Combined Package of (Work -A) Strengthening of 66kV Bus-bar and strengthening of 66kV Bay at 66/11kV KIKKERI S/s in K.R.Pete Taluk Mandya District on Total Turn Key (TTK) basis. (Work-B) Providing 01 no of additional 11kV MCVCB bus coupler between 11kV Bank-1 and Bank-3 at 66/11kV KIKKERI S/s in K.R.Pete Taluk Mandya District on Partial Turn Key (PTK) basis including supply of all matching materials/equipment(except 11kV switchgear) and erection & including civil works of all materials/equipment, testing and commissioning.
KPTCL/2025-26/SS/WORK_INDENT2538
KPTCL/2025-26/SS/WORK_INDENT2538
Open
Sub-Station
Two Tender Document System(Two Cover)
KPTCL CEE Transmission Zone Office Mysuru
17 documents required · 15 mandatory · 2 optional
Past Experience Documents (if any) such as LOI or LOA, DWA, Work Done Certificate, Performance Certificates from KPTCL and Non-KPTCL in last 05 years as per KW-1 (not compulsory)
valid Super grade Electrical Contractor License issued by the Government of Karnataka as on the date of opening of techno-commercial bid (refer 2.3 of ITT)
Construction equipment owned by the tenderer and equipment proposed to be deployed on this contract, if awarded
Reports on the financial standing of the tenderer, such as profit and loss statements and auditors reports for the last five years as per 3.10(iv) of ITT.
Qualification and experience of the key technical and management personnel in permanent employment with the tenderer and those that are proposed to be deployed on this contract, if awarded as per 3.10(xv) of ITT.
3.6: Tenderers who meet the above specified minimum qualifying criteria, will only be qualified, if their available tender capacity is more than the total tender value. The available tender capacity will be calculated as under:Assessed Available Tender Capacity: (AxNx1.5-B)Where A-Maximum value of works executed (KPTCL & Non-KPTCL) in any one year during the last five years (updated to FY 2024-2025) taking into account the completed as well as works in progress.
3.7: Even though the Tenderers meet the above criteria, they are subject to be disqualified if they have:- Made misleading or false representations in the forms, statements and attachments submitted in proof of the qualification requirements and/or- Record of poor performance such as abandoning the works, not properly completing the contract, inordinate delays in completion, litigation history, or financial failures etc. and/or- Participated in the previous Tender for the same work and had quoted unreasonably high Tender prices and could not furnish rational justification.
Minimum Average Annual Turnover (MAAT) of the bidder for best two years out of last preceding five financial years ending on March or December as the case may be, shall not be less than Amount put to Tender (ABT) as per 3.2(a) of std tender documents(ITT).
as per 3.10(iv) of ITT ( with UDI Number )
Bidder shall ensure that soft copies of No Deviation CERTIFICATE, Letter of Undertaking, as revised in Annexure , Any other undertaking / agreement (if applicable) are uploaded besides submitting the Originals to the office of the Chief Engineer, Electy., Operation, KPTCL, Mysore, after the last submission date and on or before the date & time of opening of techno commercial bids.
The bidder should furnish the works on hand details as per 3.10(v) of ITT.
Bidder shall ensure that soft copies of i. Letter of undertaking for Non performance ii. Letter of undertaking for Risk and Cost iii. Letter of undertaking for Litigation iv. Letter of undertaking to source the supply of equipment material from KPTCL approved Vendors only (if applicable) are uploaded besides submitting the Originals to the office of the Chief Engineer, Electy., Operation, KPTCL, Mysuru, after the last submission date and on or before the date and time of opening of techno commercial bids as per 3.10(xviii) of ITT
i. Letter of undertaking to source the equipment/material for the work from the approved Vendors who meet the eligibility clauses regarding restrictions on procurement from a country which shares a land border with India (Annexure-XVI) ii. Letter of undertaking as per clause No.1.5 of Annexure-XVII iii. Letter of undertaking as per clause No.1.6 of Annexure-XVII (if applicable) are uploaded besides submitting the Originals to the office of the Chief Engineer, Electy., Operation, KPTCL, Mysuru, after the last submission date and on or before the date and time of opening of techno commercial bids.
ESI certificate
EPF certificate
Bidder shall upload selfdeclaration stating that no such actions against the bidder haven been taken by KPTCL in the last 6 months as on date of bid submission invoking Risk & cost, failing which the offer is liable to be rejected (refer clause 3.10(ii) of ITT.
Any other required documents as per the terms and conditions of the tender.
Shall be uploaded besides submitting the ATTESTED xerox copies of same to the office of the Chief Engineer, Electy., Operation, KPTCL, Mysuru, after the last submission date and on or before the date and time of opening of techno commercial bids.
₹500
₹38,105
5 Sept 2025
5 Sept 2025
20 Sept 2025
12 Sept 2025
8 Sept 2025
Work-A (in Combined Package) Strengthening of 66kV Bus-bar and strengthening of 66kV Bay at 66/11kV KIKKERI S/s in K.R.Pete Taluk Mandya District on TTK basis
Single Tension string of 90 KN. 6 units with pins each along with hardware suitable for Single Drake ACSR.(66 kV) (6Nos insulator+70/90kN,16mm bolted type tension clamp=(593*+298)*6+2426)=7772.00
C-Type wedge connector (T-type) suitable for Drake-Drake
C-Type wedge connector Coyote to Drake ACSR Conductor
CT Clamps for Single Drake
Pad Clamps for Isolators suitable for drake conducturs
Terminal Connector Clamps for Bushings
of Power Transformers Suitable for 72.5 kV class bushing to suit Single Drake conductor
66 KV breaker terminal connector -Drake 4 hole paddle ACSR Conductor : 895 A
Terminal Connector Clamps for
suitable Single Drake conductor( for Surge Arrester) and 6 Nos for PI supprting Insulator
Fabrication, galvanising and supply of Steel Pole Structure (Monopole) : (including cross arms, base plate with anchor bolts, anticlimbing device, step bolts and bolt & nuts/ladder and all other equip...
Supply Of Gi Bolt Nuts of suitable size
Busbar formation: Releaseof Main bus/cross bus (all the three phases in a segment) using Drake single conductors with fixing of insulator spacers, levelling of string conductors to the required height...
Busbar formation: Re-Erection of same Main bus/cross bus (all the three phases in a segment) using Drake single conductors with fixing of insulator spacers, levelling of string conductors to the requi...
Strenghtening of equipment connections of 66kV line/transformer bays, using suitable terminal connectors and drake conductor of line/Isolators/CTs/LAs/Breakers/Power transformrs
(inclusive of releasi...
Erection, assembly and alignment of Station structure as per the directions of site Engineer
Crane hiring charges for Sub-station works ( loading of released conductor and insulators at Kikkeri and unloading at Hooagalli store )
Transportation of released materials using 10 MT lorry from Kikkeri Substation to Hootagalli Store .(70kM from Hootagalli store to Kikkeri*2)
Work-B (in Combined Package) Providing 01 no of additional 11kV MCVCB bus coupler between 11kV Bank-1 and Bank-3 at 66/11kV KIKKERI S/s in K.R.Pete Taluk Mandya District on PTK basis
11KV UG cable 1Cx1000 Sq mm
a) 11 KV Heat shrinkable cable termination kit for XLPE Cable Outdoor 1Cx1000 Sq mm
b) 11 KV Heat shrinkable cable termination kit for XLPE Cable Indoor 1Cx1000 Sq mm
11KV GOS D/B 1200Amps
Multi Function Transducers(MFT)
As per KPTCL Std, Interface: RS-485 Daisy Chain to RTU Com port,wiring: Both 3ph 4wire, supply: self powered, Measuring range voltage: 120%, current: 120%,...
Input Vtg:110V DC, input indicated by LED, input range 110VDC to 140V DC, sourcing Vtg output 48VDC, No of iputs: 12, No of outputs: 8, Source current: 5mA, at output, 8way switch to be p...
Terminal Blocks (knife type)
(8 TB's per Feeder) = (8x1 nos = 8)
Current Cable - 2.5 Sq-mm multistrand copper wire for CT termination
(Each color 15mtrs-R-Y-B) (15mts x 3 x 2 feeders = 90mtr)
Control Cable - 10 Copper core x 1.5sqmm
(From remote contol desk to RTU) (15mtrs x 2 feeders = 30mtrs)
Signal Cable - 10 Copper core x 0.5sqmm
Feeder to Feeder loop = 5mts x 2feeder =10mtrs)
Remote control desk to RTU (for DI): 15mtrs x 2 feeders = 30mtrs
1.5 Sqmm Grey wire for interfacing of DI and DO
(20 mtrs for each panel)(20x2=40mtr)
Supplying tinned copper lugs and crimping and wiring to terminal point for wire of the size 2.5 sqmm (80 lugs/panel x 2 = 160)
C-type channel of size 50x100x50x6mm
(50cm/panel) = (0.5m x 2 nos = 1 Mtrs)
Supplying and fixing of heavy duty cable glands suitable for UG cable of 1.1 KV class (metal only) (Size: 32mm dia)
CT TBs - 6 nos for each panel (2 x 6 = 12 nos)
11KV, MCVCB, 500MVA, 31.5KA, 2000A Incomer 800A feeder
11KV UG cable 1Cx1000 Sq mm
a) 11 KV Heat shrinkable cable termination kit for XLPE Cable
Outdoor 1Cx1000 Sq mm (indoor & outdoor)
11KV GOS D/B 1200Amps
Loading of 11kv switchgear (2In+4Feeder+ 1 CB+2ADP) and other materials etc for s/s works
Transportation of released MCVCBs, CTs, ,and 11Kv structurs etc from site to stores using 10MT Lorry upto 150kms
Multi Function Transducers(MFT)
As per KPTCL Std, Interface: RS-485 Daisy Chain to RTU Com port,wiring: Both 3ph 4wire, supply: self powered, Measuring range voltage: 120%, current: 120%,...
Input Vtg:110V DC, input indicated by LED, input range 110VDC to 140V DC, sourcing Vtg output 48VDC, No of iputs: 12, No of outputs: 8, Source current: 5mA, at output, 8way switch to be p...
Control Cable - 10 Copper core x 1.5sqmm
(From remote contol desk to RTU)(15mtrs x 2 feeders = 30mtrs)
Signal Cable - 10 Copper core x 0.5sqmm
Feeder to Feeder loop = 5mts x 2feeder =10mtrs)
Remote control desk to RTU (for DI):15mtrs x 2 feeders = 30mtrs
1.5 Sqmm Grey wire for interfacing of DI and DO
(20 mtrs for each panel)(20x2=40mtr)
CT TBs - 6 nos for each panel (2 x 6 = 12 nos)
Configuration of RTU and Engineering along with validation of data at SLDC
11KV Switchgear, MCVCB, 500MVA, 25KA, 1250A Incomer 800A feeder
a) Feeder panel (With CTs of 200-100/1-1A) b) Adapter Panel 1250A (for Megawin to MEI) Annunciation & Remote control panel (1IC+4F)
Wiring & Assisting in Testing and Commissioning
11 kV MCVCB Switchgear
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
Kikkeri work A&B BOM.pdf
Others - Bill of Materials BOM • 0.16 MB
Work on Hand details format (Tender).doc
Others - Works on hand • 0.06 MB
NIT - Kikkeri work A&B.pdf
Others - NIT • 0.52 MB
Tender documents - Kikkeri work A&B.docx
Tender Document • 0.37 MB
Volume II A and B.zip
Technical Information / Worksheet • 19.98 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .