Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹22.1 LAccepted-AOC H NO 90 VILLAGE REWLA KHANPUR PO NAJAFGARH NEW DELHI 110043 | NEW DELHI | WEST DELHI | DELHI | 110043 | L1 | Accepted-AOC Being L1 | |
| 2 | L2₹32.4 L+₹8.6 L (35.9%)Rejected-Finance | L2 | Rejected-Finance Being L2 |
Tender Value
₹40.5 L
EMD Value
₹81,000
Closing Date
28 Jul 2022, 6:00 pmClosed
Col Jiagar Trivedi, SM
HQ CWE (AF) Gurgaon Old Palam Road Delhi Cantt - 10
REPAIR AND PERIODICAL MAINTENANCE OF MAIN SUPPLY/DISTRIBUTION SYSTEM OF HT LINES, TRANSFORMER, VOLTAGE STABILZERS, APFC PANELS AND ALLIED WORKS OF EXTERNAL ELECTRIFICATION OF AF STN ARJANGARH UNDER GE (AF) GURGAON
2022_MES_535167_1
CWE/GGN/GT-07/2022-23
Open Tender
Electrical and Maintenance Works
Works
180 days
AF Stn Arjangarh
As per NIT
8 documents required · 8 mandatory
₹500
GE (AF) Gurgaon
₹81,000
Yes
14 Sept 2022
1 Jul 2022
5 Aug 2022
1 Jul 2022
28 Jul 2022
15 Jul 2022
1 Jul 2022 - 14 Jul 2022
Amount
Excavation of soft/loose soil in trenches not exc 1.5 meter wide & not exc 1.5 mtr in depth for foundation etc or for manholes, laying of pipe/ cables in any type of soil and getting out complete all as specified and directed.
Returning, filling in excavated approved soil, including spreading, leveling, watering and well ramming in layers not exceeding 25cm each complete all as specified and directed.
Removing excavated soil not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and directed.
M & L for dry sand cushioning to underground cables with 8cm thick before laying of cables and 15cm thick after laying and stretching of cable all as specified and directed .
M & L for Old size sub class ‘B’ bricks, laid in trenches as cable covers complete all as specified and directed. .
M & L for Cement concrete 1:4:8 type D-2 using 40mm graded stone aggregate in foundations, filling and mass complete all as specified and directed.
M & L for Cement concrete 1:3:6 type C-2 using 40mm graded stone aggregate in foundations, filling and mass concrete complete all as specified and directed.
M & L for cement concrete 1:2:4 type B-1 using 20mm graded stone aggregate in copings to poles & the like, etc including weathering, slightly rounded or chamfered angles and throating as directed including necessary form work complete all as specified and directed.
Supply , laying & testing XLPE insulated, armoured, heavy duty electric cable with stranded aluminium conductor, 11000 volts grade earthed , laid in trenches, sleeving through pipes or fixed on poles & walls or laid under floors including jointing with suitable size aluminium lugs complete of size 95 Sqmm 3 core nominal cross sectional area including taking out/down old u/s cable existing of any type and size.complete all as specified and directed.
Complte all as per item no. 9 but Size 120 Sqmm 3 core complete all as specified and directed.
Supply and fixing of GI tubing, light grade, 100 mm bore with all fitting laid in trenches / pole / wall for protection of cables in repairs complete all as specified and directed.
M&L Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armourend aluminium conductor cable of size 50 sqmm to 95 sqmm.complete all as specified and directed.
M&L Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armourend aluminium conductor cable of size 120 sqmm to 185 sqmm.complete all as specified and directed.
M&L Cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armourend aluminium conductor cable of size 50 sqmm to 95 sqmm.complete all as specified and directed.
M&L Cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armourend aluminium conductor cable of size 120 sqmm to 185 sqmm.complete all as specified and directed.
M&L for supply, stringing and fixing aluminium conductor steel reinforced ( ACSR) of any type including binding with and including suitable size of binding wire complete Including dismantling and taking out worn out ACSR conductor from overhead electric line complete all as specified and directed.
Complete all as per item No. 16 but GI wire 4 mm dia complete all as specified and directed.
Supply and fixing GI stay wire of 7/4 SWG upto required length including taking out and u/s one complete all as specified and directed.
Supply and fixing in repair mild steel galvanised stay assembly set complete comprising of 16 mm dia, 400mm long stay bow, 2150mm long stay rod 20mm dia, 300mm x 300mm x 6mm stay plate, thimble, all as shown in electrical plate No.1 of MES Schedule part-I 2010 complete including dismantling and taking out old damaged stay complete all as directed. Note :- PCC , earth work and Insulators etc shall be measured and paid separately.
M & L for Cross arms, bracing, supports, clamps and back plate, fabricated from structural steel section including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as directed including two coats of synthetic enamel paint over a coat of red oxide primer including dismantling and taking out u/s damage/rusted cross arms, bracings, supports, clamps and back plates from existing poles / dismantled poles / pole structures complete all as directed.
S&F Danger notice plate of 1.6mm thick mild steel sheet vitreous enameled white with letter figures and conventional skull and bones in signal red colour and fix with MS clamp for HT size 25 X 20 Cm and taking out of us one complete all as specified and directed.
M& L Pin type, porcelain, vitreous, white, brown or green insulator, 150 mm height, 150 mm dia for 11000 volts grade including one galvanised mild steel spindle, two galvanised iron washer and one galvanised iron nut and incl taking out of old u/s existing complete all as specified.
S&F Shackle type, porcelain, vitreous, white, brown or green insulators 150mm dia and 150 mm height for working pressure 11000 volts including galvanised mild steel strap 38 x 5 mm size, washers, 20mm dia insulator bolts, washers & nuts incll taking out of old U/S exiting complete all as specified.
M& L for Disc type insulator, porcelain, vitreous, white, brown or green insulator ( Single disc assembly ) of size 145 mm height, 255 mm dia ball socket type for working pressure 11 kv volts grade including one galvanised mild steel spindle, two galvanised iron washer and one galvanised iron nut including taking out old u/s existing one complete all as specified and directed.
M& L for loop type, porcelain, vitreous, white, brown or green insulator large type 140 mm, clearence of hole 25.5 mm for 11000 volts grade including taking out of old u/s existing one complete all as specified and directed.
M&L for lightening arrestor linear resistance type distribution class 9 KV RMS suitable for 11 KV system pole mounting type conforming to IS - 3070 Part-I including taking down old u/s existing one. complete all as specified and directed.
M&L for vice type connectors of size 4 to 7 mm dia consisting of two brass plates and two steel bolts and nuts for two conductor of equal or unequal sizes for non tension connections including treatment of connector and ACSR conductor with conducting jelly including taking out old u/s existing complete all as specified and directed.
M&L for vice type connectors of size 10 to 13 mm dia consisting of two brass plates and two steel bolts and nuts for two conductor of equal or unequal sizes for non tension connections including treatment of connector and ACSR conductor with conducting jelly ,including taking out old u/s existing complete all as specified and directed.
Supply and fix gang operated air break switches, triple pole, manually operated, mounted on insulators and steel frame, with operating mechanism worked from ground level horizontal / vertical type for rating upto 400 Amps, 11000 volts complete with GI operating pipe of heavy duty including taking down old U/S existing one. complete all as specified and directed.
S & F drop out fuse assembly complete set with Insulator-06 Nos and connected accessories for 11000 V grade of 400 Amp s capacity including taking down old u/s existing DO fuse assmbly.complete all as specified and directed.
Expulsion fuse single pole capacity of Voltage 11KV and current up to 25 Amps.complete all as specified and directed.
Ditto as per item No 31 but capacity of Voltage 11KV and current above 25 & upto 50 Amps.complete all as specified and directed.
Ditto as per item No 31 but capacity of Voltage 11KV and current above 50 & upto 100 Amps.complete all as specified and directed.
Taking down and repairing/overhauling of air break gang operated switch with DO fuse unit 200 Amp/400 Amp capacity triple pole mechanically operated mounted on insulators and steel frame installed vertically / horizontally , replacement of broken/worn-out components, oiling and greasing of mechanical moving parts, smoothing and polishing of electric contacts with providing conducting jelly of contacts refixed the same after repair including proper allienment complete all as directed. ( Note:- Warn out component/ insulators / ASCR shall be measured and paid separately)
Supply only following components to incorporated for repair of air break gang operated switch :-
Female contact or fixed contact heavy duty and high conductive metal complete capacity 200A/400 Amp11 KV
Male contact or Moving contact heavy duty and high conductive metal complete capacity 200A/400Amp 11 KV.
Tinned copper flexible jumper 200A/400A.
Fixed top contact & Fixed bottom contact 11 KV 400 Amp for DO fuse unit.
Fiber glass tube with metalic fittings both ends suitable for DO fuse 11KV
Supply only mild steel jumper carrier as per sample.
Supply only back connector plate as per sample.
Supply only post insulator 11 KV as per sample.
Disconnect HT & LT connections from any type of transformers indoor/outdoor, plinth/ pole mounted in any location in the restricted areas of 503 SU shifting to workshop for carry out any repair works, as directed install back in original location including re-connection of HT & LT supply system of capacity complete all as specified and directed. (a) 100 to 1000 KVA Note:- (a) Required tools & plant including lifting arrangement, transport etc shall be included in the rate quoted. (b) Any damage occurred during lifting/ transporting, the firm will be responsible to rectify such defect free of cost.
Shifting of trolly mounted transformer to the site and disconnecting the defective transformer from HT and LT side connection and connecting the trolly mounted stand by transformer by making neccessary HT /LT side connection properly for temporary basis and disconnecting the same after repair of removed /issolated transformer and connecting work shop repaired transformer complete all as specified and as directed.
Repair / Servicing / maintenance of transformer 11 / .433 KV indoor / outdoor type , plinth / pole mounted type including the following work services :- (a) Disconnecting transformer from electric system and providing electric power to user from alternative arrangement including taking out from existing position . (b) Decanning of transformer oil , opening top cover , disconnecting of all internal connections , lifting and taking out of core assemble , LT / HT bushesing , Tap changer etc ,cleaning and inspection of core and winding , segrigetion of serviceable and unsv items , removing of sludge and cleaning tank and cooling pipes / fins /tanks with pressure water and drying the tank complete . (c) Replacinig Unsv LT / HT bushing by replacing rubber / cork oil seals and damage terminal rod & replacement of Transformer cover gasket of rubber cork sheet . (d) Re installation of TFR including reassembling of core / winding assembly complete including replacement of unsv parts , repair the defective parts and tighting of all loose / sparks wire / nut bolts etc and refixing the to the existing position , connecting with HT/LT cables and earthing strip and testing complete including necessary Transportation ( If required ) to the work shop and back and including Dehyderation and refilling of existing or new transformer oil of required quantity .complete all as specified and directed.
Transformer capacities 100 to 400 KVA
Transformer of capacity 630 to 1000 KVA
NOTE FOR ITEM NO 36,37 & 38 :- (i) Dehydration of oil and new Transformer oil shall be measured and paid seperately . (ii) Transportation of TFR measured and paid seperately . (iii) HT & LT Busing , Tap Changer will be measured & Paid separataly. (iv) In case HV / LV Winding found damages then Contactor shall be made serviceable with new winding and the same will be measured and paid seperately . (v) The rate of corck sheet & Packing Material for following cap of TFR are included in coted rate of following cap of TFR :-
Removing of existing damage insulating material from LV Winding , Cleaning the winding and reinsulating the LV Winding with approved grade and make of insulating paper and heating the coil in the heat chamber to obtained desired result of insulating resistence complete and re-installation .complete all as specified and directed.
Material and winding of HV side copper winding with super enammeled copper wire of existing size , gauge and weight of approved grade wire including necessary insulating material and heating the coil in the heat chamber to obtained desired result of insulating resistence complete and re-installation .complete all as specified and directed.
Material and winding of LV side copper winding with existing size / type and weight of copper strip winding of approved grade including rapping of insulating tap and insulating material and heating the coil in the heat chamber is obtained desired result of insulating material .complete all as specified and directed.
NOTE FOR ITEM NO 41 & 42 : - (i) Contractor shall be open the core assrmbly and segrigatted the serviceable / unser winding and shown to the EIC before and after incorportation to the TFR . (ii) Actual weight of the new winding shall be measured and paid . (iii) In case of damages of the LV Windings and required re insulation of LV Winding then shall be measured and paid seprrately .
Supply and replace of silica jel cristal complete all as specified and directed.
Supply and fixing in repalcement of heavy duty breather assembly with Silica jel cristal for Transformer as per existing shape and size complete all as specified and directed.
Supply and fixing of new temprature guage ( 0 degree to 120 degree C ) range dial temprature as directed including taking down old unserviceable guage.complete all as specified and directed.
M & L for transformer oil level indicator assembly complete with iron frame, glass, rubber packing sheet, nuts, bolts and washers etc as per existing.complete all as specified and directed.
Supplying and laying synthetic rubber insulated mats 2.5 mm thick for voltage upto 11 KV (size 2 x 1 m) for electrical purpose as per IS 15652-2006 (superseding IS 5424) suitable for electrical shock safety. complete all as specified and directed.
Materials and labour for removing the burnt out/ damaged LV bushes with porcelain insulator and replace with Brass LV bushes, nuts , check nuts, rubber washer etc complete as per the existing size / model, for transformers of capacity complete all as specified and directed.
(i)100 to 160 KVA
(ii)400 KVA
(iii) 630 to 1000 KVA
Materials and labour for removing the burnt out/ damaged HV bushes with porcelain insulator and replace with Brass HV bushes, nuts , check nuts, rubber washer etc complete as per the existing size / model, for transformers of capacity complete all as specified and directed.
(i) 100 to 160 KVA
(ii) 400 KVA
(iii) 630 to 1000 KVA
Dehydration of existing transformers 11 KV and servo voltage stabilizer of oil minimum three cycles to achieve dielectric strength up to 60 KV in 2.5 mm gap electrode including toping up of oil if required at site.complete all as specified and directed. Note : (i) Dehydration of transformer / voltage stabilizer oil shall be carried out at site and contractor shall be taken the testing result before and after dehydration of oil and shown to the EIC at site and maintain necessary documents for record . (ii) Dehydration Machine with all T&P & Transformer oil testing machine for dehydration of Transformer oil and necessary transportation for the machines is arrange by contractor . (iii) Oil required for topping up the transformer / voltage stabilizer will be measured & paid separatly
Supply and charging topping up of new low viscosity transformer oil from sealed drums confirming to IS 335-1993 Part-II after testing the correct dielectric strength up to 60 KV at 2mm gap duly de-hydrated complete all as specified and directed.
Supply only Off load Tap changer switch of existing model / type of Transformer of capacity 100 to 160 KVA.complete all as specified and directed.
Supply only Off load Tap changer switch of existing model / type of Transformer of capacity 400 KVA.complete all as specified and directed.
Supply only Off load changer switch of existing model / type of Transformer of capacity 630 to 1000 KVAcomplete all as specified and directed.
NOTE FOR ITEM NO 53 to 55 :- (i) Fixing charges shall be includede in rate coated under Item No 38 .
M&L for preparation of old painted surfaces steel by brushing/changing stain, greasy spots with thinner and apply two coats of spray painting with super enameled smokes grey colour paint of approved by Dept. and writing the MES / SM No with white paint as directed to transformer indoor/outdoor installed at various different locations complete all as specified and directed at site.
(a) 100 to 160 KVA
(c) 630 to 1000 KVA
Disconecting the LT incoming and outgoing main cables of any size ,strip opening of the voltage stablizer , draining out the oil into a cleaned container ( container shall be arranaged by the contractor ).Lifting up dimmer and transformer with help of tripoid and chain pulley etc (The T & P shall be arranged by contractor ), checking of all the parts ,cleaning and servicing of the container,dimmer,transformers coil and allied parts including replacememnt of minor parts like nut bolts ,connecting wires ,rubber seals /packing etc . ( The repair/ replacement of the major parts shall be measured and paid seperately ) and reassembling the volt stablizer complete (in reverse order.). Refilling oil ater dehydration and filtration/cleaning by centrifuging machine including testing of samples before and after dehydrations and filtration complete, and reconeecting the incoming and outgoing cable connection, commisioning and testing of the volt stablizer on load complete all as specified and directed. Note: The cost of dehydration of oil shall be measured and paid under respective item of schedule
(a) 100 to 160 KVA
M&L for preparation of old painted surfaces steel by brushing/changing stain, greasy spots with thinner and apply two coats of spray painting with with super enameled smokes grey colour paint of approved by Dept. and writing the MES /SM No with white paint as directed to Servo Volage Stab. indoor/outdoor installed at various different locations complete all as specified and directed at site.
(a) 100 to 160 KVA
S&F in replacement of digital display unit (Auto control card) suitable for servo type voltage stabilizer with complete wiring suitable for 100 to 300 KVA stablizer. complete all as specified and directed.
Supply and fix in replacement of Dimmer coil (Variable transformer) suitable for servo voltage stabilizer with complete wiring suitable for 100 to 300 KVA complete all as specified and directed.
Supply and fix in replacement of motor gear assembly suitable for 100 to 300 KVA capaicty servo type voltage stablizer complete all as specified and directed.
Supply and fix in replacement of Dimmer gear assembly suitable for 100 to 300 KVA capacity servo type voltage stabilizer complete all as specified and directed.
S & F in replacement of Panel lamp for servo type voltage stablizer 100 to 300 KVA capacity complete all as specified and as directed.
S & F in replacement of Ampere meter of Range 0 to 500 Amps with suitable size of C.T. (Digital type) for servo type voltage stablizer 100 to 300 KVA capacity complete all as specified and as directed.
S & F in replacement of Servo motor 10 K.G. torque for servo type voltage stablizer 100 to 300 KVA capacity complete all as specified and as directed.
(a) 100 to 160 KVA
S & F in replacement of R.C. net work for 10 K.G. motor for servo type voltage stablizer 100 to 300 KVA capacity complete all as specified and as directed.
S & F in replacement of Carbon Brush for servo type voltage stablizer 100 to 300 KVA capacity complete all as specified and as directed.
S & F in replacement of finger holding carbon brush for servo type voltage stablizer 100 to 300 KVA capacity complete all as specified and as directed.
M & L for complete repairing / Serviceing of HT 11 KV Vaccum circuit breaker (VCB) after disconnecting of all incoming and outgoing connection, checking/finding of the defective spare/parts, removing of all moisture content with suitable grade chemical, replacement of rusted nuts,bolts and washer, replacement of all unserviceable post insulator and repair of all busbar joints and covered with HT insulation tape, painting of all internal surface where required and complete external surface as per existing colour and quality, replacemnt of all defective internal AC/DC circuit wiring, repair/servicing of breaker trolly including motorized operating mechanism, CT/PT, power pack and calibration of triping relays system and tripping mechanism for regulating the fault flow (Over Current, Earth Fault, Differential) in sequence from down streem to receiving Sub stn for accuracy and effective functioning of VCB complete all as specified and as directed. Note : (i) Nuts , bolts, washer, painting, cleaning material, insulation tape, copper wire for circuit wiring and defective HT 11 KV 2 Amp fuse , carrier oiling greasing to charging spring ,replacement of HRC fuse 110/220 volt 5 Amps setting of over current , earth fault ASHIDA ADR131A relays / L&T Relay complete other minor items for repair of breaker shall be deemed in qouated rate. (ii) Replacement of major unserviceable spares/accessories shall be measured and fixing rates shall be included in quoted rate. supply shall be paid seperately. (iii) During repair work/serviceing work carried out in VCB panel all the existing HT connection/HT cable connected with other VCB for continuous supply to the feeder.
Supply only shunt trip coil assembly suitable for HT VCB , operating on 30/110 volt system and testing complete all as specified and directed .
Supply only closing / tripping coil operated on 110/30 volt system suitable for working of relay for HT VCB complete all as specified and directed .
Supply and testing Epoxy resin cost totaly enclosed dual core type Current transfomer (CT) for protection and measuring of system having ratio of 100/50 : 5 / 5 A , Burden-10VA, class-I, insulation level 12/28/75 KV, STC- 18.4 KA for 1 sec as per ISS-2705 and IEC-60044 including dismantling of old one complete all as specified and directed .
Supply and testing Epoxy resin cost totaly enclosed dual core type Current transfomer (CT) for protection and measuring of system having ratio of 60/30 : 5 / 5 A , Burden-10VA, class-I, insulation level 12/28/75 KV, STC- 18.4 KA for 1 sec as per ISS-2705 and IEC-60044 including dismantling of old one complete all as specified and directed .
Supply only voltage transformer of ratio 1100 RT3 / 110RT3V Acc class 1.0 burden 200 VA STC 25 KA for 1 sec including copper extention strips of required size and rating complete all as specified and directed .
Supply only spring charging motor suitable for fixing with 11 KV indoor type VCB panel complete all as specified and directed .
Supply only charging bottle suitable for 11 KV VCB trolly complete all as specified and directed .
Supply only moving contacts of VCB made of copper and suitable for 11 KV VCB Trolley complete all as specified and directed .
Supply only battery 12 volts , 7 AH, 1.4 Amps for battery bank installed at power house complete with termination clips complete all as specified and directed .
Supply only battery charger suitable for charging to battery bank 12 volts 7 AH (02 Nos) complete all as specified and directed .
Supply only Heater 230 volts AC 60 watt for 11 KV HT VCB panel complete all as specifed and as directed.
Supply only Neon indicator lamp LED type with high intensity 40-240 volts AC and 40-220 volts DC with holder complete all as specified and as directed.
Supply only limit switch 110 volts operated suitable for HT 11 KV VCB charging motor circuit.
Supply only vacuum interputer for HT11 KV VCBs, 630/800 Amps, breaking capacity 13.1 KA suitable for Alstom make VCB complete all as specified and as directed.
Calibration of Protective relay programmable type in HT panel with carrying out secondary injection test, set the relays in accordance with the supply agency Protection/Tripping range so as to trip the MES breaker before tripping the fault to supplier grid/ system. All parameter in MES breaker tripping setting in relays shall be arranged in such away that any fault occured in the feeders after the recieving station must not transfer to the suppliers system.complete all as specified and directed.
Dismanteling and overhauling and testing potential transformer capacity 11 KV/ 110 volts AC make crompton & greaves and replacement of worn out spares such as contacts, bushing, control wiring fibre plates, gaskets , transformer oil and applying multi grease to the mechenical parts & dry graphite conductive seaslant to contacts etc. & re-assembling the same and commissioning complete all as specified and directed.
Dismantling Air Circuit Breaker 4pole/3pole, 630 to 2000 Amps 415 Volts, draw out/fixed type from location and repair /overhauling of spring drive mechanism, coil, auxiliary switch including setting of over load coil,no volt coil, tripping coil & apply multi grease for mechnical parts, cleaning and inspecting male and female contacts and apply dry graphite conductive sealant for contacts, checking of electrical wiring system, testing, and assembling all items/components parts to the respective position and testing complete all as specified and directed. Note : Spare parts will measured and paid separately.
Supply , fix ,test and commissionning in repair in existing panel APFC Relay, 12 Stages digital type suitable for 415V, 3phase, AC supply and all specified and directed.
M&L supply and fix in repair heavy duty Contractor for three phase capacitors including necessary connections all as directed for the following capacity. complete all as specified and directed.
3 pole power contactor type MNX-110.
3 pole power contactor type MNX-70.
3 pole power contactor type MNX-32.
3 pole power contactor type MNX-18.
MCB TP of 63 ams of C series .
PVC insulated, Unsheathed, multistranded, single core Copper wire of 10 sqmm FRLS grade 1100 volt. complete all as specified and directed.
Maintenance / repairs to APFC panels, 3 phase AC 415 V, by skilled technician and replacement of unserviceable spares as specified below for capacities 40 to 200 KVAR including replacement of short circuited copper conductor cables with appropriate gauge PVC insulated stranded copper conductor cables and cleaning of all moving contacts of relay contactors, tightening of all terminals and testing afer repairs to ensure serviceability and corrected output at specified powerfactor all as specified and directed at site.
Supply and install capacitor metalized poly propylene ultra heavy duty (LTXL) for 3 phase ,440 V, 50 Hz System for permissible non- linear load 15%. complete all as specified and directed.
(a)25 KVAr
(b)20 KVAr
(c)10 KVAr
(d) 5 KVAr
(e) 2KVAr
M & L for Restrainingre of HT /LT over head line single ACSR conductor comprising of any size of conductor aluminium/copper/GI after opening binding wire from insulators and replace binding wire and achieved permissible sag limit of over head line conductor complete all as directed and specified.
Trimming of tree branches upto 11m from ground level all along the over head electric supply lines, to clear all branches maintaining a clear distance of 1.5m from the conductors. The maximum average dia of branches shall not exceed 20cm. After trimming the cut pieces and branches are cleared from the road upto a distance 200m.complete all as specified and directed. Note: (a) Required tools, ladder, Safety equipment etc. shall be arranged by the firm. (b) Area wise shut down to feeders shall be given on one day notice upto 4hrs.
Supply ,install testing and commisioning of maintenance free chemical earthing system conforming to IS: 3043 using 77mm dia 3000mm long copper rod with exothermic T point rod with long copper strip of size 50mm x 6 mm and 90 mm dia terminal pipe of thickness 1.6 mm and 3000 mm long with copper test certifcate 99.99%. The ground enhancing compound made of Marconite conductive aggregate (consist of Marconite resin-based cements, adhesive and gypsum plasters) shall not be less than 45 kg. The electrode shall be provided on its top with an earth termination clamp made out of electrolytic grade copper for connecting earth continuity conductor with copper wire. PCC chamber of size 300x300x300 mm with cover shall be provided on the top of the earth system on 100 mm thick PCC 1:3:6 bed concrete . The chamber shall burried in ground with top edge projecting upto 75 mm from ground surface complete all as specified and directed. Note: (i) The quoted rate shall include cost of copper strip 50mm x 6 mm upto 7.5 m length and bore in hard/disintegrated rock. (ii) The earth resistance shall not be more than 01 ohm . (iii) the size of bore should not be less than 1500 mm dia.
M & L for Earthing to OH/Sub stn with galvanised steel earth plate electrode 60cm x 60cm x 6mm thick, buried directly in ground (earth pit not less than 2.25m below normal ground level) with top edge of earth plate not less than 1.5m below normal ground level connected to main earth lead GI wire 4 mm dia by means of bolts, nut, check nuts and washers of galvanized iron or steel all as shown in electrical plate No.5 of MES Schedule pt-I 1991, GI earth lead wire protected by GI pipe 15mm dia light grade and connected to earth test point including excavation in any type of soil,returning filling, disposal of soil, providing charcoal dust and common salt upto top edge of earth plate, construction of PCC pit with RCC cover, funnel, watering pipe of 20mm dia GI light grade and provision of earth test point including testing on completion complete Note : Main earth lead beyond 7.5 meter shall measured and paid saperatly.
complete all as item 81above but main earth lead 32 x 6 mm galvanised iron strip.complete all as specified and directed.
Complete all as item No 81 above but using copper plate 60×60cm×3.15 mm thick electrode and 20×3mm copper strip as earthing lead.complete all as specified and directed.
M&L in repair for Earth continuity conductor or main earthing lead of 32 x 6 mm galvanized iron strip, buried in ground or fixed to wall in repair complete all as specified and directed.
M&L for Test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed including 3 nos. 8mm dia 25mm long hex. head screw.complete all as specified and directed.
M&L for Aluminium strip 25 x 3.15mm with saddles and fixing screws etc. for roof conductors and down conductors above ground. complete all as specified and directed.
M&L for Copper strip 20 x 3.15mm with saddles and fixing screws etc. for roof conductors and down conductors above ground.complete all as specified and directed.
Supply and fix epoxy insulators 25 mm dia base with suitable screws complete for fixing AL strip if size 25x3.15 mm. complete all as specified and directed.
Supply and fix porcelain insulator (white colour) for running of GI/Aluminium/Copper strips of size 32/20/25 mm including suitable size of screws for fixing vertically/horizontal plane at any height and making suitable size holes on strips including nut/bolts/wahsers etc complete all as specified and directed.
M&L for Air termination of Lighting conductors, single pointed aluminium rod 12mm dia and 300mm long complete all as specified and directed .
M&L for Air termination, single pointed, copper rod 12mm dia and 300mm long complete all as specified and directed .
Supply & Fix shock treatment chart standard size with diagrams and illustrations dully framed properly laminated including hooks for fixing/ fastening. The detail illustrations shall be in Hindi & English all as directed and as specified.
M&L for pole painting, concrete pole with 02 coat of wheather exposed dust proof "apex" emulsion, pole height should be 9/11 mtr. Painting should be done from top to bottom at ground level. Bottom portion of the pole upto 1.50 m from top of the copping with one coat of synthetic enamel paint with marking pole numbers & marking three blue & two white strips width 25 cm by fluorescent paint complete all all as specified and directed .
Supply and fix in repair ACB 4 pole 415 volts , 630 amps , AC 50 Hz with breaking capacity 50 KA conforming to IS/IEC-60947-2 with themal magnetic release and manual drawout type (Thermally adustable type) inclding electrical connection as per site requirement complete all as specified and directed .
Supply and fill of back feel compound in earth pit complete all as specified and directed .
M&L Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armourend aluminium conductor cable of size 50 sqmm to 95 sqmm . complete all as specified and directed.
M&L Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armourend aluminium conductor cable of size 120 sqmm to 185 sqmm.complete all as specified and directed.
Supply , laying & testing in repair for XLPE insulated, armoured, heavy duty electric cable with stranded aluminium conductor, 1100 volts grade, laid in trenches, sleeving through pipes or fixed on poles & walls or laid under floors including jointing with suitable size aluminium lugs complete of size 10 Sqmm nominal cross section x 4 core.complete all as specified and directed.
Complete all as per item No 98 but Size 16 Sqmm X 4 core. complete all as specified and directed.
Complete all as per item No 98 but Size 25 Sqmm X 4 core. complete all as specified and directed.
Complete all as per item No 98 but but Size 50 Sqmm X 3.5 core. complete all as specified and directed.
Complete all as per item No 98 but but Size 70 Sqmm X 3.5 core. complete all as specified and directed.
Complete all as per item No 98 but Size 95 Sqmm X 3.5 core. complete all as specified and directed.
Complete all as per item No 98 but Size 120 Sqmm X3.5 core. complete all as specified and directed.
Complete all as per item No 98 but Size 240 Sqmm X3.5 core. complete all as specified and directed.
Supply and fixing of GI tubing, light grade, 40 mm bore with all fitting lais in trenches / pole / wall for protection of cables in repairs complete all as specified and directed.
Supply and fixing of GI tubing, light grade, 80 mm bore with all fitting lais in trenches / pole / wall for protection of cables in repairs complete all as specified and directed.
Supply and fix in repair cable jointing kit for 1.1 KV grade cable for straight through joint complete with Jointing material of tubular sleeve version and accessories suitable for 3½ / 4 core XLPE armoured Al conductor cable of size 25 to 50 sq mm complete all as specified and directed. .
Supply and fix in repair cable jointing kit for 1.1 KV grade cable for straight through joint complete with Jointing material of tubular sleeve version and accessories suitable for 3½/ 4 core XLPE armoured Al conductor cable of size 70 to 150 sq mm complete all as specified and directed.
Supply and fix in repair cable jointing kit for 1.1 KV grade cable for straight through joint complete with Jointing material of tubular sleeve version and accessories suitable for 3½/ 4 core XLPE armoured Al conductor cable of size 185 to 300 sq mm complete all as specified and directed.
Supply and fixing steel tubular pole, swaged, complete with cast iron base plate, finial taper plug, bolts, nuts, washer and screws including painting with two coats of aluminium paint over one coat of red oxide primer on all exposed surfaces and tarring with black bituminous paints to portion embedded in PCC including numbering of poles with two coats of synthetic enamel paints, type 410-SP-31 (9 meter long) complete, Including disconnecting and taking out old damage PCC pole all as directed .
Supply and fixing prestressed concrete pole 9 meters long 102 mm x 152 mm at top and 102 mm x 289 mm at bottom of class 10 complete, Including disconnecting and taking out old damage PCC pole complete all as specified and directed. Note : for item no 111 & 112 Earth work and PCC shall be measured and paid separately as these respectively.
Supply and fix ON load four pole changeover switch with front handle operated of 4 pole 415 volt 50 Hz 630 amps in open execution to be fixed in existing panel with suitable size nut/bolts and complete all as directed .
Supply and fix ON load four pole changeover switch with front handle operated of 4 pole 415 volt 50 Hz 400 amps in open execution to be fixed in existing panel with suitable size nut/bolts and complete all as directed.
Supply and fix ON load four pole changeover switch with front handle operated of 4 pole 415 volt 50 Hz 200 amps in open execution to be fixed in existing panel with suitable size nut/bolts and complete all as directed.
Supply and fix ON load four pole changeover switch with front handle operated of 4 pole 415 volt 50 Hz 100 amps in open execution to be fixed in existing panel with suitable size nut/bolts and complete all as directed.
M & L for Painting of steel pole with cross arms, clamp of any length and shape for LT overhead line with single coat of aluminium paint including preparation of the existing surface including marking pole numbersand marking three blue & three white bends width 20 cm by fluorescent paint, from bottom of pole to 1.5 Mtr height complete all as specified and directed.
M & L for Restraining of LT over head line single ACSR conductor comprising of any size of conductor aluminium/copper/GI after opening binding wire from insulators and replace binding wire and achieved permissible sag limit of over head line conductor complete all as directed and specified.
S&F Danger notice plate of 1.6mm thick mild steel sheet vitreous enameled white with letter figures and conventional skull and bones in signal red colour and fix with MS clamp for LT size 20 X 15 Cm fix in repairs complete all as specified.
M& L Pin type, porcelain, vitreous, white, brown or green insulator, 100mm height, 65 mm dia for 1100 volts grade including one galvanised mild steel spindle, two galvanised iron washer and one galvanised iron nut, fixed in repairs complete all as specified and directed.
M&L for Shackle type insulator from LT overhead line and S&F new Shackle type, porcelain, vitreous, white, brown or green insulators 100mm dia and 115 mm height for working pressure 1100 volts including galvanised mild steel strap 31 x 3mm size, washers, 14mm dia insulator bolts, washers & nuts , fixed in repairs complete all as specified and directed.
M& L loop type, porcelain, vitreous, white, brown or green insulator, 65 x 90 mm , clearence of hole 16 mm for 1100 volts grade including fixed in repairs complete all as specified and directed.
M&L in repair/replacement for LT line PVC Spacers for the following sizes :-
(a) Spacer for two wire
(b) Spacer for three wire
(c) Spacer for four wire
(d) Spacer for five wire
Supply only Aluminium lugs of any type complete all as per of sample of following sizes :-
Supply only Copper lugs of any type complete all as per of sample of following sizes :-
Supply & Fixing in repair including making connection testing and commissioning of new MCCB 3 Pole, 415 V, fixed type, 25 to 100 Amps with breaking capacity 16 KA.complete all as specified and directed. Note: The make of MCCB shall be of existing make in the existing plannel board or exactly suitable to the existing frame size. In case only one particular make is procuring by the bidder necceasry alteration required to fix the same at no extra cost shall be done by the bidder .
Complete all as above item No 126 above but MCCB TP 125 Amps, 415 Volts, 36 KA, 50 Hz complete with extended terminals and PVC spreader complete all as specified and directed.
Complete all as above item No 126 above but MCCB TP 250 Amps, 415 Volts, 36 KA, 50 Hz complete with extended terminals and PVC spreader complete all as specified and directed.
Complete all as above item No 126 above but MCCB TP 400 Amps, 415 Volts, 36 KA, 50 Hz complete with extended terminals and PVC spreader complete all as specified and directed.
Complete all as above item No 126 above but MCCB TP 630 Amps, 415 Volts, 50 KA, 50 Hz complete with extended terminals and PVC spreader complete all as specified and directed.
Complete all as above item No 126 above but 4 Pole, 125 Amps, 415 V, 25 KA, 50 hz complete with extended terminals and PVC spreader complete all as specified and directed.
Complete all as above item No 126 above but 4 Pole, 200 Amps, 415 V, 25 KA, 50 hz complete with extended terminals and PVC spreader complete all as specified and directed.
Complete all as above item No 126 above but 4 Pole, 400 Amps, 415 V, 36 KA, 50 hz complete with extended terminals and PVC spreader complete all as specified and directed.
Complete all as above item No 126 above but 4 Pole, 630 Amps, 415 V, 50 KA, 50 hz complete with extended terminals and PVC spreader complete all as specified and directed.
M&L for replacement of CT for ratio (50 /5 , 100/5/200/5 as per existing model complete all as specified and directed.
M & L for PVC insulated, stranded aluminium conductor served with inner sheathing PVC tape and over all PVC sheathed in service connection suspended by insulating hanger not more than 1 meter apart including 4 mm dia GI suspension wire , two single core cable of 10 Sqmm , complete all as specified and directed.
S & F in repair sub main wiring for circuit of size two run 6 sq mm single core (FRLS) alongwith earth wire of 6 sq mm single core of FRLS PVC insulated unsheathed cable, 1100 volts grade with multistranded copper conductor in existing PVC conduit complete all as specified and directed.
S & F in repair sub main wiring for circuit of size two run 4 sq mm single core (FRLS grade) alongwith earth wire of 4.0 sq mm single core of FRLS grade PVC insulated unsheathed cable, 1100 volts grade with multistranded copper conductor in existing PVC conduit complete all as specified and directed.
Supply and fixing in repair TPN DB's 8 way vertical type 415 V, double door suitable for housing of 125 Amps MCCB as main incoming. complete all as specified and directed.
Complete all as per item No. 139 above but of 4 way and suitable for housing of 100 A/63 A MCCB as main incoming. complete all as specified and directed.
S&F MCCB 125 Amps capacity, 4 pole, 25 KA, fixed thermal and magnetic release complete with extended terminals to be fixed in 8 way TPN DB complete all as specified and directed.
Complete all as per item No. 141 above but capacity of 100 Amps, fixed thermal and magnetic release, 4 Pole, 25 KA suitable to be fixed in 4 way TPN DB complete all as specified and directed.
Suply and fixing 240 V, 10 KA, 'B' curve miniature circuit breaker (MCB) of single pole and current carrying capacity SP 63 Amps in the MCB DB complete with connection testing and commissioning. complete all as specified and directed.
Supply, laying & testing in repair for XLPE insulated, armoured, heavy duty electric cable with stranded aluminium conductor, 1100 volts grade, laid in trenches, sleeving through pipes or fixed on poles & walls or laid under floors including jointing with suitable size aluminium lugs complete of size 10 Sqmm nominal cross section x 2 core incl taking out/down old u/s existing cable of any size and type.complete all as specified and directed.
Fabricate, Supply install test and commissioning in repair of CPRI approved Outdoor type LT panel board suitable for 440 Volt, 3 phase & Neutral , 50Hz supply , floor mounted weather and vermin proof fabricated from MS angle of size 50x50x5 mm as base frame,with 3.15 mm thick CRCA sheet load bearing members and load bearing members such as door partitions etc of thick no less than 2.0 mm thick , with gland paltes at bottom with suitable Brass chromium plated glands, with locking arrangements complete, duly powder coated with siemens grey colour after chemical treatment, including LED RYB indicators -06 nos on incoming side and ON/OFF/TRIP indications on outgoing side of breaker, interconnections from bus bars to MCCB's with suitable size aluminium bus bars, all internal ckt / protection wiring with FRHR 1100 V grade wiring with MCB protection,including terminal adapters, spreader links on incoming and out going sides of MCCB's complete all as specified and directed and comprising of the following: -
Bus bar Aluminium - 400 A capacity- 04 Nos high conductivity, suitable for 415 V, 50 Hz supply including interconnection from incoming, and out going feeders with suitable mounting insulators, heat shrinkable colour sleeves.
MCCB 250 Amps 4 pole 36 KA, with adjustable thermal magnetic range as in coming - 01 No.
MCCB 63 Amps 3 pole 16 KA with adjustable thermal setting as out going- 06 Nos.
MCB SP 63 Amps, 10 KA, 'B' Series- 12 Nos
Digital multifuctional meter (Make : L&T), 4410 Series, Cat No. WL441010OOOO
ON/OFF indication lamp with toggle switch and three Nos indication lamp (R,Y,B) - 01 Set
M&L for searching fault location of HT/LT UG cable 11000/415 Volts laid in trenches/ducts with the help of electronic fault locating machine comprising of surge generator pulse, ECHO fault locator with frequency distance calculator etc incl transportation of machinery. Excavation in normal soil strata exposing the cable fault removal of deteriorated portion of the cable treating of cable of any size including disconnecting and re-fixing cables with lugs as per direction of Engineer-in-charge.
Fabricate, Supply install test and commissioning in repair of CPRI approved Outdoor type LT panel board suitable for 440 Volt, 3 phase & Neutral , 50Hz supply , floor mounted weather and vermin proof fabricated from MS angle of size 50x50x5 mm as base frame,with 3.15 mm thick CRCA sheet load bearing members and load bearing members such as door partitions etc of thick no less than 2.0 mm thick , with gland paltes at bottom with suitable Brass chromium plated glands, with locking arrangements complete, duly powder coated with siemens grey colour after chemical treatment, including LED RYB indicators -06 nos on incoming side and ON/OFF/TRIP indications on outgoing side of breaker, interconnections from bus bars to MCCB's with suitable size aluminium bus bars, all internal ckt / protection wiring with FRHR 1100 V grade wiring with MCB protection,including terminal adapters, spreader links on incoming and out going sides of MCCB's complete all as specified and directed and comprising of the following:
Bus bar Aluminium - 600 A capacity- 04 Nos high conductivity, suitable for 415 V, 50 Hz supply including interconnection from incoming, and out going feeders with suitable mounting insulators, heat shrinkable colour sleeves.
MCCB 400 Amps 4 pole 36 KA, with adjustable thermal magnetic range as in coming - 01 No.
MCCB 63 Amps 3 pole 16 KA with adjustable thermal setting as out going- 09 Nos.
MCB SP 63 Amps, 10 KA, 'B' Series .
Digital multifuctional meter.
ON/OFF indication lamp with toggle switch and three Nos indication lamp (R,Y,B) - 01 Set of three
Net Contract Sum will be after deducting Sch of Credit of Rs 1,79,534.00
D P ENTERPRISES
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .