Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance 1 SHAKTI NAGAR JAMMU JAMMU KASHMIR 180001 | JAMMU | JAMMU AND KASHMIR | 180001 | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance | Admitted-Finance |
Tender Value
₹11.1 L
EMD Value
₹22,500
Closing Date
2 Nov 2024, 4:00 pmClosed
XEN MECHANICAL AND HOSPITAL DIVISION JAMMU
XEN MECHANICAL AND HOSPITAL DIVISION JAMMU
DESIGN, SUPPLY, INSTALLATION, TESTING, COMMISSIONING OF FIRE ALARM SYSTEM WITH ALLIED WORKS AT BOYS HOSTEL OF GOVT AYURVEDIC COLLEGE AND HOSPITAL, AKHNOOR, JAMMU.
2024_PWDJK_261094_1
MHDJ/e-NIT 126 of 2024-25
Open Tender
Machineries/ Mechanical Engg Items
Turn-key
20 days
Ayurvedic College Hospital Akhnoor Jammu.
as per e nit
2 documents required · 2 mandatory
₹1,000
XEN MECHANICAL AND HOSPITAL DIVISION JAMMU
₹22,500
16 Dec 2024
18 Oct 2024
4 Nov 2024
18 Oct 2024
2 Nov 2024
25 Oct 2024
18 Oct 2024 - 2 Nov 2024
Amount
SITC of 1 Loop Analogue Addressable Fire Alarm Control Panel expandable up to 2 Loop, loop current 500mA maximum per loop, dual flash based microprocessor, supports to connect 240 addressable devices one each loop via fully digital communication protocol, equipped with a white backlit display (240x64 pixel resolution) graphical LCD Display with at least 6 lines of information, 200 fire zones (soft zones), fully programmable via alphanumeric keypad or configuration software, dedicated USB and RS-232 serial port for direct or PC connection. 5500 events storage, loop current 500 mA, panel shall be equipped with in-built multimeter for live monitoring of loop current, earth voltage, loop voltage etc., installer's logo application, can be networked to compatible addressable panels and repeater panels by adding a network card, features battery charger status and temperature, supports programmable cause/effect on outputs, panel housing meets IP30 ingress protection classification. Make: - GST/Honeywell/Apollo or any other reputed make.
SITC of Intelligent Analogue Optical Smoke Detector with base mounting with advanced optical chamber and smoke inlet design to provide resistance to entry of dust to provide immunity to false alarms, programmable multiple smoke sensitivity level setting, bi-directional in-built short circuit isolator to protect against cable faults, dual bi-colour LED's with 360o view of status, auto-addressable/electronically addressed, utilizes fully digital communication addressable protocol with high noise rejection. Approved by LPCB for EN 54-7 & EN 54-17 standard. Make: - GST/Honeywell/Apollo or any other reputed make.
SITC of Intelligent Analogue Multi-Criteria (combination of smoke and heat) Detector with Base and special algorithms to utilize information from both smoke and heat sensing elements to ensure high level of immunity to false alarms without compromising genuine alarm sensing performance, programmable multiple smoke sensitivity level and 9 modes of operation, bi-directional in-built short circuit isolator to protect against cable faults, dual bi-colour LED's with 360o view of status, auto- addressable/ electronically addressed, utilizes fully digital communication addressable protocol with high noise rejection. Approved by LPCB for EN 54-5, EN 54-7, & EN 54-17 standard. Make: - GST/Honeywell/Apollo or any other reputed make.
SITC of Intelligent Analogue Class-P Heat Detector with Base and two thermal sensitivity level, the two level corresponds to rate-of-rise (ROR) A1R Class (most sensitive) and Class BS (least sensitive), thermal alarm threshold for ROR A1R Class 58oC and BS Class 58oC, bi-directional in-built short circuit isolator to protect against cable faults, dual bi-colour LED's with 360o view of status, auto-addressable/electronically addressed, utilizes fully digital communication addressable protocol with high noise rejection. Approved by LPCB for EN 54-5 & EN 54-17 standard. Make: - GST/Honeywell/Apollo or any other reputed make.
SITC of Intelligent Sounder Interface Module allows to connect conventional Sounder or Sounder Beacon to addressable loop Beacon to addressable loop, with in-built short circuit isolator, allows for two stage alarm capability, addressed through auto and manual options. Approved by LPCB for EN 54-17 & EN 54-18 standard. Make: - GST/Honeywell/Apollo or any other reputed make.
SITC of Intelligent Analogue Manual Call Point with resettable operating element, with in-built bidirectional short circuit isolator. Bi-Colour LED for local indication of device status, single action operation, reset to normal condition using special reset key, clearly visible alarm flag in the activated state. Approved by LCPB for EN 54-11 standard5dBm (3mW), enabled with 7 operating frequency channels for bi-directional wireless communication, operating frequency range 865MHz, IP 65 rated. Approved by LPCB for EN 54-18 and EN 54-25 standard. Make: - GST/Honeywell/Apollo or any other reputed make.
SITC of Single Loop Driver Card designed for use with compatible analogue addressable panels, provides control and connection/ communication to maximum 240 addressable devices per loop. Make: - GST/Honeywell/Apollo or any other reputed make.
SITC of Mounting Accessories like back box for detectors, devices & cable glands, etc.
Supplying and laying of 2C x 1.5 Sq.mm PVC insulated copper conductor armoured cable encased inside (by providing and laying) 1.5” dia PVC insulated conduit/pipe along with fittings and fixtures. Complete Job includes cost of material (PVC conduit, Cu Cable). labour and transportation. Make: - Gloster/Polycab/Havells or any other reputed make.
The Job also includes providing and fixing of Fire auto glow signage with printed “IN CASE OF FIRE, USE STAIR UNLESS INSTRUCTED OTHERWISE” in stickers/acrylic sheet from on boards made out of 03 mm thick PVC foam board of 1.5 cm height letters in Red With White back ground for whole building. The size of the board shall be 25 cm x 30cm and shall fix at a height of 02 mtr. from finished floor near manual call points.
Providing and Fixing of the Fire Notice, Fire Order, Exit Sign, Floor No’s to be displayed at required places as per requirements of NBC Part –IV.
Fabrication of CGI Sheet (Coloured Sheet) Shed for safeguarding of firefighting pumping equipments by way of bush cutting, cleaning the site by removing unwanted material for erection of CGI shed. Job includes providing, fitting and erection of CGI Sheets on the angle Iron frame of size 12’ x 10’ x 08’ in the rectangular shape by welding 40 mm x 40 mm x 06 mm MS angle iron lengths to make a rectangular shed for installation of electro-mechanical equipments. The angle iron frame to be supported by adequate vertical length of angle iron with a height of 08’ from the floor of the shed with provision of a gradual slanting slope for easy flow of water during rains. Providing and fitting of the vertical frames of steel channels in four corners of shed to be embedded with a cement concrete mix of 1:2:4 ratio after laying of cement concrete plinth 01 feet below ground level and 01 feet above ground level. CGI Sheets of approximate size to be fixed on the angle iron frame horizontally and vertically with the help of hooks and nuts to make it complete water proof. Fabrication of angle iron door frame of 6’x4’ size of angle 40 mm x 40 mm x 06 mm with CGI Sheet fixed on the angle iron door at the front side of the shed for entry. Fabrication of 01 no window of suitable size for proper ventilation with angle iron frame and CGI Sheet fixed on the window angle frame. Providing, fitting and welding appropriate number of support of angle iron lengths for proper strengthening and durability of the shed. Laying the cement concrete flooring in the ratio 1:2:4 after filling of malba up to the required floor level and compacting the earth surface within and around the shed. Also providing of proper drainage around the shed by compacting and concreting the sides outside the shed for easy flow of water. Painting of the shed with superior quality enamel paint. Electrification of the CGI shed by providing and fitting of LED Bulbs with holders – 02 No each; Gang Box with 16 Amp socket – 02 no and ON OFF switches complete job is executed by providing and laying of copper cable, PVC pipe and other allied accessories. Job includes providing and fitting of – 02 no Turbo Ventilator fans on the top of the shed. The job includes cost of material, charges for all types of skilled and unskilled labour along with tools and tackles including the cost of miscellaneous item/parts used during execution of job.
Earthing:- Suitable chemical earthing for all Fire Fighting Electro-mechanical equipments by way of Chemical Earthing including job of making pit of suitable size for chemical earthing. The job includes earth work by using labour for making pit of suitable size for proper earthing and after that laying Copper rod of suitable size (3 mtrs approx.) and filling the pit with chemical (Chemical Earthing). Job also includes clamping the copper rod with the copper strip of size (20 x 3 mm) with nut and bolts. Complete job includes cost of Copper rod, Copper Strips and Copper wire, chemical and other related material and cost of labour charges (02 No Earthing).
CYBER INFOTECH SERVICES (BID ID -2207899)
Dogra and Dogra Enterprises (BID ID -2207637)
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .