Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹1.5 CrAccepted-Finance | ₹1.5 Cr | 1 | Accepted-Finance Lowest Quoted Price Bid |
| 2 | 2₹1.8 Cr+₹34.1 L (23.2%)Accepted-Finance | ₹1.8 Cr+₹34.1 L (23.2%) | 2 | Accepted-Finance 2nd Lowest Quoted Price Bid |
| 3 | Not Admitted-Fee/PreQual/Technical | - | - | Not Admitted-Fee/PreQual/Technical Others-Work experience not in line with the required standards. |
Tender Value
₹1.8 Cr
EMD Value
₹3.6 L
Closing Date
16 Aug 2022, 4:00 pmClosed
Execurive Engineer Project Div Srinagar Right
Execurive Engineer Project Div Srinagar Right Peer Bagh near Shalimar Bakery Srinagar
SUBTRANSMISSION WORK (33/11KV) LEVEL UNDER CAPEX AT TAILBAL IN SRINAGAR CITY.
2022_PDD_178577_1
PD/SR/01 of 2022-23
Open Tender
Electrical Works
Turn-key
180 days
Tailbal Srinagar
As per SBD
5 documents required · 5 mandatory
₹5,000
Yes
Accounts Officer Projects KPDCL
₹3.6 L
Yes
2 Sept 2022
9 Jul 2022
18 Aug 2022
12 Jul 2022
16 Aug 2022
19 Jul 2022
15 Jul 2022 - 18 Jul 2022
Amount
Supply, of 33/11kV, 10 MVA ONAN, Copper wound, Out-door Type, conventional Power Transformer, Oil Filled with OLTC and all accessories including HT and LT Terminal connectors
Supply at Site of 33 kV C&R Panel along with O/C, E/F and differential relays (IEC61850), mimic diagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays, 3-phase Tri-vector meter -5 Amps, DLMS Compliant with RS-485 port for 33/11KV Power Transformer Protection (SCADA Compatible)
Supply at Site of 33 kV C&R Panel along with O/C, E/F (IEC61850), mimic diagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays, 3-phase Tri-vector meter -5 Amps, DLMS Compliant with RS-485 port for Feeder Protection (SCADA Compatible)
Supply, of 33 kV Current Transformer (33 kV, 1Φ, Multi Ratio Multi-Core, Outdoor) (1 No. per Φ)
Supply, of 30 kV Lightening Arrestors (30 kV, 10kA, Station class, ZnO,Polymer/porcelain) gap less
Supply, of 33 kV, 1250 A, Isolator with Earthing Blade
Supply, of 33 kV, 1250 A, Isolator without Earthing Blade
Supply, of33 kV Post Insulator Polymer 36kV,235kV Impulse, creepage distance 1224m
Supply, of 33 kV DO Fuse, 100 Amp.
Supply, of Porcelian/Polymerr Disc Insulator 36KV, Lightening Impulse 170kV Positive and 180kV Negative, creepage distance 900mm,min failing load 70kN for 33 KV Line Bay
Supply, of T Clamps for Panther Conductor
Supply, of Single Tension Fittings for Panther Conductor
Supply, of A.C Distribution Panel (415 V, AC) made of CRCA thickness not less than 2mm. Powder Coated, degree of protection IP43. 200 Amps Switch Fuse disconnector for incoming supply and 5 No TPN MCB's (16-125 Amps ) and 5 No DP MCBs (0-32A), rectangular busbar suitable for 200 Amps continuous Supply including indication lamps and cables and other accessories (for new receiving substation)
Supply, of DC Distribution Panel (30 V, DC) made of CRCA thickness not less than 2mm. Powder Coated, degree of protection IP43 for 2 No battery incoming supply with 2 No 63 Amps DP MCBs for incoming supply Double busbar of adequate size, 12 No DP DC MCB (0-32A) including indication lamps and cables and other accessories (for new receiving substation)
Supply of duly fabricated Galvanised Pipe Structure Nonimal Bore 200, 5.9 mm Thick for 33 KV Line Bay , Transformer Bay
Supply, of Galvanised Steel Structures Duly fabricated as per approved drawings (for 33 KV Transformer Bay, line bay, feeder gantry etc)
Supply, of GI flat for earthing 50x6 mm (for earthing risers at receiving substations)
Supply, of Yard Lighting at new Receiving Station using 4 No 12 Mtr Long GI High Mast Poles,Continuosly tapered of Octagonal of cross Section including suitable shallow raft foundation using 8 Nos non integeral flood Light Luminaire with single piece die cast Al.housing and pot optic reflector and toughened glass cover conforming to IP-66 complete with all accessories bearing Cat No SGP 438 1XODM-TT 250Watt GLA/HPL-T 250W Philips Make and Suitable Control Feeder Panel.
Supply, of Earth Wire 7/4.00 mm sq.
Supply, of 11 kv Isolator Doble break 3 pole ,600A Horizontal mount with earth switch
Supply, of Fire Fighting Equipment a) Dry Chemical Powder type (6Kg) for control room:-3No. b) Co₂ Type of 4.5 kg capacity for control room:-4No c) Co₂ type trolly mounted of 22.5Kg capacity for switch yard:-2No (at new receiving substation)
Supply, of a). Battery Bank 30 V,100 AH , of 15 No. cells of 2 V each, sealed maintenance free VRLA type,High impact Polyprophelene copolymer container,flame retardant. b). 30V,100 AH , Float-Cum-Boost Charger With Full wave rectification for 220 V, 1Phase, 50 HZ AC Input Supply . (at new receiving substation)
Supply, of 11 kV, VCB Panel Board(12KV,1250 Amp, 25 kA for 3 sec Outdoor) with O/C,E/F Relays (IEC 61850) Mimic Diagram Voltmeter, Ammeter, Annunciation Windows with annunciation relays, 3Ph Tri vector meter 5Amp DLMS Compliant with RS-485 Port.SCADA Compatible (1 Incomer Panel +3 Outgoing Panel)
Supply, of 11 KV XPLE Power Cables‐ Single Core 630 mm²
Supply, of 11 KV XPLE Power Cables‐ 3C 400 mm²
Supply, of Indoor Type Cable Termination Kit for 11 kV Single Core 630 mm² XLPE Cable
Supply, of Outdoor Type Cable Termination Kit for 11 kV Single Core 630 mm² XLPE Cable
Supply, of Supply, of Indoor Type Cable Termination Kit for 11 kV 3C 400 mm² XLPE Cable
Supply, of Outdoor Type Cable Termination Kit for 11 kV 3C 400 mm² XLPE Cable
Supply, of 12 Core 2.5 mm² Control cable copper Armoured , 1.1 kV Grade, ISI, FRLS. including lugs, ferrules etc.
Supply, of 6 Core 2.5 mm² Control cable copper Armoured , 1.1 kV Grade, ISI, FRLS. including lugs, ferrules etc.
Supply, of 2 Core 2.5 mm² Control cable copper Armoured , 1.1 kV Grade, ISI, FRLS. including lugs, ferrules etc.
Supply, of 100 KVA, 33/0.4 KV Stn. Transformer, Copper Winding, with Bimetallic Terminal Connectors, Energy Efficiency Level-II as per IS: 1180 (Part-I): 2014
Supply, of MCCB ‐ 200 Amps (with Enclosure and pole mounting arrangement)
Supply, of 120 mm² 3.5 Core LT XLPE Cable
Supply, of 9 Mtr. Long Steel Tubular Pole with welded steel base plate of Designation 410 SP -33(IS 2713, Pt I, II, III 1980.)
Supply of Safety Helmet at site
Supply at site of Rubber Gloves for 33 kV level
Supply at site of Rubber Gloves for 11kV level
Supply at site of Safety Belt
Supply at site of Safety Shoes
supply at site of Rubber Mat 1mx2m 19mm thick
Supply at site of Earthing rod (set of 3 rods)
Supply at site of HV Detectors all voltages
Supply at site of Earthing Mat (GI flat 50mm x 12mm)
Supply at site of Earthing Electrode 3m long, 40mm dia GI pipe through GI stirip 50 x6mm
Installation Testing and Commisioning of 33/11kV, 10 MVA ONAN, Copper wound, Out-door Type, conventional Power Transformer, Oil Filled with OLTC and all accessories including HT and LT Terminal connectors
Installation Testing and Commisioning of 33 kV Vacuum Circuit Breaker (36 kV, 1250A, 26.2 kA, Outdoor Type) (Departmental Supply).
Installation Testing and Commisioning of 33 kV C&R Panel along with O/C, E/F and differential relays (IEC61850), mimic diagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays, 3-phase Tri-vector meter -5 Amps, DLMS Compliant with RS-485 port for 33/11KV Power Transformer Protection (SCADA Compatible)
Installation Testing and Commisioning of 33 kV Current Transformer (33 kV, 1Φ, Multi Ratio Multi-Core, Outdoor) (1 No. per Φ) (3 no deptt supply and 3 no TKC supply)
Installation, Testing and Commisioning of 33 kV Voltage Transformer (33 kV/110 V, 1Φ, Multi-Core, Outdoor), (1No. per Φ) (Departmental Supply).
Installation, Testing and Commisioning of 30 kV Lightening Arrestors (30 kV, 10kA, Station class, ZnO,Polymer/porcelain) gap less
Installation Testing and Commisioning of 33 kV, 1250 A, Isolator with Earthing Blade
Installation Testing and Commisioning of 33 kV, 1250 A, Isolator without Earthing Blade
Installation Testing and Commisioning of33 kV Post Insulator Polymer 36kV,235kV Impulse, creepage distance 1224m
Installation Testing and Commisioning of 33 kV DO Fuse, 100 Amp.
Installation Testing and Commisioning of Porcelian/Polymerr Disc Insulator 36KV, Lightening Impulse 170kV Positive and 180kV Negative, creepage distance 900mm,min failing load 70kN for 33 KV Line Bay
Laying of 200 sqmm ACSR Conductor (for 33 kV Line Bay, 33KV bus and Transformer Bay at receiving substation) deptt supply
Installation Testing and Commisioning of T Clamps for Panther Conductor
Installation Testing and Commisioning of Single Tension Fittings for Panther Conductor
Installation Testing and Commisioning of A.C Distribution Panel (415 V, AC) made of CRCA thickness not less than 2mm. Powder Coated, degree of protection IP43. 200 Amps Switch Fuse disconnector for incoming supply and 5 No TPN MCB's (16-125 Amps ) and 5 No DP MCBs (0-32A), rectangular busbar suitable for 200 Amps continuous Supply including indication lamps and cables and other accessories (for new receiving substation)
Installation Testing and Commisioning of DC Distribution Panel (30 V, DC) made of CRCA thickness not less than 2mm. Powder Coated, degree of protection IP43 for 2 No battery incoming supply with 2 No 63 Amps DP MCBs for incoming supply Double busbar of adequate size, 12 No DP DC MCB (0-32A) including indication lamps and cables and other accessories (for new receiving substation)
Erection of Galvanised Pipe Structure Nonimal Bore 200, 5.9 mm Thick for 33 KV Line Bay , Transformer Bay (Deptt Supply 1.5MT and TKC supply 1.3MT)
Erection of Galvanised Steel Structures for 33 KV Line bay,Transformer Bay,feeder gantry, station transformer etc ( 2 MT Departmental supply and TKC supply 6 MT)
Installation Testing and Commisioning of GI flat for earthing 50x6 mm (for earthing risers at receiving substations)
Installation Testing and Commisioning of Yard Lighting at new Receiving Station using 4 No 12 Mtr Long GI High Mast Poles,Continuosly tapered of Octagonal of cross Section including suitable shallow raft foundation using 8 Nos non integeral flood Light Luminaire with single piece die cast Al.housing and pot optic reflector and toughened glass cover conforming to IP-66 complete with all accessories bearing Cat No SGP 438 1XODM-TT 250Watt GLA/HPL-T 250W Philips Make and Suitable Control Feeder Panel.
Installation Testing and Commisioning of Earth Wire 7/4.00 mm sq.
Installation Testing and Commisioning of 11 kv Isolator Doble break 3 pole ,600A Horizontal mount type with earth switch
Installation Testing and Commisioning of Fire Fighting Equipment a) Dry Chemical Powder type (6Kg) for control room:-3No. b) Co₂ Type of 4.5 kg capacity for control room:-4No c) Co₂ type trolly mounted of 22.5Kg capacity for switch yard:-2No (at new receiving substation)
Installation Testing and Commisioning of a). Battery Bank 30 V,100 AH , of 15 No. cells of 2 V each, sealed maintenance free VRLA type,High impact Polyprophelene copolymer container,flame retardant. b). 30V,100 AH , Float-Cum-Boost Charger With Full wave rectification for 220 V, 1Phase, 50 HZ AC Input Supply . (at new receiving substation)
Installation Testing and Commisioning of 11 kV, VCB Panel Board(12KV,1250 Amp, 25 kA for 3 sec Outdoor) with O/C,E/F Relays (IEC 61850) Mimic Diagram Voltmeter, Ammeter, Annunciation Windows with annunciation relays, 3Ph Tri vector meter 5Amp DLMS Compliant with RS-485 Port.SCADA Compatible (1 Incomer Panel +3 Outgoing Panel)
Installation Testing and Commisioning of 11 KV XPLE Power Cables‐ Single Core 630 mm²
Installation Testing and Commisioning of 11 KV XPLE Power Cables‐ 3C 400 mm²
Installation Testing and Commisioning of Indoor Type Cable Termination Kit for 11 kV Single Core 630 mm² XLPE Cable
Installation Testing and Commisioning of Outdoor Type Cable Termination Kit for 11 kV Single Core 630 mm² XLPE Cable
Installation Testing and Commisioning of Installation Testing and Commisioning of Indoor Type Cable Termination Kit for 11 kV 3C 400 mm² XLPE Cable
Installation Testing and Commisioning of Outdoor Type Cable Termination Kit for 11 kV 3C 400 mm² XLPE Cable
Installation Testing and Commisioning of 12 Core 2.5 mm² Control cable copper Armoured , 1.1 kV Grade, ISI, FRLS. including lugs, ferrules etc.
Installation Testing and Commisioning of 6 Core 2.5 mm² Control cable copper Armoured , 1.1 kV Grade, ISI, FRLS. including lugs, ferrules etc.
Installation Testing and Commisioning of 2 Core 2.5 mm² Control cable copper Armoured , 1.1 kV Grade, ISI, FRLS. including lugs, ferrules etc.
Installation Testing and Commisioning of 11 kV LA Station Type (Departmental Supply).
Installation Testing and Commisioning of 100 KVA, 33/0.4 KV Stn. Transformer, Copper Winding, with Bimetallic Terminal Connectors, Energy Efficiency Level-II as per IS: 1180 (Part-I): 2014
Installation Testing and Commisioning of MCCB ‐ 200 Amps (with Enclosure and pole mounting arrangement)
Installation Testing and Commisioning of 120 mm² 3.5 Core LT XLPE Cable
Erection of 9 Mtr. Long Steel Tubular Pole with welded steel base plate of Designation 410 SP -33(IS 2713, Pt I, II, III 1980.)
Installation,testing and commisioning of Earthing Mat incl risers (complete job)
Installation,testing and commisioning Earthing Electrode 3m long, 40mm dia GI pipe through GI stirip 50 x6mm
Modification/Canibalization/refabrication of GI items supplied by the department where ever Necessary
Supply at site 11 Mtr. Long Steel Tubular Pole with welded steel base plate of Designation 410 SP -56(IS 2713, Pt I, II, III 1980.)
Supply and Painting of Red Oxide at sites
Supply and Painting of Aluminium Paint at site
Supply at site Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI strip
Supply at site PG Clamps for Wolf Conductor
Supply at site 33kV Polymer composite/Porcelain Pin Insulator 36kV, 10kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm
Supply at site GI V cross-arm with top Bracket including clamp
Supply at site GI Channel X-arm including clamps and braces
Supply at site Galvanised Nuts & Bolts with washers
Supply at site 33 kV Danger Plates with Clamps
Supply at site Anti-Climbing Device (GI Barbed Wire) with Clamps
Supply at site Galvanised Stay Set with 50 x 8 mm stay clamp,guy insulator (2Nos.) , anchor plate (300x 300 x 8 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 20 mm diameter solid GS stay rod & 7/4.00 mm dia GI stranded wire complete
Erection of 11 Mtr. Long Steel Tubular Pole with welded steel base plate of Designation 410 SP -56(IS 2713, Pt I, II, III 1980.)
Installation Testing and commissioning of Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI strip
Laying Testing and commissioning of 150 sqmm ACSR Wolf Conductor (Deptt supply)
Installation Testing and commissioning of PG Clamps for Wolf Conductor
Installation Testing and commissioning of 33kV Polymer composite/Porcelain Pin Insulator 36kV, 10kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm
Erection of GI V cross-arm with top Bracket including clamp
Erection of GI Channel X-arm including clamps and braces
Installation Testing and commissioning of Galvanised Nuts & Bolts with washers
Installation Testing and commissioning of 33 kV Danger Plates with Clamps
Installation Testing and commissioning of Anti-Climbing Device (GI Barbed Wire) with Clamps
Installation Testing and commissioning of Galvanised Stay Set with 50 x 8 mm stay clamp,guy insulator (2Nos.) , anchor plate (300x 300 x 8 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 20 mm diameter solid GS stay rod & 7/4.00 mm dia GI stranded wire complete
Cement Bottoming1:2:4 mix as per REC Standards
NOTE: 1. All the supplies/Erections should be as per the approved drawings. 2. Supply: All inclusive means exworks price, frieght, packaging, insurance, delivery at sites and other applied duties without GST. 3. Installation/testing/commissioning: All Inclusive means erection charges at site including pre-commisioning and final commissioning tests. 4. Intersee position of bidders shall be determined by the total package cost.
M AND COMPANY ENGINEERS AND CONTRACTORS PRIVATE LIMITED
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .