Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹15.2 LAccepted-AOC 25 A BR SAMY LANE KATTOOR COIMBATORE 641009 | COIMBATORE | COIMBATORE | TAMIL NADU | 641009 | L1 | Accepted-AOC Being lowest | |
| 2 | L2₹15.8 L+₹61,542.27 (4.05%)Rejected-AOC 1A BASEMENT 30 31 RAJA HOUSE NEHERU PLACE NEW DELHI | NEW DELHI | NEW DELHI | DELHI | L2 | Rejected-AOC Not being lowest | |
| 3 | L3₹19.6 L+₹4.4 L (29.2%)Rejected-AOC 704 SILVER DEAL DAFFODIL WING 1 B T KAWADE ROAD PUNE 411 001 | PUNE | PUNE | MAHARASHTRA | 411001 | L3 | Rejected-AOC Not being lowest |
Tender Value
₹14 L
EMD Value
₹28,000
Closing Date
15 Apr 2023, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
CWE WELLINGTON
Headquarters Commander Works Engineers Wellington, Barracks Post The Nilgiris PIN 643 231
COMPLETION OF INCOMPLETE WORK FOR PROVN OF STANDBY POWER SUPPLY TO ITRC AND DR SITE WORKS UNDER GE DSSC WELLINGTON
2023_MES_586073_1
84614/E8
Open Tender
Electrical and Maintenance Works
Item Rate
120 days
WELLINGTON
For MES Enlisted Contractors Class E, Category b (i)
For other contractors Meeting Enlistment Criteria of MES for Class E, Category b (i)
7 documents required · 7 mandatory
₹500
GE DSSC WELLINGTON
₹28,000
12 May 2023
16 Mar 2023
17 Apr 2023
16 Mar 2023
15 Apr 2023
1 Apr 2023
17 Mar 2023 - 24 Mar 2023
Amount
Supply, installation, commissioning & testing of silent built in within an acoustic enclosure diesel engine driven generating set water cooled including customized AMF panel for standby power supply 415 volts, 03 Phase, 4 wire, 50 cycles/sec, 100 KVA (80.0 KW) at 0.8 power factor perfectly suitable for outdoor mounting (open to air) at an altitude of 1850.0 Mtr above MSL (Mean Sea Level) & suitable for starting at a temperature of - 3 degree C complete with alternator directly coupled to diesel engine, mounted on common base frame & complete with self starter, fuel tank capacity not less than 08 hours fuel requirement & battery as per OEM, battery leads, sound proof canopy, cold starting kit & confirming to latest CPCB norms with features for automatic shutdown in the event of a circuit failure condition arising from low lube oil pressure, high engine temperature, over/under speed etc. with & including Microprocessor based genset controller with the following undermentioned features & complete all as specified and as directed. (a) Graphical LCD display. (b) Operator interface. (c) Suitable to provide a record of most recent fault conditions & fault history. (d) Complete alternator data viz, voltage ph - ph, ph - neutral, current, KVA , KW, frequency, PF etc. (e) Complete engine data viz, starting battery voltage, engine temp, engine runnning hours, engine oil pressure etc. (f) Battery charging condition, fuel usage, AMF feature etc. (g) Control incl provn of service adjustment & calibration of DG control functions. GENSET SPECIFICATIONS: NO OF PHASES : 03 POWER FACTOR : 0.8 (LAG) FREQUENCY : 50 HZ VOLTAGE : 415 V, 3 PH
ENGINE SPECIFICATIONS : PRIME MOVER RATING : 100 KVA / 80.0 KW ASPIRATION : TA NO OF CYLINDERS : 04 RPM : 1500 (Model - 4K 1080TA G2 of Make: KOEL or techno commercially equivalent) ALTERNATOR SPECIFICATIONS : IP PROTECTION : IP 23 INSULATION CLASS : H CLASS (Make: KOEL or techno commercially equivalent) CONFORMANCE STANDARDS : IS 4722, IS 1460, ISO 8528, ISO 3046, IS 13018, IS/IEC 60034-1, IS 10002, BS 5514, CPCB-II etc. Make, Size & No of Battery : As per OEM. AMF PANEL SPECIFICATIONS (Outdoor Type) : TNEB I/C : MCCB 4P (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting having breaking capacity 36 KA of rating 200A - 01 Nos. DG I/C : MCCB 4P (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting having breaking capacity 36 KA of rating 200A - 01 Nos. AMF MAIN O/G : MCCB 4P (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting having breaking capacity 36 KA of rating 200A - 01 Nos. The size/rating of all the connected accessories viz. Contactors, relays, timers, bus-bars, connecting cables etc. of the AMF Panel shall be as per OEM & in conformity with the I/C & O/G MCCBs duly provided with bypass system/arrangement complete.
IMPORTANT NOTES : (1) Design/drawing/BOM of the AMF panel & DG SET showing the dimensions is to be obtained from DG SET/Panel board manufacturer/Auth supplier & is to be got approved from Engr-in-charge & GE before placing final order to the manufacturer. (2) The electrical connection of digital Multi Functional Meter in the AMF panel is to be done from load side so that monitoring of various parameters viz. Voltage, Current, KW, KVA, power factor, frequency etc. can be done for both SEB mains & DG mains. (3) The cost of periodical/routine servicing including minor repairs/replacement such as topping up of coolant, engine/lube oil, diesel as well as lube-oil filters including periodical checking of the complete DG set & AMF panel for the complete defect liability period from the authorized Service Dealer as & when required/due is deemed to be included in the unit quoted rates. (4) The complete installation, commissioning & testing of the DG Set & AMF Panel is to be got done from the OEM or their auth Rep/Sister Concern/Channel Partners only. (5) Anything missed out in the technical specifications but technically required for efficient working of the DG Set & AMF Panel is deemed to be included in the quoted rates. (6) Necessary PCC foundation/plinth for DG set is already existing at site. (7) The quoted rate shall be deemed to be inclusive of 12 Hrs test run at site as specified in the PS in presence of rep of Accepting Officer, all testing arrangements / equipments, resistive load including POL shall be made available by the contractor. (8) The approximate distance between the DG Set & the AMF Panel shall be within 20 Mtrs & the cost of control cabling etc. from DG Set to the AMF Panel is deemed to be included in the unit quoted rates. (9) The quoted rate is deemed to be inclusive of any Addn/Altn reqd on grounds/site for proper installation/Commissioning of the DG set. (10) Firm is required to visit the site of work for any doubts/clarifications wrt specifications/qty etc before quoting of the tender. Any query/clarifications etcafter conclusion of the contract shall NOT be entertained & decision of the AO shall be final & binding.
M&L for earthing complete with GI plate electrode 600 x 600 x 6.0 mm thick buried directly in ground (in vertical position) earth pit not less than 2.25 mtr below normal ground level with the top edge of the earth plate not less than 1.5 mtr (B.G.L.) and connected to GI strip 32 x 6 mm by means of bolts, nuts, check nuts, and washers of galvanized iron including PCC chamber & cover with suitable handle, including necessary excavation and earth work in any type of soil, 20 mm dia med grade galvanized steel tube for watering with one end fixed with cast iron funnel and wire mesh, 40 mm bore medium grade galvanized steel tubing for drawing earth lead GI strip for protection & common salt, charcoal in alternate layers etc. complete all as shown in EP No 3 of SSR Part 1 and testing on completion complete all as specified and as directed.
S&F 40 mm dia GI pipe light grade, fixed on walls, floors under ducts/culverts etc. for protection of earthing lead/cables etc. complete all as specified and as directed.
S&F 80 mm dia GI pipe light grade, fixed on walls, floors under ducts/culverts etc. for protection of cables etc. complete all as specified and as directed.
M&L for cutting the existing hard standing/PCC/WBM road at a depth not less than 45 cm and 25 cm in width for passing of cable through GI pipe, returning filling in, complete including finishing the surfaces by providing cement concrete type B-1 (1:2:4) with 20 mm grade aggregate upto 20 cm, finishing to a uniform smooth surface complete all as specified & as directed by Engr-In-Charge.
Supply, laying & testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables, heavy duty with stranded aluminum conductor, 1100 volts grade, of size 70 sq mm, 3.5 core complete all as specified and as directed.
Supply, laying & testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables, heavy duty with stranded aluminum conductor, 1100 volts grade, of size 25 sq mm, 4.0 core complete all as specified and as directed.
Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m in depth for laying of pipe and getting out in hard/dense soil complete all as specified and as directed.
Returning, filling in including spreading, levelling, watering and well ramming in layers not exceeding 25cm thick complete all as specified and as directed.
Removing of excavated material not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and as directed.
M&L for providing sand cushioning for protection of UG cable in trenches with dry coarse sand approved quality including filling, spreading and punning down to desired thickness complete all as specified and as directed.
Supply and laying sub class "B" bricks in trenches for protection of UG Cable complete all as specified and as directed.
MONA GENERATOR SEVICES PVT. LTD.
M/S - KRUPA ELECTRICALS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .