Tender Value
₹3.0 L
EMD Value
₹6,100
Closing Date
18 Aug 2023, 4:00 pmClosed
Ex Engineer ED-1st Srinagar
Office of the Ex Engineer ED-1st Srinagar BASANT BAGH
Creation of 100KVA, 11kV / 433V, 3-Phase, sub station at NPL Bund
2023_PDD_223231_1
EDI No 038 of 2023-24
Open Tender
Electrical Works
Lump-sum
15 days
SRINAGAR
Please refer Tender documents.
5 documents required · 5 mandatory
₹200
Yes
Ex Engineer ED-1st Srinagar
₹6,100
Yes
22 Aug 2023
24 Jul 2023
19 Aug 2023
24 Jul 2023
18 Aug 2023
24 Jul 2023
24 Jul 2023 - 25 Jul 2023
Installation, testing and commissioning of 11/0.433kV, 3-phase 100KVA Distribution Transformers with Bimetallic Terminal Connectors Energy Level-2, and with LV Cable Box having detachable Al Gland plate. Transformer should have arrangement for vertical take off. [Transformer provided by LCMA]
Supply, Loading, Transportation, insurance, Unloading, Carriage and Delivery at Site and erection of 9 Mtr. Long ST Poles with pit excavation [IS 2713 410 SP 33]
Supply, Loading, Transportation, insurance, Unloading, Carriage and Delivery at Site and Laying of 0.05 ACSR Conductor
Supply,installation, testing and commissioning of 11kV G.O. AB Switch 3-Phase, 3-Pole 200A Vertical Type.
Supply,installation, testing and commissioning of Gapless Surge Arrestor, 9kV, 10KA LA with polymer housing, station type.
Supply,installation, testing and commissioning of 11 kV Horn Gap Fuse Set 3 Phase 200A
Supply,installation, testing and commissioning of 11kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Providing and fixing of GI i). Channel iron (100x50x6)mm 8ft long 2No's alongwith braces 2).Channel iron (75x40x6)mm 8ft long 6No's alongwith braces 3)Channel iron (75x40x6)mm 6ft long 2No's alongwith braces 4)Angle Iron belt for Transformer (50x50x6)mm 5ft long 2 No
Providing and fixing of Galvanized Nuts & Bolts of size
Providing and fixing of Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6) mm, nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete.
Supply,installation, testing and commissioning of LT Distribution Box for 100 kVA DTR with 160 Amp MCCB 3P 16 kA for incomer & 100 Amp MCCB 3P 16 kA 2 No.s for Outgoing Circuits.
Providing and fixing of Aluminium thimbles
Supply,installation, testing and commissioning of SL Clamps of Sizes
Supply,installation, testing and commissioning of 120 mm² AB (LT) Cable ( 3 x 120 + 1 x 25 + 1 x 95) mm² XLPE (1.1kV, 3+1 C, Al). (Polycab / Gloster / Havells or equivalent)
Supply,installation, testing and commissioning of Straight Through Cable Jointing Kit
Supply,installation, testing and commissioning of Insulating Piercing Connectors
Providing and laying of Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover.
Providing & fixing of Earthing Complete by GI Pipe 40 mm 3mtr long through GI Strip 25x3 mm
Providing and painting of 8/9 Mtr ST poles with two coats of red oxide and two coats of aluminium paint
Providing and laying of Cement Bottoming in 1:2:4 mix 0.5 cum per pole
Laiba electrical Suppliers and mechanical work
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .