.00 meters long) swaged poles conforming to IS 2713 (Part-I to III) 1980 all as specified including two coats of black bitumen paint through out internally and externally upto planting depth and applying two coats of aluminum paint over one coat of red oxide primer (externally) and Numbering of poles as directed including excavation /earth work, PCC 1:4:8 type D-2 using 40mm aggregate for pole foundations of size 600x600x1500mm height upto ground level and using PCC 1:2:4 B-1 for coping with size 450x450x300mm including necessary formwork complete with including taking down old unserviceable pole all as specified and as directed.
Materials and labour as in replacement for earthing complete with galvanized earth plate electrode 600 x 600 x6mm thick burried directly in ground vertically to a depth not less than 2.25 M below normal ground level ) with top edge of the plate not less than 1.50 M below normal ground level , connected to and including GI wire 4.0 mm as earth lead soldered and riveted to earth plate by means of nuts, bolts, check nuts & washers, of galvanized iron or steel with connected to test point and testing on completion including 40mm GI light grade pipe for earth lead protection from earth point to earth plate, including provn adequate quantity of charcoal dust mixed with 35 % common salt to a packed thickness of not less than 32 cm in alternate layers of charcoal and salt on all sides of earth plate with 20mm bore medium grade GI Pipe for watering,GI check nut, funnel and wire mesh with and including all necessary excavation & earth work in soft/loose soil, returning filling in, removal of surplus soil to a distance 50 metre, PCC 1:3:6 type C-1 as in earth pit, 40 mm thick RCC cover using cement concrete 1:2:4 type B-1 reinforced with & including 8 mm dia mild steel TMT bar @ 100 mm c/c Both way with suitable handle for lifting arrangement & including form work complete all as specified and shown in electrical plate No 3 of MES SSR Part I 2009 and as directed. NOTES:- (a) On testing, after completion of Job, if desired earth resistance is not obtained, the earthing shall be redone at without any extra cost by contractor.
Materials and labour as in replacement for earthing complete with galvanized steel earth plate electrode 600x600x6mm thick buried directly in ground vertically to a depth not less than 2.25m below ground level with top edge of earth plate not less than 1.5m below ground level connected to galvanized iron earth strip 32 x 6 mm by means of bolts, nuts, check nuts, washers of galvanized iron and connected to main switch/control board upto 7.5m away from the earth electrode including excavation earth work, PCC chamber, RCC cover slab char coal, watering pipe, wire mesh lugs, earth lead protection pipe 40 mm bore, light grade 7.5m long as applicable and as per plate No. 3 of SSR 2009 and all as specified. (a) Excavation and earth work in any type of soil. (b) Drilling of holes in electrode (c) PCC pit in cement concrete (1:2:4) type B-1 (d) 40 mm thick Pre-cast RCC cover with suitable handle. (e) Funnel with watering pipe of GI 20 mm nominal bore ,medium grade & copper lug etc. (f) 40 mm nominal bore medium grade GI protection pipe 7.50 m long for protection of earthing lead. (g) Requisite quantity of charcoal and common salt. (h) Connection to earthing test point and testing on completion.
Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 32x6 mm GI strip complete all as specified and directed.
Supply and fixing in repair retro reflective boards in shape of rectangle of size 1.0 m x1.4 m made out of 2 mm thick stainless steel both side bounded/pasted with high prismatic (iv) sheet mannufactured by avery dennison or 3 M with desired letters/logos designed as directed the board shall be supplied with and including stainless steel frame made out of 25 mm dia pipe in frame around duly welded with and including stainless steel sheet and stainless steel posts of 38 mm dia and full length of 2.20 m one side and 2.8 m other side complete all as specified and directed. ( Note :(i) Rate for fixing of boards with PCC 1:2:4 type B2 filling of size 45x45x60 cm to be incl in unit rate. (ii) The board should be written description as direction given by Engineer-in-Charge)
Supply and fixing in replacement 1100 volts grade heavy duty cable PVC insulated aluminium conductor, 4 sqmm 2 core, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 metre apart including 4mm suspension wire. Make :- Havells / Polycab / KEI / Finolex
Supply and fixing in replacement 1100 volts grade heavy duty cable PVC insulated aluminium conductor, 6 sqmm 2 core, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 metre apart including 4 mm suspension wire. Make :- Havells / Polycab / KEI / Finolex
Supply and fixing in replacement 1100 volts grade heavy duty cable PVC insulated aluminium conductor, 10 sqmm 2 core, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 metre apart including 4 mm suspension wire. Make :- Havells / Polycab / KEI / Finolex
S & F in replacement 1100 Volts grade Copper conductor, PVC insulated, round sheathed (flexible), industrial cable, 1.5 sqmm 3 core. Make :- Havells / Polycab / KEI / Finolex
S&F in replacement ONLOAD Changeover switch 160 Amps, 4 Pole, 415 V in sheet steel enclosure suitable for fixing on wall at existing position, including with all incoming and outgoing connection with cable lugs, washers, nutbolts and accessories complete with taking down old unserviceable changeover switch all as specified and directed. Make - L&T/Legrand/Havells/
S&F in replacement ONLOAD Changeover switch 100 Amps, 4 Pole, 415 V in sheet steel enclosure suitable for fixing on wall at existing position, including with all incoming and outgoing connection with cable lugs, washers, nutbolts and accessories complete with taking down old unserviceable changeover switch all as specified and directed. Make - L&T/Legrand/Havells/
S&F in replacement ONLOAD Changeover switch 63 Amps, 4 Pole, 415 V in sheet steel enclosure suitable for fixing on wall at existing position, including with all incoming and outgoing connection with cable lugs, washers, nutbolts and accessories complete with taking down old unserviceable changeover switch all as specified and directed. Make - L&T/Legrand/Havells
Supply, fixing and testing in replacement of Automatic Street light Timer Switch using combination of NATURE SWITCH for automatic switching of street lights based on LUX level of natural light consisting with Sensor (Natural Switch) along with suitable power contractor, MCB and support terminals should be enclosed in pole/ wall mountable SMC enclosure made out of Rust proof, Electric shock proof, termite proof and FR grade SMC junction Box conforming to IP 54 protection of capacity 12 KW 3 phase, current range 40 Amps, 4 wire (3 separate power contactor) including all accessories and fixing arrangement all as specified and directed. Model No. Swadeep - 02EC-8kW3P.
Supply and fixing in replacement of Contactor of type MU-2P series (rating 16 A / 25A / 40A) suitable for existing Automatic Street light Timer Switch complete with taking down old unserviceable Contactor all as specified and as directed. Make - L&T/ BCH
Supply and fixing in replacement of Contactor of Freedom series, 3 pole (rating 18 A / 25A / 40A) suitable for existing Automatic Street light Timer Switch complete with taking down old unserviceable Contactor all as specified and as directed. Make - L&T/ BCH
Supply and installation, testing & commissioning self-supporting totally enclosed factory fabricated LT bus Each bar panel box made out of 3.15mm thick MS sheet with projected globe roof for rain water protection, dust and vermin proof hinged double shutter doors with neoprene rubber gasket epoxy powder coated including danger plate, earth strip, ventilation louvers, bottom detachable gland plate complete with suitable size zinc chromium plated nuts, bolts, and washers etc outdoor type cubicle panel board suitable for 3 Feeder phase 4 wire 415 volt 50 HZ and 40 mm x 40 mm x 6 mm angle iron frame, weather proof ventilated with locking arrangement incl of PCC pedestal, accommodate and consisting of the following items :- (i) Aluminium bus-bar 600 Amps, supported with suitable size Porcelain stand lock with suitable size brass nut, bolts and washers with heat shrinkable colour coded PVC sleeving for 3 phase & neutral . - 01 Set (ii) MCCB with Thermal Magnetic Release (Manual Fixed type) , 4 pole, 400Amps, 36 KA, 415 Volts, 50 Hz Adjustable - 01 No.
M&L for drilling suitable dia horizontal bore holes for insertion/ laying of upto 110mm bore HDPE pipe/GI pipe of any description below/under existing road surfaces/apron /floors etc with using mechanical and / or manual devices as required at site including making good the disturbed surfaces to match with the existing strata after laying pipes complete all as specified and directed. (NOTE : (i) Pipes shall be laid minimum 60 cm below/under existing road surfaces/ apron /floors etc). (ii) Equipment, tools and plant material (horizontal boring rig machine) required for boring shall be arranged by contractor without any extra cost to the Govt.
Supplying and fixing in replacement of HDPE Pipe, 90 mm bore (PN 10), suitable for insertion in horizontal boring for protection of cable / croossing of cable, complete all as specified and directed.
Material and labour for cable route indicator made out of PCC (1:2:4) type B1 of size 60cm x 15cm x 5cm thick grouted in PCC (1:2:4) type B1 pillar fo size 30 cm x 30 x 45 cm in ground with and including necessary foam work and making on board 1100 Volt LT Cable with arrow indicating cable path (marking shall be engraved and colour painted), complete all as specified and directed.
M&L for preparing surfaces of electric poles of any type of following sizes including MS cross arms, MS clamps, street light brackets, bracket clamps, cable protection pipe stay etc of any sizes and shape & dusting, cleaning the surface complete and applying one coat of primer and two coat of aluminium paint completely, alternate layer of yellow and black paint of 150 mm strip at the bottom of pole 1.5 mtr above coping with synthetic enamel paint all as specified and as directed by Engineer-in-Charge. (a) Height of rail /tubular poles exceeding 7.5 Mtrs upto 11 Mtrs above ground level.
All as per item No. 50 but height of steel tubular poles 7.5 Mtrs above ground level .
M&L for preparing surfaces of electric poles of RCC type of any sizes including MS cross arms, MS clamps, street light brackets, bracket clamps, cable protection pipe stay etc of any sizes and shape & dusting, cleaning the surface complete and applying one coat of primer and two coat of weather proof paint completely and alternate layer of yellow and black synthetic enamelled paint of 150 mm strips at the bottom of pole 1.5 mtr above coping all as specified and as directed by Engineer-in-Charge.
M&L for preparing surfaces of electric Two pole Structures of any make and height of pole up to 10 Mtrs above ground level including MS cross arms, AB Switch pipe, DO Fuse assembly, MS clamps, brackets, bracket clamps, cable protection pipe stay etc of any sizes and shape & dusting, cleaning the surface complete and applying one coat of aluminium paint completely as directed by Engineer-in-Charge.
M&L for preparing surfaces of electric Four pole Structures of any make and height of pole up to 10 Mtrs above ground level including MS cross arms, AB Switch pipe, DO Fuse assembly, MS clamps, brackets, bracket clamps, cable protection pipe stay etc of any sizes and shape & dusting, cleaning the surface complete and applying one coat of aluminium paint completely as directed by Engineer-in-Charge.
M&L for writing pole No. with letters of size 25 mm height on pole/ plate with Black synthetic enamelled paint complete all as specified and directed.
M&L for cleaning and removal of disintegrated & deteriorated paint by hand scrapping and preparation of of old painted exposed surfaces of Chain link fencing of 11 KV Sub Stn incl gate etc and applying two coat of aluminium / Synthetic enamel paint over a coat of a red oxide all around the exposed chain link fencing, compete all as specified and directed.
M&L for Spray painting to existing LT Panel of any capacity / size / type including mounting angle with two coats of approved colour synthetic enamel paint complete including dusting, cleaning of existing dust before applying synthetic enamel paint and writing feeder name with approved colour synthetic enamel paint complete all as specified and directed.
Cleaning of sub station area by uprooting all types vegitation, shrubs, weeds, saplings and creepers of unwanted trees complete with the help of spade, axes, crowbars, and thereafter chemical spraying will be done and other mechanical means after taking necessary electrical shutdown from concerned incharge of various sub stns of Military Stn Kamptee.
Trimming of tree branches touching of Over head Electrical Lines upto 2.5 mtr distance from conductors after taking necessary shutdown from concerned incharge all as directed . (Note : Space between two poles will be measured as distance in RM irrespective of nos of conductors).
Taking down the unserviceable APFC Panel / LT Panel / feeder pillar of any size complete with all accessories all as specified and as directed.
item No. 61Contd../- The APFC controller should have Auto on/off capacitor banks in the step of (2x1+3x1+5x1+10x1+20x4) KVAR MPP-H capacitor banks rating and accessories are as under :- i) Power capacitor for two branch 01 No of capacity 2 KVAr each ii) Power capacitor for two branch 01 No of capacity 3 KVAr each iii) Power capacitor for two branch 01 No of capacity 5 KVAr each iv) Power capacitor for three branch 01 No of capacity 10 KVAr each v) Power capacitor for three branch 4 Nos of capacity 20 KVAr each vi) Switching device for 2 KVAr capacitor Branch = MO C5 (1 NO aux contacts for each branch) vii) Switching device for 3 KVAr capacitor Branch = MO C 20 (1 NO aux contacts for each branch) viii) Switching device for 5 KVAr capacitor Branch = MO C15 (1 NO aux contacts for each branch) ix) Switching device for 10 KVAr capacitor Branch = MO C12.5( 1 NO aux contacts for each branch) x) Switching device for 20 KVAr capacitor Branch = MO C12.5( 1 NO aux contacts for each branch) xi) Accessories for switching device = 1 Normally closed + normally opened side add-on lock for each Branch xii) protection for each branch tripple pole MCB of rating not less than 2 times the charging current of indiusal stage. xiii) APFC microprocessor Controller = 5 Star APFC Relay
All as per item No 61 here-in-before but for the APFC panel 240 KVAR panel with Incommer MCCB 400 Amps, 35 KA, 4 pole, contactor suitable for capacitor rating &MPP-H capacitor banks. The APFC controller should have Auto on/off capacitor banks in the step of (5x1+10x1+25x1+50x4) KVAR MPP-H capacitor banks rating and accessories are as under :- i) Power capacitor for two branch 01 No of capacity 5 KVAr each ii) Power capacitor for two branch 01 No of capacity 10 KVAr each iii) Power capacitor for two branch 01 No of capacity 25 KVAr each iv) Power capacitor for three branch 4 Nos of capacity 50 KVAr each v) Switching device for 2 KVAr capacitor Branch = MO C5 (1 NO aux contacts for each branch) vi) Switching device for 3 KVAr capacitor Branch = MO C 20 (1 NO aux contacts for each branch) vii) Switching device for 5 KVAr capacitor Branch = MO C15 (1 NO aux contacts for each branch) viii) Switching device for 10 KVAr capacitor Branch = MO C12.5( 1 NO aux contacts for each branch) ix) Switching device for 20 KVAr capacitor Branch = MO C12.5( 1 NO aux contacts for each branch) x) Accessories for switching device = 1 Normally closed + normally opened side add-on lock for each Branch xi) protection for each branch tripple pole MCB of rating not less than 2 times the charging current of indiusal stage. xii) APFC microprocessor Controller = 5 Star APFC Relay
Supply and fix including testing and commissioning of 50 A / 415 volts, 3 phase AHF Panel (Active Harmonic Filter and Automatic Load Balancer) as per IEEE 519-2014, Power factor compensation 100% (Lead / Lag), Load Balancing : Negative Sequence Compensation (Zero Sequence compensation in 4 P / 4 W range), Reaction time: <0.3 ms, Interface (Communication) GSM, MODBUS RTU, USB, Ethernet, Profibus Compatible, IP-65, air cooling, overheating protection including necesary excavation and foundation work, complete all as specified and directed. Make : Havells HSN Code No. 8543 or equivalent in L&T/Schneider
NOTE:- SCHEDULE OF CREDIT (Amount shall be deducted offline from the total quoted amount to workout the net contract sum to be considered for acceptance.) [(-) Rs. 38,865.00]
Chinmaya Enteprises (BID ID -3290175)
Paragon Electrotechnics (BID ID -3290402)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .