Loading…
India Infra Updates on WhatsApp
Join the Tenderkart WhatsApp channel for India Tender Updates
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance 145 1 0 NEAR OLD LIC SHIV NAGAR VILLAGE TOWN MODIPURAM CITY MEERUT MEERUT UTTAR PRADESH 250110 INDIA | MEERUT | UTTAR PRADESH | 250110 | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance 2ND FLOOR SHOP NO 303 MARUTI PLAZA RONCHI BANGAR TOWNSHIP MATHURA | MATHURA | UTTAR PRADESH | 281001 | Admitted-Finance |
Tender Value
₹19.9 L
EMD Value
₹20,000
Closing Date
8 Jun 2023, 1:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
SE ETC Mathura
132 KV S/S Aurangabad Mathura
Works for Increasing Capacity from 2X63 MVA to 3X63 MVA with construction of transformer bay and other associated works at 132 KV Sub-Station Vrindavan Under ETD Mathura
2023_UPTCL_806656_1
ET-04/ETC(M)/23-24
Open Tender
Electrical Works
Lump-sum
180 days
Under ETC Mathura
Please refer Tender documents.
2 documents required · 2 mandatory
₹590
EE ATT ETC Mathura
₹20,000
15 Jun 2023
27 May 2023
9 Jun 2023
27 May 2023
8 Jun 2023
27 May 2023
Amount
Construction of 132 KV Transfer Bus bay , 63 MVA Transformer bay, Erection of 2 Nos capacitor bank
Erection of main and auxiliary structure consisting of columns, beams, peaks, masts etc. structure required for installation of Main /Transfer bus, Jack busbar, isolators, P.I., CTs., L.As. and all other equipments. The job consists of shifting of all material i.e. conductor, fittings, structure parts, nuts, bolts, washer etc. from store to site of erection, erection of structure as per relevant drawing and practices using flat and spring washer with each bolt. Matching of holes, cutting, matching of members if required shall also be done by the contractor without any extra cost to complete the work satisfactorily. All material to be erected shall be supplied by UPPTCL free of cost but all men, material and T&P required for satisfactorily completion of work shall be arranged by the contractor at his own cost.
Dismantling of complete capacitor bank including jack bus & structure (ALP 10 NO, ABL-6 NO), CCM-4 No., CGM-2 No. series reactor 08 Nos. NCT-04 Nos., PT-03 Nos. capacitor bank cells 04 unit, Circuit Breaker- 02 No, CT-06 No, Bus isolator -02 No, Line isolator -04 No, BCT-01 Nos. etc. Opening of cable termination at CB and , CT end, PT end , opening of inter connection/jumper capacitor bank bay between 33 KV bus to BI to CB to CT to LI to capacitor Bank etc by opening earthing and shifting dismantled material from site to store /designated place with in S/S boundry and other associated work to complete the job satisfactory as per direction of supervising Engineer.
Erection of following equipments as per instruction manual of various equipments and technical specifications including shifting of material/equipments from store to erection site including all other associated work to complete the job satisfactorily.
132KV PT Junction box
132 KV CT junction box
T/F C&R Panel
33 KV VCB
33 KV BI/LI
33 KV CT/PT/NCT
33KV CT/PT Junction Box
Series Reactor for capacitor bank
Stringing of various main, Transfer & T/F jack bus of 132 KV/33 KV with different type conductor and different length of span mention below including fitting of tension clamp hoisting of insulators cutting of conductor and also shifting of all material form store to work site and all other associated works required for completion of job satisfactorily as per technical specification.
132 KV Jack Bus with 3x Panther (Approx 20Mtr section)
132 KV Main Bus 3x Moose (Approx 25 Mtr section)
132 KV Transfer Bus with 3x Panther (Approx 25Mtr section)
Stringing of 33 KV Main bus 3x Moose (Approx 28 Mtrs section)
Stringing of 3x panther Jack Bus for capacitor bank (Approx 28 Mtrs section)
Stringing of 3x panther Trasfer Bus (Approx 28 Mtrs section)
Making of new jumpers of 132 KV & 33KV C.B., C.T., ,Isolator and LA Including Capacitor bank by the single/Twin Moose/Zebra/Panther conductor with cutting bending and shaping of conductor along with shifting of material from site store to work place.
Providing inter connection diagram and cable schedule as per drawing to complete above job including C.B., C.T., Isolator, Panel and Transformer.etc.
Laying of following sizes of control cable in the cable trench from control relay panel to various equipments/marshalling boxes/junction box etc. in switchyard as per cable schedule, their saddling at every 750mm distance with M.S. saddles of size 25x3mm size including carriage of cable drums from store to laying site and shifting back the remaining material to store and all other associated work to complete the job satisfactorily as per technical specification.
6x2.5 Sq. mm.
4x2.5 Sq. mm.
2x2.5 Sq. mm.
Termination of following sizes of cable as laid above as per cable schedule including making necessary holes in glands plates or box wherever required. Supply and fixing of cable glands of appropriate size, supply and providing ferrules and Nos. for each core. (The rates of termination of control cable include the all cores of cable at one end with lug)
6x2.5 Sq. mm.
4x2.5 Sq. mm.
2x2.5 Sq. mm.
Cutting, straightening bending & laying 800mm below inside ground and above ground of following size M.S. flat for earthing of main and auxiliary structure, equipment structure etc. including welding with main earthmat and with object to be earthed excavation of trenches, its back filling, painting and all other associated work as required to complete the work satisfactorily excluding the cost of M.S. flat.
To make earthing for L.A. with 06 Nos. Electrode of 03 meter long M.S. round including cutting, welding and making electrode and making a rectangle with 75x10mm M.S. flat inside earth below 0.8mtr. deep including excavation and refilling of soil with T&P and labour etc for completion satisfactorily.
Laying of 40/36 mm size M.S. round bar 600 mm below ground level including cutting, straightening welding, painting of joints with bitumen black Japan paint, excavation of trench, its back filling and all other associated work to complete the work satisfactorily as per drawing and technical specification (excluding the cost of MS bar) work includes providing and fixing of 100 mm long, 50X50X6 mm MS angle (4 Pcs) at each cross joint of earth mat as per direction of supervising engineer to complete the job satisfactorily.
Fabrication of 3 meter long Electrodes with the 40 mm/36mm MS rod having 150 MM long conical shape and then its piercing vertically inside the ground with top 600 mm below ground level and its welding with main earthmat excluding the cost of MS bar, providing anf fixing 50x50x6 angle 100 mm pieces for each joints as per direction of supervising engineer to complete the job satisfactory.
Sorting/counting/stacking erection mark wise and proper loading of GI substation structure (CCM,CGM, ALP, ABL, BCT,AXM, BTM, ATM, BBL, BTI, ) etc. in trucks / trailor at EFU Nainy Allahabad and Safe carriage of loaded structure from EFU Nainy Allahabad to 132 KV S/S Vrindavan Under ETD Mathura. App. 600 Km and Unloading of carriage structure from the trucks/trailor at132 KV S/S Vrindavan Under ETD Mathura. Its sorting, counting and proper stacking at the S/S premises as per direction of supervisory engineer to complete the job satisfactorily (Appr. weight of 21 MT)
Erection of capacitor bank unit (1X5 MVAR) by erecting of its structure with the help of post insulators, Nut and bolts and then fixing of cells properly and jumpering between each cells and all other associated works required for completion of job satisfactorily as per direction of supervising engineer.
Preparation of Inter connection diagram and cable schedule as per drawing to complete the job of cable termination of capacitor bank completely
Providing and fixing of retro reflective sign board of size 3ftx2ft made out of 2mm thick aluminum sheet, face to fully covered with 3M DG cube retro reflective sheet of green colour. The letters and symbols shall be computer cut and in white colour. Board is to be supplied along with the back support from of size 35x35x5mm & two legs for grouting. Backside of aluminum sheet shall be painted with stove enamel black paint for new 63 MVA, 132/33KV Transformer-III. Language for writing will be provided by the department (UPPTCL).
Fabrication of hut type fire bucket stand made of MS angle of size 40x40x6 mm and ISI mark MS roofing sheet, having arrangment for hanging 10 buckets. All the metal surfaces should be painted with one coat of red oxide and two coats of first quality post office red synthetic enamel paint of Asian Paints/Nerolac/Berger. " FIRE" in 25 cm should be written in white color on the top of the both side of roof after painting in red colour. All the material including MS angle shall be provided by the contractor at his own cost.
Providing fire buckets of 9 ltr capacity as per IS 2546, buckets should be painted inside by white and outside by post office red colour; ear and handle by black color with two coats of first quality synthetic enamel paint after one coat of red oxide, from Asian Paints/Nerolac/Berger. "FIRE" and "AGNI (Hindi)" in 10 cm font in white color should be written on opposite sides of buckets. All the material shall be provided by the contractor at his own cost.
Shifting ,loading,carrage.unloading & shifting of 30/20 KL capacity T/f oil empty tank from Any S/S under ETD Mathnura At 132 kv S/s vrindavan.
Erection and Comissioning of 63 MVA Transformer
Shifting of main tank of 63 MVA,132/33 KV transformer from unloading place to the plinth distance about 20 meter including turning of tank, if required , including all T&P and all other works required to complete the job satisfactorily.
Additional shifting of approx. 5 Mtrs or part thereof. if any.
Draining out fresh transformer Oil from 209 Ltr. drums to 20 KL tank. (App. 29 Drums)
Complete erection of 63 MVA capacity transformer by erection of radiators conservator tanks, all bushing, turrets, connecting oil pipe lines, cooling fans, motor drive mechanism of tap changer, RTCC panel, etc to complete the job satisfactory.
Erection of 63 MVA T/F, 132/33 KV T/F Control and relay Panel
Centrifuging of transformer oil in transformer main tank for 72 hours by 10 KL/Hour capacity centrifuging machine, to be arranged by the contractor alongwith operator and taking the B.D.V values of the oil periodically till the required value is achieved as per direction of supervising engineer.
Earthing of 63 MVA T/F HV and LV Neutrals, Body, Marshaling box, Drive mechanism etc. with 75X10/50X6 MS flat (To be provided by department) including, bending, cutting & welding etc.
Delta earthing for 63 MVA T/F after fabrication of delta set with 3 nos. 40mm/36mm dia size 3 mtrs. long electrodes their placing inside the ground at distance of 3 Mtr. to each other in delta pettern and connecting all the three electrodes with 75x10mm MS flat 700mm deep and connecting the delta with T/F HV and LV neutral seprately with the help of 75x10 mm MS flat. (M.S flat and M.S rod will be arranged by the Department).
Transformer oil sample collection testing of transformer oil at CPRI/ERDA Lab Sonipath & furnishing test report for a- Dissolve Gas Analysis test -01 Nos b- Breakdown Voltage Test - 01 Nos c- Water Content Test- 01 Nos
Work of Strengthening of Lighting Arrangement
Supply & fixing of round pole of MS pipe B class 9 meter long (114.3 mm x4.5mm x5meter 88.9 mm.x3 65mm x2.0 meter, 76.1mm x3.2mm x2meter) with base plate work induded duly bainted with synthetic Aluminium enamel paint completely as outer surface of ms round pole and grouting with plinth size 300mm duly earth with MS electrode and All other associated work to complete the job satisfactory as per direction of supervising Engineer.
Supply of fixing of pole bracet of '2' dia MS pipe of B Class (ID 50mm OD 60mm.)1 2 meter long filled at angle of 30 degree suitable at 100 W LED luminaries and All other associated work to complete the job satisfactory as per direction of supervising Engineer.
Supply of fixing of 100 watt LED Lamp Crompton Greaves /Bajai/Syska/Philips make fiting including lamp and all fixtures etc. for fixing of round pole including cost of all meterial labour and T&P for completion of work. and All other associated work to complete the job satisactory as per direction of supervising Engineer.
Supply of fixing of junction box on lighting poles of sive 200x200x150 mm of MS sheet 16 SWG duly painted with synthetic enamel paint box should be fixed with 01 No 6Amp MCB and backlite terminal surip of 4 Nos terminal both should be fixed on sunmica sheet and half round M.S. Clamp with Gl pipe for fixing the junction box on the pole and All other associated work to complete the job satisfactory as per direction of supervising Engineer.
Laying of 4x2.5/6x2.5 sqmm PVC cable 50cm. Blow the ground level in PVC conduct pipe afler exavation and back fitling including all labor PVC pipe etc and All other associated work to complete the job satisfaclory as per direction of supervising Engineer.
Laying of 2x2.5 Sqmm PVC cable from fitting to junction box inside the pole and All other associated work to complete the job satisfactory as per direction of supervising Engineer.
Providing and fixing of 400 W HPSV Ballest for standard make.
Providing and fixing of 400 W HPSV lamp for standard make.
Providing and fixing of 400 W HPSV Ignitor for standard make.
Providing and fixing of 400 W 42 MFD Capacitor for standard make.
Providing and fixing of 250 W HPSV Ballest for standard make.
Providing and fixing of 250 W HPSV lamp for standard make.
Providing and fixing of 250 W HPSV Ignitor for standard make.
Providing and fixing of 250 W HPSV Ignitor for standard make.
Providing and fixing new generation energy saving and enviournemnt friendly long life versatile pressure die cast aluminium out door high beam flood light with high power 120W LEDs as light source and exclusively design poly carbonate cover satisfying IP65 standard alongwith electronic driver and complete fitting including GI pipe, clamp for round pole or GI structure, suitable for 220 V AC supply make CGL/Havells/Philips and Providing and fixing of junction box of 16 SWG MS sheet duly painted having size 150x150x200mm for above light on bottom of main structure or pole with the help of clamps junction box contain 01 No., 6Amp single pole MCB (L&T/Havells/Schneider make), 01 No. link and cable gland etc. as per specification and Laying, dressing and termination of contorl cable for the light with the help of clamps vertically on the gentry and all other associated to complete the work.
Laying of 3.5x50 sqmm LT Power cable 50 cm. blow the ground level after evacavation and to put the bricks and river sand along the side of cable and back filling. and All other associated work to complete the job satisfactory as per direction of supervising Engineer.
Providing & fixing of outdoor 3 phase Ac supply cubical box of size 1200x600x500mm duly painted with synthtics enamel paint 4 Nos. insulated bus bar for AC distributional of single phase double pole MCB of rating 16 Amp 15 No. & 100A MCB isolator 01 No. & fixing of 30 No. Terminal block of rating 16 Amp. cubical box of 16 Swg sheet in double shutter with indoor locking arrangements with wiring of proper size and phse indicator. and All other associated work to complete the job satisfactory as per direclion of supervising Engineer.
For Supply
Supply of Bolted type bus bar tension fitting suitable for Moose conductor made of LM-6 alloy Complete with ball eye socket and ‘D’ shackle single phase.
Supply of Bolted type bus bar tension fitting suitable for ACSR Panther conductor made of LM-6 alloy Complete with ball eye socket and ‘D’ shackle single phase type turn buckle in all respect.
Supply of P.G. clamp made of LM-6 alloy along with Galv. nut, bolt & washer suitable for Moose to Panther conductor.
Supply of P.G. clamp made of LM-6 alloy along with Galv. nut, bolt & washer suitable for Panther to Panther conductor.
Supply of P.G. clamp made of LM-6 alloy along with Galv. nut, bolt & washer suitable for Moose to Zebra conductor.
Supply of P.G. clamp made of LM-6 alloy along with Galv. nut, bolt & washer suitable for Zebra to Zebra conductor.
Supply of P.G. clamp made of LM-6 alloy along with Galv. nut, bolt & washer suitable for Moose to Moose conductor.
Supply of 145 KV Insulator Bus Post clamp made of LM-6 alloy along with Nut, Bolt & washer suitable for Panther conductor.
Supply of suspension fitting suitable for Moose conductor made of LM-6 alloy Complete with ball eye socket and ‘D’ shackle single phase.
Supply of suspension fitting suitable for Panther conductor made of LM-6 alloy Complete with ball eye socket and ‘D’ shackle single phase.
Supply of tinned copper bond size 15x550mm long made of 12mm multi stranded rope type 450mm long should be joined together and cramped with copper lug (20mm hole) on both ends as per sample
Supply of 33 KV spacer 150 mm for twin Zebra conductor made of LM-6 aluminum alloy both side connecting for 33 KV with 12mm dia HDG nut, bolt & washer as per technical specification.
Supply of Earthing/Discharge rod of first class insulation for system voltage upto 400 KV having total height as 7200mm (24’) one set consisting following items. (a) Earthing pole 6.5Mtr. long in four pieces made of epoxy bonded glass fiber. (b) Earthing cable 12mtr. long with transparent PVC insulated 12 mm2 dia flexiblity copper wire fitted with line end earthing clamp of all alloy suitable for 4” IPS tube Moose/Zebra conductor. (c) Canvas carry bag for above.
P&H Engineering
Hi-tech power transmission
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .